Troubleshooting and fault elimination
System error messages
71
EDK10200EV3 DE/EN/FR 7.1
Remedy
Cause
Fault
Display
PC
1)
Keypad
H05
105
Internal fault
Contact Lenze
H08
108
Error when
configuring the
extension board
Extension board has not
been plugged−on correctly
or not supported by the
program
l
Check plug connection
l
Check if the extension board
is supported by the operating
system version
per
74
Error in program
flow
An error has been
detected in the program
flow.
Send Drive PLC with data set (to
floppy disk) to Lenze
pi
79
Initialisation error
during parameter
set transfer
l
During the parameter
set transfer to the
Drive PLC an error has
been detected
l
Wrong parameter set
for Drive PLC
Correct parameter set
Pr0
75
Internal fault
Contact Lenze
Pr1
72
PAR1 incorrectly
transferred via
keypad/PC
PAR1 is defective
Repeat data transfer or load
Lenze setting
Pr5
79
Internal fault
Save cyclic parameter set
Do not execute "Save cyclic
parameter set" since this
damages the EEPROM
1)
LECOM error number
Note!
Detailed information on the system error messages of the Drive PLC can be
found in the PDF manual "Drive PLC" (chapter Appendix: System error
messages)