Page 16
XP25
Brazing Connections
Use the procedures outlined in figures 9 and 10 for brazing
line set connections to service valves.
WARNING
When using a high pressure gas such as
dry nitrogen to pressurize a refrigeration or
air conditioning system, use a regulator
that can control the pressure down to 1 or
2 psig (6.9 to 13.8 kPa).
CAUTION
Brazing alloys and flux contain materials which are
hazardous to your health.
Avoid breathing vapors or fumes from brazing operations.
Perform operations only in well-ventilated areas.
Wear gloves and protective goggles or face shield to
protect against burns.
Wash hands with soap and water after handling brazing
alloys and flux.
WARNING
Fire, Explosion and Personal Safety Haz
ard.
Failure to follow this warning could result in
damage, personal injury or death.
Never use oxygen to pressurize or purge
refrigeration lines. Oxygen, when exposed
to a spark or open flame, can cause a fire
and/or an explosion, that could result in
property damage, personal injury or death.
Содержание XP25-024-230-01
Страница 46: ...Page 46 XP25 Typical Unit Wiring Diagrams Figure 24 Typical Unit Wiring XP25 024 and 036...
Страница 47: ...Page 47 XP25 Figure 25 Typical Unit Wiring XP25 048 and 060...
Страница 73: ...Page 73 XP25 Perform DC volt checks 19 23 VDC between FAN PWM and COM Figure 54 VAC Voltage Check...