Codes
Important controller codes
l
106
EDS82ZAFPC201 EN 4.0
ƒ
Transferring parameter sets with the keypad:
Selection
Important
You can use the keypad to transfer parameter sets to other controllers.
During the transfer, access to the parameters via other channels will be inhibited!
Keypad
ð
controller
Overwrite all available parameter sets (PAR1 ... PAR4, FPAR1 if
available) with the corresponding keypad data
70
With function module
10
(other)
Keypad
ð
PAR1 (+ FPAR1)
Overwrite the selected parameter set and, if available, FPAR1
with the corresponding keypad data
71
With function module
11
(other)
Keypad
ð
PAR2 (+ FPAR1)
72
With function module
12
(other)
Keypad
ð
PAR3 (+ FPAR1)
73
With function module
13
(other)
Keypad
ð
PAR4 (+ FPAR1)
74
With function module
14
(other)
Controller
ð
keypad
Copy all available parameter sets (PAR1 ... PAR4, FPAR1 if
available) into the keypad
80
With function module
20
(other)
Keypad
ð
function module
Overwrite only the module−specific parameter set FPAR1 with
the keypad data
40
Only with function module
Function module
ð
keypad
Copy only the module−specific parameter set FPAR1 into the
keypad
50
Only with function module
ƒ
Saving your own setting:
Selection
Important
9
PAR1
ð
own setting
You can store your own setting for the controller parameters
(e.g. the delivery state of your machine):
1. Check that parameter set 1 is active
2. Inhibit the controller
3. Set C0003 = 3, confirm with
v
4. Set C0002 = 9, confirm with
v
, your own setting has
been stored
5. Set C0003 = 1, confirm with
v
6. Enable the controller
This function can also be used to copy PAR1 to the parameter
sets PAR2 ... PAR4
5
Own setting
ð
PAR1
Restore your own setting in the selected parameter set
6
Own setting
ð
PAR2
7
Own setting
ð
PAR3
8
Own setting
ð
PAR4