SMVector
14
ENGLISH
Commissioning
Code
Possible Settings
IMPORTANT
No.
Name
Default Selection
TPDO#1 configuration parameters
P460
(4)
TPDO#1 COB ID
385
0
2047 If P413 = 0, 2: Setting will change to
384 + Node ID during power-up or P418
reset.
P461
TPDO#1
enable/disable
2
0 Disable
1 Enable (no RTR)
2 Enable (with RTR)
Enable individual polling of TPDO#1
P462
TPDO#1
transmission type
255
0
255
•
P462 = 0...240: Transmit TPDO#1 after
every n
th
SYNC re Event +
RTR (if enabled)
•
P462 = 253: Event + RTR (if enabled)
•
P462 = 254: COS triggered (WORD0 of
TPDO#1) + Event + RTR (if enabled)
•
P462 = 255: Event + RTR (if enabled)
P463
(4)
TPDO#1 inhibit
time
0.0
0.0
{0.1 ms}
65535 Sets minimum time between TPDO#1
transmissions.
P464
TPDO#1 event
timer
0
0
{ms}
65535
•
Sets the fixed interval for TPDO#1
transmission
•
P464 = 0: disables event timer
P466
(4)
TPDO#1 mapping
(see TPDO
mapping details)
2
0 DSP402 (Drives & Motion Control):
Status Word 0x6041
1 DSP402 (Drives & Motion Control):
Status Word
vl target velocity 0x6044
•
vl control effort units = signed RPM.
•
RPM calculation based on P304 and
P305
2 Drive Status Word + Actual
Fre I/O
Actual Frequency Scaling: 10 = 1.0 Hz
3 Drive Status Word + Actual
Fre PID Setpoint
Signed PID Setpoint: -999 … 31,000
4 Drive Status Word + Actual
Fre Torque Setpoint
Torque Setpoint: 0…400%
5 Status Word matches the drives
Control Word
Setting used to control another
Drive. See Appendix A1.1.
P467
TPDO#1 WORD0
bit mask
65535 0
65535
•
COS (change of state) bit mask applied
to WORD0 of TPDO selected by P466.
•
P467 = 65535: activates all bits of
WORD0 for COS triggering
•
P467 = 0: disables COS triggering
•
P462 = 254
P469
TPDO#1 counter
0
255
•
Read-only
•
Number of transmitted TPDO#1
messages
•
Above 255, starts over at 0
(4)
These parameters take effect only after power-up, P418 reset, P461 transition from disable to enable, “NMT reset node”, or “NMT reset communication services”