Page 41
XP25
During thermostat demand of the outdoor control, the 7-segment display shows the cooling or heating (percent demand), fan RPM, error codes if present, and
outdoor ambient, Coil and liquid line temperatures need to be manually enabled to be displayed.
How to enable liquid line temperature information on a 7-segment display
Both coil and liquid line temperatures can be enabled for display
either during normal demand operation or while in idle mode.
PERCENTAGE OF
MAXIMUM CAPACITY
FAN RPM
OUTDOOR
AMBIENT
ACTIVE ERRORS
ONLY
OUTDOOR COIL
TEMP (*)
OUTDOOR LIQUID
LINE TEMP
NOTE - IF SYSTEM POWER IS RECYCLED, DISPLAY STRING
REVERTS BACK TO DEFAULT. THE ABOVE PROCEDURE
NEEDS TO BE REPEATED TO ENABLE OUTDOOR COIL AND
LIQUID LINE TEMPERATURE INFORMATION. ALL TEMPER
ATURES ARE DISPLAYED IN FAHRENHEIT.
Outdoor control is either in
IDLE
mode or heating / cooling
demand)
To enable temperature display, push
and hold button next to 7-segment
display until
dash
symbol appears
and immediately release button.
Once dash starts flashing, proceed
to next step.
Wait until unit returns
to a active demand or
idle mode.
Push and hold the button until the solid
appears on the 7-segment display.
Then, immediately release the button.
Yes
_
_
Push and hold button until the
flashing
stops flashing then
release button. The display shows
the coil and liquid line temperature if
there is an active demand running.
NOTE - The coil and liquid line temperature readings are temporarily shown on the outdoor 7-segment display when the iComfort Wi-Fi
®
diagnostic screen is
accessed.
Figure 21. Enabling Liquid Line Temperature Information
Содержание XP25-024-230-01
Страница 46: ...Page 46 XP25 Typical Unit Wiring Diagrams Figure 24 Typical Unit Wiring XP25 024 and 036...
Страница 47: ...Page 47 XP25 Figure 25 Typical Unit Wiring XP25 048 and 060...
Страница 73: ...Page 73 XP25 Perform DC volt checks 19 23 VDC between FAN PWM and COM Figure 54 VAC Voltage Check...
Страница 89: ...Page 89 XP25 Figure 67 XP25 Charging Sticker...