Electrical installation
Mounting steps
l
38
EDKZS3YA200 DE/EN/FR/ES/IT 3.0
How to connect the filter:
1. Loosen four screws
0
and remove the terminal cover
1
.
2. Connect the filter input cable to terminals 1U1, 1V1, 1W1.
Connect the filter output cable to terminals 1U2, 1V2, 1W2.
–
Use shielded cables.
–
Connect the two PE conductors to the PE stud using ring cable lugs (PE
connection must comply with EN 61800−5−1).
–
Observe tightening torques.
3. Turn down the shield and connect it to the shield sheet (PES) with a
surface as large as possible.
–
Fix the shield with a metal cable tie or hose clip
2
.
–
Use an additional cable tie for strain relief
3
.
4. Insert the terminal cover
1
and fix it with four screws
0
.
{
Danger!
Hazardous electrical voltage
The terminal cover
1
serves to protect persons!
If the filter is operated without a terminal cover
1
, it is possible to
touch live parts at the terminals. These parts remain live for up to
three minutes after mains disconnection.
Possible consequences:
ƒ
Death or severe injuries.
Protective measures:
ƒ
Only commission the filter if the terminal cover is mounted.
ƒ
Switch off the power supply and wait for at least three minutes
before dismounting the terminal cover. Ensure that all terminals
are in a de−energised state.