Troubleshooting and fault elimination
System error messages
70
EDK10200EV3 DE/EN/FR 7.1
System error messages
Display
Fault
Cause
Remedy
Keypad
PC
1)
noer
0
No fault
−
−
ccr
71
System fault
Heavy interference
injections on the control
cables
Install shielded control cable
Earth loops in wiring
ce0
61
Communication
error at AIF
Transmission of control
commands via AIF is faulty
Firmly insert the communication
module in the diagnosis
terminal
ce1
62
Communication
error at
CAN−IN1 with sync
control
CAN−IN1 object receives
faulty data or
communication is
interrupted
l
Check plug connection of bus
module
ó
FIF
l
Check transmitter
l
Possibly increase monitoring
time in C0357/1
ce2
63
Communication
error at
CAN−IN2
CAN−IN2 object receives
faulty data or
communication is
interrupted
l
Check plug connection of bus
module
ó
FIF
l
Check transmitter
l
Possibly increase monitoring
time in C0357/2
ce3
64
Communication
error at
CAN−IN3 with event
or time control
CAN−IN3 object receives
faulty data or
communication is
interrupted
l
Check plug connection of bus
module
ó
FIF
l
Check transmitter
l
Possibly increase monitoring
time in C0357/3
ce4
65
Bus−off
(many
communication
errors occurred)
Drive PLC received too
many faulty messages via
system bus and decoupled
itself from the bus
l
Check whether bus
termination is present
l
Shield connection of cables
l
Check PE connection
l
Check bus load, reduce baud
rate, if necessary
EEr
91
External fault (TRIP
set)
A digital signal assigned
with the TRIP set function
was activated
Check external encoder