SOLENOID CONTROL OPTION 

PROVIDED BY LEONARD VALVE 

Description: 

The Solenoid Control Option (SCO) is designed to accept dry contact inputs, either Normally Open 
(N.O.) or Normally Closed (N.C.), in order to switch an AC powered solenoid opened or closed. 

Solenoid valve 

and associated power supply are to be provided by others. 

 

Application: 

The primary application is in systems where it is desirable to control an AC powered solenoid in the event that 
the alarm on the LMS-188-4P is active. When in non-alarm condition the relay is in a N.O. state and the 
solenoid will allow water to flow through it freely. Once the alarm is active, the relay on the LMS-188-4P will 
switch to N.C. and the solenoid will shut down. 

Solenoid valve and associated power supply are to be 

provided by others.

 

 

Installation: 

Included with every SCO is a 12 VDC/600 mA power source with a 10’ lead that requires a dedicated 110 VAC 
outlet to plug into. See wiring diagram below for reference. Do Not Energize SCO, LMS-188-4P, or solenoid 
valve until wiring is complete. 

Solenoid valve and associated power supply are to be provided by others.

 

 

1.

 

Connections from the power source to the SCO (+ side to terminal 

7

), terminal to 

solid state relay (terminals 

3+ to 8

), and power source to solid state relay (- side to terminal 

4-

) have 

been made at the factory. 

2.

 

Properly ground the SCO by using the screw provided inside of the enclosure and 

connect to suitable earth ground 

3.

 

Connect terminal 

5

 (12VDC) to the 

COMMON ‘C’

 terminal (

9

) of the LMS-188-4P 

relay switch. 

4.

 

Connect either terminal 

9 or 11

 from the LMS-188-4P relay switch to terminal 

6

 on 

the terminal strip. Use terminal 

9

 with N.C. solenoids; use terminal 

11

 with N.O. solenoids.  

5.

 

Connect the positive side of the solenoid power supply to terminal 

on the solid state 

relay.  

6.

 

Connect terminal 

2

 on the sold state relay to the positive side of the solenoid valve. 

Complete the circuit by connecting the neutral side of solenoid to the neutral side of power supply.  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание LMS-188-4P

Страница 1: ...d Avenue Cranston RI 02910 Tel 401 461 1200 Fax 401 941 5310 Toll free 800 222 1208 www leonardvalve com G LMS 188 4P February 2021 WARNING This product can expose you to chemicals including lead whic...

Страница 2: ...time Display Error Bookmark not defined Alarm Conditions Error Bookmark not defined Temperature Alarms 5 Low High Alarm Limits 5 Min Max Readings 5 LMS Email Notification Feature 6 LMS Overview 10 RDU...

Страница 3: ...tep button STEP o Alarm Limits decrement button vv o Min Max increment button o Mute Menu increment button MUTE MENU Sensor Probe The probes supplied with the Multi Probe Alarm System are highly accur...

Страница 4: ...t finger tight Warning do not overtighten Power up Shows LMS startup screen NO BATTERY Power Down Install Battery The unit will run without a backup battery but will show NoBatt on the display to indi...

Страница 5: ...elay Delay times Units with a single relay have one Relay Delay time that applies to any alarm condition Limit Parameters 1 Low 1 High 2 Low 2 High 3 Low 3 High 4 Low 4 High Time Parameters 1AlarmDela...

Страница 6: ...to 30000 22718 Depending on the Network being utilized the factory setting on the alarm unit for IP1 IP2 and IP3 may need to be changed to match the corresponding settings of the network IP4 may also...

Страница 7: ...r through Control Panel or the internet connection icon on your taskbar 2 Click on Local Area Connection to bring up the status page 3 Click properties and then highlight Internet Protocol Version 4 T...

Страница 8: ...is utilized See Network administrator for DNS Server SMTP information If these parameters are unavailable use 8 8 8 8 for DNS Server smtp 1and1 com for SMTP Server t140 hampshirecontrols com for SMTP...

Страница 9: ...IP address to access the unit After reviewing main web page add setup html to the IP to access the Setup Info Name setupadmin unchangable case sensitive Passcode 22718 Enter your Subnet Mask Gateway D...

Страница 10: ...RelayDelay 2RelayDelay Mute Special Group SETUP 1 Offset 2 Offset channels 1 Define 0 tenthC 1 wholeC 2 tenthF 3 wholeF 4 wholeRH 2 Define Relay Def 0 single unit relay 1 individual channel relays Doo...

Страница 11: ...while still providing the degree of safety required III Installation 1 Remove the plastic case cover by removing the 2 Phillips screws from the back Apply light pressure on the face plate the cover a...

Страница 12: ...that an alarm condition has persisted for the set time and has been transmitted to the monitoring device this LED will continue to flash even if the alarm condition has corrected itself Pressing RESET...

Страница 13: ...quires a dedicated 110 VAC outlet to plug into See wiring diagram below for reference Do Not Energize SCO LMS 188 4P or solenoid valve until wiring is complete Solenoid valve and associated power supp...

Страница 14: ...arm is active the relay on the LMS 188 4P will switch to N C and the solenoid will shut down Solenoid valve and associated power supply are to be provided by others Installation Solenoid power supply...

Страница 15: ...LMS Operating Manual Page 15...

Отзывы: