background image

Page 31

VII-ACCESSORIES   

The accessories section describes the application of most of
the optional accessories which can be factory or field installed.
OPTIONAL ACCESSORIES section (see table of contents)
show specific size per unit.

A-LARMF Mounting Frames

When installing units on a combustible surface for downflow

discharge applications, the  Z1CURB roof mounting frame is

used. The roof mounting frames are recommended in all

other applications but not required. If units are not mounted

on a flat (roof) surface, they MUST be supported under all

edges and under the middle of the unit to prevent sagging.

The units MUST be mounted level within 1/16” per linear foot

or 5mm per meter in any direction.

The assembled Z1CURB mounting frame is shown in fig­

ure 16. Refer to the roof mounting frame installation instruc­

tions for details of proper assembly and mounting. The roof

mounting frame MUST be squared to the roof and level be­

fore mounting. Plenum system MUST be installed before

the unit is set on the mounting frame. Typical roof curbing

and flashing is shown in figure 17. Refer to the roof mount­

ing frame installation instructions for proper plenum

construction and attachment.

B-Transitions

Transitions are field-provided.

C-Supply and Return Diffusers

Optional flush mount diffuser/return FD11 and extended mount

diffuser/return RTD11 are available. Refer to manufacturer's

instructions included with transition for detailed installa­

tion procedures.

FIGURE 16

ASSEMBLED ROOF MOUNTING FRAME

SUPPLY AIR

OPENING

RETURN AIR

OPENING

FIGURE 17

ROOF

MOUNTING FRAME

(Extends around entire

perimeter of unit)

FIBERGLASS

INSULATION

(Furnished)

COUNTER FLASHING

(Field Supplied)

UNIT BASE

BOTTOM

RIGID INSULATION

(Field Supplied)

ROOFING

MATERIAL

CANT STRIP

(Field Supplied)

NAILER STRIP

(Furnished)

UNIT BASE RAIL

TYPICAL FLASHING DETAIL

D-Z1ECON16/20B Economizer

(Field or Factory Installed)

Economizers use outdoor air for free cooling when temper­
ature and/or humidity is suitable. See figure 18.

The mixed air temperature sensor (R1) measures the sup­
ply air sensible temperature. See figure 19. The outdoor air
sensible control is the default economizer control. An out­
door air single sensible sensor, S175, is also provided. See
table 7 for outdoor and return air (OA and RA) sensor op­
tions. Refer to instructions provided with sensors for instal­
lation.

An IAQ sensor is used when demand control ventilation
(DCV) is specified. Damper minimum position can be set
lower than traditional minimum air requirements resulting in
cost savings. The IAQ sensor allows the A6 to open damp­
ers to traditional ventilation requirements as room occu­
pancy (CO

2

) increases.

TABLE 7

Sensors

Dampers will modulate to 55°F

discharge air (RT6) when:

Single OA Sensible

OA temperature (S175) is lower
than free cooling setpoint.

Single OA Sensible

OA temperature and humidity (A7)
is lower than free cooling setpoint.

Differential Enthalpy - 1
in OA and 1 in RA

OA temperature and humidity (A7)
is lower than RA temperature and
humidity (A62).

IAQ Sensor

CO

2

 sensed (A63 ) is higher than

CO

2

 setpoint.

Содержание ZHA Series

Страница 1: ...personal injury or loss of life Installation and ser vice must be performed by a licensed professional HVAC installer or equivalent service agency CAUTION Electrostatic discharge can affect electronic...

Страница 2: ...890 rpm Factory O O O Kit 2 800 1105 rpm Factory O O O Kit 3 795 1195 rpm Factory O O O Kit 4 730 970 rpm Factory O O O Kit 5 940 1200 rpm Factory O O O Kit 6 1015 1300 rpm Factory O O O Kit 10 900 1...

Страница 3: ...X ELECTRICAL Voltage 60 hz 208 230V 3 phase Factory O O O 460V 3 phase Factory O O O 575V 3 phase Factory O O O Bottom Power Entry Kit Z1PEKT01B 1 11H66 X X X ELECTRIC HEAT 7 5 kW 208 230V 3ph Z1EHO0...

Страница 4: ...ometric Relief Dampers With Exhaust Hood LAGEDH03 15 53K04 X X X OUTDOOR AIR Outdoor Air Dampers Motorized Dampers with outdoor air hood Z1DAMP20B 1 10Z33 X X X Manual Dampers with outdoor air hood Z1...

Страница 5: ...800 8800 Indoor Coils Net face area total sq ft 12 8 12 8 12 8 12 8 Tube diameter in 3 8 3 8 3 8 3 8 Number of rows 3 3 4 4 Fins per inch 14 14 14 14 Drain connection Number and size 1 1 in NPT coupli...

Страница 6: ...g Expansion device type Refrigerant Metering Orifice RFC 2 Indoor Blower and Drive Selection Nominal motor output 2 hp 3 hp 5 hp Maximum usable motor output US Only 2 3 hp 3 45 hp 5 75 hp Motor Drive...

Страница 7: ...0 49 650 0 70 719 0 87 786 0 98 852 1 09 915 1 20 972 1 32 1026 1 47 1076 1 65 2250 533 0 41 599 0 62 667 0 82 735 0 99 802 1 10 866 1 21 928 1 33 984 1 46 1037 1 63 1085 1 81 1132 2 01 1178 2 21 1226...

Страница 8: ...913 1 57 968 1 74 1020 1 93 1068 2 13 1116 2 34 1165 2 56 1215 2 78 1268 3 01 3000 620 0 95 678 1 11 741 1 25 806 1 40 870 1 58 930 1 75 985 1 94 1036 2 14 1084 2 36 1131 2 58 1180 2 80 1230 3 02 1283...

Страница 9: ...POWER EXHAUST FAN PERFORMANCE Return Air System Static Pressure Air Volume Exhausted in w g cfm 0 3575 0 05 3405 0 10 3550 0 15 3245 0 20 3115 0 25 3020 0 30 2900 0 35 2785 FACTORY INSTALLED OPTIONS F...

Страница 10: ...00 0 44 0 36 0 29 0 21 4200 0 49 0 40 0 33 0 24 4400 0 54 0 44 0 37 0 27 4600 0 60 0 49 0 42 0 31 4800 0 65 0 53 0 46 0 35 5000 0 69 0 58 0 50 0 39 5200 0 75 0 62 0 54 0 43 CEILING DIFFUSER AIR THROW...

Страница 11: ...ric Heat 7 5 kW 58 61 61 64 68 71 32 33 36 24 25 28 15 kW 77 83 81 87 87 93 43 44 47 33 34 37 22 5 kW 97 106 100 109 107 116 54 56 59 42 43 46 30 kW 117 129 120 132 127 139 66 67 70 51 52 55 45 kW 156...

Страница 12: ...ric Heat 7 5 kW 60 63 63 66 70 73 33 35 37 25 26 29 15 kW 80 86 83 89 90 96 45 46 49 34 35 38 22 5 kW 99 108 102 111 109 118 56 57 60 43 44 47 30 kW 119 131 122 134 129 141 67 69 71 52 53 56 45 kW 158...

Страница 13: ...eat 15 kW 88 94 91 97 98 104 47 48 51 37 38 40 22 5 kW 108 117 111 120 117 126 58 60 62 46 47 49 30 kW 127 139 130 142 137 149 70 71 74 55 56 58 45 kW 166 184 169 188 176 194 92 94 96 73 74 76 60 kW 1...

Страница 14: ...7 100 1 20 7 70 700 1 27 5 93 900 1 41 3 141 000 1 55 1 188 000 1 240 7 5 25 600 1 15 0 51 200 1 22 5 76 800 1 30 0 102 400 1 45 0 153 600 1 60 0 204 800 1 440 6 9 21 500 1 12 6 43 000 1 18 9 64 500 1...

Страница 15: ...TIONAL F4 FUSE BLOCK OPTIONAL BLOWER HOUSING INVERTER OPTIONAL ELECTRIC HEAT CONTROLS 20 x 24 x 2 FILTERS BEHIND COIL TB1 LOW VOLTAGE TERMINAL STRIP TB13 HIGH VOLTAGE TERMINAL STRIP TB2 TERMINAL BLOCK...

Страница 16: ...tors with a 24VAC coil K1and K2 energize compres sors B1 and B2 respectively in response to first or second stage cooling demands On CE M volt units contactor is CE approved by manufacturer Siemens Se...

Страница 17: ...to the motor When the relay senses and overload condition a set of normally closed contacts open to de en ergize 24VAC power T1 transformer 13 Terminal Block TB1 TB1 provides 24VAC field connections...

Страница 18: ...ing jumper is in the TEST position at power up the defrost control will ignore the test pins When the jumper is placed across the TEST pins for two seconds the control will enter the defrost mode If t...

Страница 19: ...TDOOR COIL STAGE 1 UPPER OUTDOOR COIL STAGE 2 LOWER DRIERS S4 HIGH PRESSURE LIMIT S7 HIGH PRESSURE LIMIT S5 HIGH TEMPERATURE LIMIT S8 HIGH TEMPERATURE LIMIT COMPRESSOR 2 DISCHARGE LINE COMPRESSOR 2 SU...

Страница 20: ...sound will be heard when the compressor is running un loaded Protector will reset when low pressure in system rises above 40 psig DO NOT REPLACE COMPRESSOR 2 Thermal Protectors S5 S8 Some compressors...

Страница 21: ...rma tion and available replacements All units are equipped with belt drive blowers 1 Blower Wheels All units have one 15 in x 15 in 381 mm x 381 mm blower wheel 2 Indoor Blower Motor B3 All units use...

Страница 22: ...base should be equal at both ends i e par allel along gap 3 Tighten four bolts securing motor mounting base to frame 4 Relieve tension on two adjusting bolts PULLEY MOTOR SIDE VIEW ALLEN SCREW BELT AD...

Страница 23: ...bolt to the left or counterclockwise to loosen belt tension IMPORTANT Align top edges of blower motor base and mounting frame base parallel before tightening two bolts on the other side of base Motor...

Страница 24: ...ting the unit 5 Recheck voltage and amp draw with unit running If voltage is not within range listed on unit nameplate stop unit and consult power company Refer to unit nameplate for maximum rated loa...

Страница 25: ...harge NOTE System charging is not recommended below 60_F 15_C In temperatures below 60_F 15_C the charge must be weighed into the system If weighing facilities are not available or to check the charge...

Страница 26: ...temperature TABLE 4 092S Normal Operating Pressures Outdoor Coil Entering Air Temperature 65 F 75 F 85 F 95 F 105 F 115 F Suct psig Disc psig Suct psig Disc psig Suct psig Disc psig Suct psig Disc ps...

Страница 27: ...19 337 120 383 121 430 127 491 Circuit 1 124 265 132 309 137 355 141 405 145 459 145 515 129 268 138 312 146 363 153 415 159 472 160 530 116 260 119 298 123 340 126 385 131 437 136 405 125 266 128 306...

Страница 28: ...10 127 354 131 401 134 448 137 498 132 279 140 319 145 365 148 414 152 469 155 524 137 284 147 329 155 379 163 430 171 486 171 539 11 70 80 90 100 110 120 130 Suction Pressure psig Outdoor Temperature...

Страница 29: ...panel on back side of unit See figure 13 Lift filter stop to remove filters See fig ure 14 WARNING Units are shipped from the factory with temporary fil ters Replace filters before building is occupie...

Страница 30: ...ial coil cleaner and inspect monthly during the cooling season Outdoor coils are made of single and two formed slabs On units with two slabs dirt and debris may become trapped between the slabs To cle...

Страница 31: ...detailed installa tion procedures FIGURE 16 ASSEMBLED ROOF MOUNTING FRAME SUPPLY AIR OPENING RETURN AIR OPENING FIGURE 17 ROOF MOUNTING FRAME Extends around entire perimeter of unit FIBERGLASS INSULAT...

Страница 32: ...led a steady green DCV LED indicates that the IAQ reading is higher than set point requiring more fresh air See figure 20 FIGURE 20 A6 ENTHALPY CONTROLLER A B C D Open Min Pos FREE COOLING SETPOINT A...

Страница 33: ...ximate desired fresh air percentage Note Damper minimum position can be set lower than traditional minimum air requirements when an IAQ sensor is specified Dampers will open to DCV MAX setting if CO2...

Страница 34: ...time period a cooling demand will open dampers to minimum position and mechanical cooling functions normally During the occupied time period dampers will open to DCV MAX when IAQ reading is above set...

Страница 35: ...n dampers are further open Adjust the EXH SET potentiometer lower counterclockwise toward 2V to energize fans when dampers are further closed Thirty second delay allows dampers to partially open be fo...

Страница 36: ...Page 36 VIII Wiring Diagrams and Sequence of Operation ZHA UNIT DIAGRAM 1 2 5 15 13 18 14 19 11 20 21 7 8 2 10 11 7 14 6 15 8...

Страница 37: ...133 relay coil which closes K133 1 N O contacts 24VAC is routed to S7 and S8 N C high pressure switches Compressor con tactor K2 is energized 10 K2 closes energizing compressor B2 First Stage Heat com...

Страница 38: ...OSTAT POWER 1 Terminal strip TB1 energizes thermostat components with 24VAC OPERATION 2 TB1 receives data from the electronic thermostat A2 Y1 Y2 W1 W2 G OCP The 24VAC signal from TB1 ener gizes the a...

Страница 39: ...supplies B7 with 0 10 VDC to control the positioning of economizer 4 The EXH power exhaust set point found on the face of A6 is factory set at approximate 50 of the dial range Econ omizer control mod...

Страница 40: ...Page 40 EHA 7 5 15 22 5 30 45 60kW Y VOLTAGE ZHA SERIES UNITS 1 6 3 3 5 4 Heat 2 W2 24V Power R 24V Common C 5...

Страница 41: ...Page 41 EHA 7 5 15 22 5 30 45 60kW G J VOLTAGE ZHA SERIES UNITS 1 6 3 3 4 5 5 Heat 2 W2 24V Power R 24V Common C...

Страница 42: ...into defrost mode 3 24VAC W2 signal is routed from the thermostat through TB1 to P2 2 After S15 N C primary limit and S19 sec ondary limit is proved the electric heat contactor K15 is energized 4 N O...

Страница 43: ...Page 43 TYPICAL MSAV UNIT DIAGRAM 2 5 6 4 6 4 1 2 5...

Страница 44: ...speed in the same manner as G Blower Demand Y2 Cooling Demand 4 K186 relay is energized and K186 N O contacts close 5 The blower demand closes K117 N O contacts 24VAC is routed through K117 and K186 c...

Отзывы: