CAUTION

DO NOT remove LEONICS NB-series/NBP-series UPS cover for repairing

by  yourself.  Complicated electronic devices inside the UPS may be

damaged or caused hazard to life.  Repairing is only referred to technician.

1.1 Electrical Safety

1.1.1 Do not work alone where there is danger of shock.

         1.1.2

Contact with live conductors will cause burns and dangerous electric shock.

         1.1.3

Please allow ONLY a certified electrician to wire your system permanently.

         1.1.4

Periodically check your cable, outlets and power source to make sure that they

                       are in good condition.

1.1.5 To reduce risk from electric shock if you can not find the electrical ground of

                       the building, unplug the UPS from the AC source before plug in your load at

                       the rear side of the UPS. Then, plug in the UPS to AC source.

        1.1.6

Do not touch any metal parts of the loads when they are plugged into the UPS.

SAFETY INSTRUCTIONS

- 1 -

For your convenience and quick reference for LEONICS UPS service, please

fill the requested information in the blanks  below.

UPS Model

: _____________________________

Serial Number

: _____________________________

Purchase date

: _____________________________

Purchased from : _____________________________

       

Please read carefully and follow this LEONICS NB-series/NBP-series UPS guide.

           Important  :

Please keep this manual for reference in order to use the LEONICS

UPS properly  and safely. This user's guide contains instructions  for installation,

maintenance, operation and unit specifications.

           If   there are any symptoms of problems  which  are not mentioned  in  this  guide or

any queries, please contact your LEONICS  local distributors,  LEONICS  Service Center,

send e-mail to  [email protected]  or visit www.leonics.com.

- 2 -

       1.1.7

Use ONLY one hand when plugging and unplugging the load in order to avoid

                       electric shock from touching two surfaces with different potential.

        1.1.8

It is recommended to connect the UPS to a three wire AC source (two poles

                        plus ground) which connects to a protected circuit such as employs a fuse or

                       automatic circuit breaker.

1.2 CAUTION ! Safety guide for installation and operation

1.2.1 Install the UPS in dry location with good ventilation, low humidity, no chemical

particles, no inflammable substances.  Avoid to install the UPS near radio

transmission station, heat dissipation equipments, or directly to sunlight.

1.2.2 DO NOT block the ventilation grills.

1.2.3 Connect the UPS to utility line and turn it on at all time.

1.2.4 When you want to connect the computer to the UPS, turn off UPS and disconnect

 it from the utility line before connect the computer.

1.2.5 Turn on the UPS before turn on the load to prevent surge from the loads.

1.2.6 DO NOT connect utility power to the UPS OUTPUT.  This may cause the UPS

damaged.

1.2.7 When heavy rain, avoid using electronic instruments including UPS to prevent

 it from lightning.

1.28

Use soft cloth to clean the UPS when it is OFF.  DO NOT clean it with solvent.

1.2.9 DO NOT use the UPS with life recovery instruments.  The failure of UPS may

cause life recovery instruments failure or effect to their performance or effect

to the safety system of those instruments.

1.3 Warning ! Battery Safety

1.3.1 The UPS has hazardous voltages inside, do not disassemble any parts of UPS

                       except for the battery. Users are not allowed to repair, recondition or

                       disassemble the UPS. This must be done by LEONICS qualified technicians

                       only.

                       The battery that is inside your UPS can be recycled. It contains LEAD, which is

                       harmful to health and the environment. If It can not be disposed of properly,

                       please return it to a LEONICS local distributor or  Leonics Service Center.

1.3.2 Do not dispose of batteries in a fire. They may be exploded.

Содержание NB 1K25

Страница 1: ...NBP series NB series TRUE ON LINE DOUBLE CONVERSION UPS LEN MAN UPS 068 Rev 3 00 2008 www leonics com e mail global_business leonics com U S E R S G U I D E ...

Страница 2: ...CONTENT SAFETY INSTRUCTIONS 1 INTRODUCTION 3 FRONT AND REAR PANEL 6 INSTALLATION 14 OPERATION 16 TROUBLESHOOTING 19 MAINTENANCE 20 ...

Страница 3: ... plugging and unplugging the load in order to avoid electric shock from touching two surfaces with different potential 1 1 8 It is recommended to connect the UPS to a three wire AC source two poles plus ground which connects to a protected circuit such as employs a fuse or automatic circuit breaker 1 2 CAUTION Safety guide for installation and operation 1 2 1 Install the UPS in dry location with g...

Страница 4: ... to avoid electric shock 1 3 5 Replace batteries with the same type and rating and follow the proper battery replacement procedure Vocabulary Load Any equipment which is plugged into the UPS and gets power from the UPS such as a computer printer fax machine or modem UPS NB Series and NBP series UPS VA The unit of UPS power rating showing its capacity 2 2 1 When utility power and loads are normal A...

Страница 5: ...on and turn off the UPS 3 1 2 FUNC button The button to mute alarm sound or turn on the LCD s back light The back light will turn off automatically in 10 seconds after release this button 3 1 3 LINE indicator The Indicates when utility line normally 3 1 4 RECTIFIER indicator The indicator is displayed when utility line normally It supplies power to the UPS in rectifier section and supplies power t...

Страница 6: ...al port to connect the LAN cable to computer network to monitor electrical and UPS status via SNMP HTTP Read more details in Net Agent manual 3 2 14 BATTERY TERMINAL for NBP0811 and NBP1011 The teminal for connecting to extension battery unit 3 1 13 LCD DISPLAY The screen to displays Input voltage Vin Output voltage Vout Battery Level B and Load level LD as shown in the picture below Note The valu...

Страница 7: ...reaker OPTION Thecomponenttoswitchthepower source of loads to utility power when maintenance 3 1 18 SNMP AGENT OPTION The additional port to connect the LAN cable to computer network to monitor electrical and UPS status via SNMP HTTP Read more details in Net Agent manual 3 1 19 NO LOAD SHUT DOWN SWITCH The switch to enable automatic shutdown when there is no load and power fails No load means the ...

Страница 8: ... 11 3 2 6 3 2 1 3 2 12 3 2 9 3 2 8 3 2 7 3 2 13 3 2 10 3 2 11 12 ...

Страница 9: ...loads 3 2 11 GROUND The terminal for connecting to ground system 3 2 12 MAINTENANCE BYPASS SWITCH option Turn this switch to position B when UPS is under maintenance 14 INSTALLATION Model Input cable mm2 Output cable mm2 Earth cable mm2 Battery cable mm2 NB2K25 2 5 4 1 5 2 5 2 5 4 NBP 3K25 4 2 5 2 5 4 NBP 5K25 6 4 4 NBP 6K25 6 6 6 NBP 0811 10 6 10 6 6 NBP 1011 16 16 10 6 10 4 1 Connect the RS 232 ...

Страница 10: ...rn on INPUT circuit breaker 5 1 2 2 Turn on POWER button and wait until INVERTER indicator is lit 5 1 2 3 Turn on BATTERY circuit breaker 5 1 3 Model NBP 0811 and NBP 1011 5 1 3 1 Turn on INPUT circuit breaker 5 1 3 2 Turn on POWER button and wait until INVERTER indicator is lit 5 1 3 3 Turn on BATTERY circuit breaker 5 1 3 4 Turn on OUTPUT circuit breaker Note When the UPS is out of order turn on...

Страница 11: ...ch as when user turns on computers When the loads consume power less than 125 for 10 seconds UPS switches back to normal operation mode 5 3 4 If you connect loads to UPS more than 100 OVERLOAD indicator is lit we recommend you to unplug some of them until load is less than 100 to let loads get high quality power from UPS and backup power from battery Note LEONICS suggests that for highest reliabil...

Страница 12: ... UPS is turned on UPS does not supply backup power when power fails No indicator displays at the panel when the UPS is turned on UPS does not supply backup power when power fails MODEL PROBLEM SOLUTION 20 6 2 How to turn on INPUT circuit breaker for NB2K25 NBP 3K25 NBP 5K25 NBP 6K25 NBP 0811 and NBP 1011 6 2 1 Turn off the UPS by pressing the POWER button at the front panel 6 2 2 Turn on the INPUT...

Страница 13: ...n user wants to use the UPS plug the INPUT CABLE to wall outlet utility line Turn on POWER button and wait until the ventilation fan blows Then turn on BATTERY circuit breaker 7 4 2 Model NB 2K25 NBP 3K25 NBP 5K25 and NBP 6K25 7 4 2 1 Turn off the UPS by pressing the POWER button at the front panel 7 4 2 2 Turn off the BATTERY circuit breaker 7 4 2 3 Turn off the INPUT circuit breaker 7 4 2 4 When...

Отзывы: