Process data transfer
Lenze device control
Process input data configuration
l
44
EDS82ZAFPC201 EN 4.0
FIF status word 1 (FIF−STAT1)
FIF status word 2 (FIF−STAT2)
Bit
Assignment
Bit
Assignment
0
Current parameter set bit 0
(DCTRL1−PAR−B0)
0
Current parameter set bit 1
(DCTRL1−PAR−B1)
0
1
Parameter set 1 or 3 active
Parameter set 2 or 4 active
0
1
Parameter set 1 or 2 active
Parameter set 3 or 4 active
1
Pulse inhibit
(DCTRL1−IMP)
1
TRIP, Q
min
or pulse inhibit active
(DCTRL1−TRIP−QMIN−IMP)
0
1
Power outputs enabled
Power outputs inhibited
0
1
False
True
2
I
max
limit
(MCTRL1−IMAX)
(If C0014 = 5: Torque setpoint)
2
PTC warning active
(DCTRL1−PTC−WARN)
0
1
Not reached
Reached
0
1
False
True
3
Output frequency = frequency setpoint
(DCTRL1−RFG1=NOUT)
3
Reserved
Do not write to this bit!
0
1
False
True
4
Ramp function generator input 1 = ramp function
generator output 1
(NSET1−RFG1−I=O)
4
C0054 < C0156 and Q
min
threshold reached
(DCTRL1−(IMOT<ILIM)−QMIN)
0
1
False
True
0
1
False
True
5
Q
min
threshold
(PCTRL1−QMIN)
5
C0054 < C0156 and NSET1−RFG1−I=O
(DCTRL1−(IMOT<ILIM)−RFG−I=O)
0
1
Not reached
Reached
0
1
False
True
6
Output frequency = 0
(DCTRL1−NOUT=0)
6
LP1 warning (fault in motor phase) active
(DCTRL1−LP1−WARN)
0
1
False
True
0
1
False
True
7
Controller inhibit
(DCTRL1−CINH)
7
f < f
min
(NSET1−C0010 ... C0011)
0
1
Controller enabled
Controller inhibited
0
1
False
True
11...8
Device status
(DCTRL1−STAT*1 ... STAT*8)
8
TRIP active
(DCTRL1−TRIP)
Bit 11 10 9
8
0
1
False
True
0
0
0
0
0
1
0
0
Controller initialisation
Switch−on inhibit
9
Motor is running
(DCTRL1−RUN)
0
0
0
1
1
0
1
0
Operation inhibited
Flying−restart circuit active
0
1
False
True
0
1
0
1
DC−injection brake active
10
Motor is running clockwise
(DCTRL1−RUN−CW)
0
0
1
1
1
1
0
1
Operation enabled
Message active
0
1
False
True
1
0
0
0
Fault active
11
Motor is running counter−clockwise
(DCTRL1−RUN−CCW)
1
1
1
1
Communication with basic device not
possible
0
1
False
True
12
Overtemperature warning
(DCTRL1−OH−WARN)
12
Reserved
0
1
No warning
J
max
− 10
C reached
13
DC−bus overvoltage
(DCTRL1−OV)
13
Reserved
0
1
No overvoltage
Overvoltage
14
Direction of rotation
(DCTRL1−CCW)
14
C0054 > C0156 and NSET1−RFG1−I=0
(DCTRL1−(IMOT>ILIM)−RFG−I=O)
0
1
CW rotation
CCW rotation
0
1
False
True
15
Ready for operation
(DCTRL1−RDY)
15
Reserved
0
1
Not ready for operation (fault)
Ready for operation (no fault)
Tab. 7−2
Parameter structure FIF status word (FIF−STATx)