![Lenze 8200 motec Скачать руководство пользователя страница 112](http://html1.mh-extra.com/html/lenze/8200-motec/8200-motec_mounting-instructions_1882264112.webp)
T
Commissioning
Linear V/f-characteristic control
EDK82MV222 DE/EN/FR 9.0
L
NNO
qÜÉ ÑçääçïáåÖ áåëíêìÅíáçåë ~ééäó íç ÅçåíêçääÉêë ÉèìáééÉÇ ïáíÜ ~ ëí~åÇ~êÇJfLl
ÑìåÅíáçå ãçÇìäÉ ~åÇ ~ íÜêÉÉJéÜ~ëÉ ^` ãçíçê ïÜáÅÜ Ü~ë ÄÉÉå ëÉäÉÅíÉÇ
~ÅÅçêÇáåÖ íç ~ éçïÉêJÄ~ëÉÇ ~ëëáÖåãÉåíK
1.
Connect the keypad
2.
Ensure that controller inhibit is
active after mains connection
misc001
20
28
X3
}
Terminal X3/28 = LOW
3.
Switch on the mains
ON
misc002
4.
The keypad is in ”Disp” mode
after approx. 2 s and indicates
the output frequency (C0050)
000
000
a
b
c
d
e
m n o
p
q r
Hi
Hz
Lo
1
j g f k i h
PS
0050
The
USEr
menu is active
5.
Change to the
mode to
configure the basic settings for
your drive
000
000
a
b
c
d
e
m n o
p
q r
Hi
Hz
Lo
1
j g f k i h
PS
0050
z
y
w x
Blinking on the display:
0050
6.
Adapt the voltage/current range
for the analog setpoint selection
(C0034)
Lenze setting: -0-,
(0 ... 5 V/0 ... 10 V/0 ... 20 mA)
z
y
w x
0
000
a
b
c
d
e
m n o
p
q r
Hi
Lo
1
j g f k i h
PS
0034
Set the DIP switch on the
standard I/O to the same
range (see Mounting
Instructions for the
standard I/O)
7.
Adapt the terminal configuration
to the wiring (C0007)
Lenze setting: -0-, i. e.
E1: JOG1/3 fixed setpoint
selection
E2: JOG2/3
E3: DCB DC injection brake
E4: CW/CCW rotation
z
y
w x
0
000
a
b
c
d
e
m n o
p
q r
Hi
Lo
1
j g f k i h
PS
0007
8.
Set the minimum output
frequency (C0010)
Lenze setting: 0.00 Hz
M B
xÑz
NMM B
`MMNN
`MMNM
9.
Set the maximum output
frequency (C0011)
Lenze setting: 50.00 Hz
efesotomasyon.com - Lenze