SPECIFICATIONS
10 TON
General Data
Nominal Tonnage
10 Ton
10 Ton
Model Number
ZHA120S4B
ZHA120S4M
Efficiency Type
Standard
Standard
Blower Type
Constant Air Volume (CAV)
MSAV (Multi-Stage Air Volume)
Cooling
Performance
Gross Cooling Capacity - Btuh
121,900
121,900
1
Net Cooling Capacity - Btuh
118,000
118,000
AHRI Rated Air Flow - cfm
3600
3600
Total Unit Power - kW
10.7
10.7
1
EER (Btuh/Watt)
11.0
11.0
1
IEER (Btuh/Watt)
11.3
12.5
Refrigerant Type
R-410A
R-410A
Refrigerant Charge Furnished
Circuit 1
16 lbs. 0 oz.
16 lbs. 0 oz.
Circuit 2
14 lbs. 12 oz.
14 lbs. 12 oz.
Heating
Performance
1
Total High Heat Capacity - Btuh
116,000
116,000
Total Unit Power - kW
10.3
10.3
1
C.O.P.
3.3
3.3
1
Total Low Heat Capacity - Btuh
70,000
70,000
Total Unit Power (kW)
9.1
9.1
1
C.O.P.
2.25
2.25
Electric Heat Available - See page 3
15, 22.5, 30, 45 and 60 KW
Compressor Type (number)
Scroll (2)
Scroll (2)
Outdoor
Coils
Net face area (total) - sq. ft.
26.2
26.2
Tube diameter - in.
3/8
3/8
Number of rows
3
3
Fins per inch
20
20
Expansion device type
Balance port TXV, removable head
Outdoor
Coil Fans
Motor - (No.) hp
(2) 1/2
(2) 1/2
Motor rpm
1075
1075
Total Motor watts
960
960
Diameter - (No.) in.
(2) 24
(2) 24
Number of blades
3
3
Total Air volume - cfm
9000
9000
Indoor
Coils
Net face area (total) - sq. ft.
13.54
13.54
Tube diameter - in.
3/8
3/8
Number of rows
4
4
Fins per inch
14
14
Drain connection - Number and size
(1) 1 in. NPT coupling
Expansion device type
Refrigerant Metering Orifice (RFC)
2
Indoor
Blower and
Drive
Selection
Nominal motor output
2 hp, 3 hp, 5 hp
Maximum usable motor output
(US Only)
2.3 hp, 3.45 hp, 5.75 hp
Motor - Drive kit number
2 hp
Kit 1
590-890 rpm
Kit 2
800-1105 rpm
Kit 3
795-1195 rpm
3 hp
Kit 4
730-970 rpm
Kit 5
940-1200 rpm
Kit 6
1015-1300 rpm
5 hp
Kit 10
900-1135 rpm
Kit 11
1040-1315 rpm
Kit 12
1125-1425 rpm
Blower wheel nominal diameter x width - in.
(1) 15 X 15
(1) 15 X 15
Filters
Type of filter
Disposable
Number and size - in.
(4) 20 x 24 x 2
Electrical characteristics
208/230V, 460V or 575V - 60 hertz - 3 phase
NOTE - Net capacity includes evaporator blower motor heat deduction. Gross capacity does not include evaporator blower motor heat deduction.
1
AHRI Certified to AHRI Standard 340/360:
Cooling Ratings
- 95°F outdoor air temperature and 80°F db/67°F wb entering indoor coil air.
High Temperature Heating Ratings
- 47°F db/43°F wb outdoor air temperature and 70°F entering indoor coil air.
Low Temperature Heating Ratings
- 17°F db/15°F wb outdoor air temperature and 70°F entering indoor coil air.
2
Using total air volume and system static pressure requirements determine from blower performance tables rpm and motor output required. Maximum usable output of
motors furnished are shown. In Canada, nominal motor output is also maximum usable motor output. If motors of comparable output are used, be sure to keep within
the service factor limitations outlined on the motor nameplate.
NOTE – Units equipped with MSAV
®
(Multi-Stage Air Volume) option are limited to a motor service factor of 1.0.