Commissioning
Configuring the host system (master)
l
29
EDS82ZAFPC201 EN 4.0
6.3
Configuring the host system (master)
The host must be configured before communication with the communication module is
possible.
Master settings
For configuring the PROFIBUS, the device data base file (GSE file) of the communication
module has to be imported into the configuring software of the master.
I
Tip!
The GSE file can be downloaded from www.Lenze.com.
Device data base file
The device data base file
LENZ081B.GSE
contains the following configurations:
Module in LENZ081B.GSE
Parameter data
without/with
consistency
Process data
without/with
consistency
Assigned
I/O memory
Without
With
Without
With
Drivecom−PAR (cons)
+ PZD (n Words)
DRIVECOM
n words
4 + n words
Drivecom−PAR (cons)
+ PZD (n Words Cons.)
n words
4 + n words
PKW (cons)
+ PZD (n Words)
PKW
n words
4 + n words
PKW (cons)
+ PZD (n Words Cons.)
n words
4 + n words
PZD (n Words)
Without parameter data
channel
n words
n words
PZD (n Words Cons.)
Without parameter data
channel
n words
n words
n = 1 ... 10