Terminal data
Inverter
I95AExxxF
Inverter
kW
0.55 ... 4.0
7.5 ... 15
22
30 ... 45
55 ... 75
90 ... 110
Connection
Mains connection X100
Connection type
Pluggable screw terminal
Screw terminal
Max. cable cross-section
mm²
2.5
16
35
50
95
150
Stripping length
mm
8
14
18
19
22
28
Tightening torque
Nm
0.5
1.8
3.8
4
10
18
Required tool
0.5 x 3.0
0.8 x 4.0
0.8 x 5.5
Hexagon
socket 5
Hexagon
socket 6
Hexagon
socket 8
Inverter
I95AExxxF
Inverter
kW
0.55 ... 4.0
7.5 ... 15
22 ... 75
90 ... 110
0.55 ... 4.0
7.5 ... 15
Connection
PE connection
Motor connection X105
Connection type
PE screw
PE bolt
Pluggable screw terminal
Max. cable cross-section
mm²
6
16
25
150
2.5
16
Stripping length
mm
10
11
16
-
8
14
Tightening torque
Nm
2
3.4
4
10
0.5
1.8
Required tool
Torx 20
PZ2
Width AF 13
0.5 x 3.0
0.8 x 4.0
Inverter
I95AExxxF
Inverter
kW
22
30 ... 45
55 ... 75
90 ... 110
Connection
Motor connection X105
Connection type
Screw terminal
Max. cable cross-section
mm²
35
50
95
150
Stripping length
mm
18
19
22
28
Tightening torque
Nm
3.8
4
10
18
Required tool
0.8 x 5.5
Hexagon socket 5
Hexagon socket 6
Hexagon socket 8
The terminal data for the terminal X1 can be found under:
The terminal data for the terminals X82 and X83 can be found under:
Fusing data
EN 60204-1
Inverter
Fuse
Circuit breaker
Earth-leakage circuit
breaker
Characteristic
Max. rated
current
Characteristic
Max. rated
current
A
A
I95AE155F
gG/gL or gRL
10
B
10
≥ 30 mA, type B
I95AE175F
gG/gL or gRL
10
B
10
≥ 30 mA, type B
I95AE222F
gG/gL or gRL
16
B
16
≥ 30 mA, type B
I95AE240F
gG/gL or gRL
16
B
16
≥ 30 mA, type B
I95AE275F
gG/gL or gRL
50
B
40
≥ 300 mA, type B
I95AE311F
gG/gL or gRL
50
B
40
≥ 300 mA, type B
I95AE315F
gG/gL or gRL
50
B
40
≥ 300 mA, type B
I95AE322F
gG/gL or gRL
63
B
63
≥ 300 mA, type B
I95AE330F
gG/gL or gRL
80
B
80
≥ 300 mA, type B
I95AE345F
gG/gL or gRL
125
B
125
≥ 300 mA, type B
I95AE355F
gR
160
-
-
≥ 300 mA, type B
I95AE375F
gR
160
-
-
≥ 300 mA, type B
I95AE390F
gR
300
-
-
≥ 300 mA, type B
I95AE411F
gR
300
-
-
≥ 300 mA, type B
Electrical installation
Mains connection
3-phase mains connection 400 V
119
Содержание i950-Cabinet
Страница 2: ......
Страница 4: ...4...
Страница 29: ...22 kW Die Abmessungen in mm gelten f r 22 kW I95AE322F Mechanische Installation Abmessungen 29...
Страница 30: ...30 hp Die Abmessungen in inch gelten f r 30 hp I95AE322F Mechanische Installation Abmessungen 30...
Страница 49: ...I95AE322F 3 3 Elektrische Installation Anschluss an das IT Netz 49...
Страница 50: ...I95AE330F I95AE345F I95AE355F I95AE375F 3 3 3 3 Elektrische Installation Anschluss an das IT Netz 50...
Страница 51: ...I95AE390F I95AE411F 3 3 Elektrische Installation Anschluss an das IT Netz 51...
Страница 103: ...22 kW The dimensions in mm apply to 22 kW I95AE322F Mechanical installation Dimensions 103...
Страница 104: ...30 hp The dimensions in inch apply to 30 hp I95AE322F Mechanical installation Dimensions 104...
Страница 105: ...30 kW 45 kW The dimensions in mm apply to 30 kW I95AE330F 45 kW I95AE345F Mechanical installation Dimensions 105...
Страница 106: ...40 hp 60 hp The dimensions in inch apply to 40 hp I95AE330F 60 hp I95AE345F Mechanical installation Dimensions 106...
Страница 107: ...55 kW 75 kW The dimensions in mm apply to 55 kW I95AE355F 75 kW I95AE375F Mechanical installation Dimensions 107...
Страница 108: ...75 hp 100 hp The dimensions in inch apply to 75 hp I95AE355F 100 hp I95AE375F Mechanical installation Dimensions 108...
Страница 109: ...90 kW 110 kW The dimensions in mm apply to 90 kW I95AE390F 110 kW I95AE411F Mechanical installation Dimensions 109...
Страница 110: ...120 hp 150 hp The dimensions in inch apply to 120 hp I95AE390F 150 hp I95AE411F Mechanical installation Dimensions 110...
Страница 123: ...I95AE322F 3 3 Electrical installation Connection to the IT system 123...
Страница 124: ...I95AE330F I95AE345F I95AE355F I95AE375F 3 3 3 3 Electrical installation Connection to the IT system 124...
Страница 125: ...I95AE390F I95AE411F 3 3 Electrical installation Connection to the IT system 125...
Страница 153: ......