Commissioning
Vector control
T
EDK82MV222 DE/EN/FR 9.0
NNT
L
16.
If necessary, change other
parameters
Activate e.g. JOG frequencies
(C0037, C0038, C0039) or motor
temperature monitoring (C0119)
17.
Go to the
ALL
menu
A Check the fan monitoring
setting under code C0608:
– for 8200 motec 0.25...0.37
kW and 0.55...2.2 kW:
C0608 = 0! (default setting)
– for 8200 motec 3...7.5 kW:
C0608 =1 (recommended)
or C0608 = 2!
Stop!
Function must be
activated during
commissioning!
Otherwise, the
controller may be
destroyed through
overheating!
– for all other controllers:
C0608 = 0 ! (default
setting)
B Select additional functions via
codes, if necessary.
When all settings are complete:
18.
Select the setpoint
E.g. via potentiometer at
terminals 7, 8, 9
19.
Enable the controller
20
28
X3
misc002
Terminal X3/28 = HIGH
20.
The drive should now be running.
If the drive does not
start, press
in
addition