Outdoor Control Operation, Checkout and Status / Error Codes
OPERATION:
The outdoor control is a microprocessor-based device for use with variable-capacity compressors up to 5-tons in capacity
operating on 24VAC residential power. The outdoor control integrates the functionality of maintaining compressor speed,
demand, defrost and fan PWM controls. The outdoor control is self-configuring. During start-up the outdoor control selects
one of two configurations variable-capacity air conditioner or variable-capacity heat pump
.
PUSH
BUTTON
7-SEGMENT
DISPLAY
WHEN UNIT IS IN PUMP-DOWN MODE,
WILL BE DISPLAYED
ON 7-SEGMENT.
TO ACTIVATE PUMP-DOWN MODE, REFER TO PUMP-DOWN
CYCLE SEQUENCE ON PAGE 39.
NOTE - The green LED located on the outdoor control flashes when
communication occurs between the outdoor control and either the
thermostat or the inverter.
Figure 48. Outdoor Control Unit
STATUS CODES:
Table 13. Outdoor Control 7-Segment Display Alert Codes - Outdoor Control Status
NOTE - System fault and lockout codes take precedence over system status codes (cooling, heating operating percentages or defrost/dehumidification).
Only the latest active fault or lockout codes are displayed (if present). If no fault or lockout codes are active, then system status codes are displayed. Alert
codes are also displayed on the iComfort Wi-Fi
®
or iComfort
®
S30 thermostat.
Alert Codes
Priority
Alarm Description
Possible Causes and Clearing Alarm
E 600
Critical
Compressor has
been cycled OFF on
utility load shedding.
Load shedding function: Provides a method for a local utility company to limit the maximum power
level usage of the outdoor unit. The feature is activated by applying 24 volts AC power to the L and C
terminals on the outdoor control.
E 601
Critical
Outdoor unit has
been cycled OFF on
low temperature
protection.
Low temperature Protection: Outdoor unit will not operate when the outdoor temperature is at or
below 4°F (20°C). If the unit is operating and the outdoor temperature drops below 4°F (20°C),
the unit will continue to operate until the room thermostat is satisfied or the outdoor temperature
drops to 15°F (26°C). (Outdoor unit ambient sensor provides temperature readings.)
Содержание XC20-024-230-01
Страница 45: ...45 XC20 Unit Wiring Diagrams Figure 22 Typical Unit Wiring XC20 024 and 036...
Страница 46: ...46 XC20 Figure 23 Typical Unit Wiring XC20 048 and 060...
Страница 48: ...48 XC20 Factory Wiring Diagrams Figure 25 Typical Factory Wiring XC20 024 and 036...
Страница 49: ...49 XC20 Figure 26 Typical Factory Wiring XC20 048 and 060...