62
XC20
ERROR:
Table 12. Outdoor Control 7-Segment Display Alert Codes - Top Cap Switch
NOTE - System fault and lockout codes take precedence over system status codes (cooling, heating operating percentages or defrost/dehumidification).
Only the latest active fault or lockout codes are displayed (if present). If no fault or lockout codes are active, then system status codes are displayed. Alert
codes are also displayed on the iComfort Wi-Fi
®
thermostat.
Alert
Codes
Priority
Alarm Description
Possible Causes and Clearing Alarm
E 422
Moderate
Compressor top cap switch ex
ceeding thermal limit.
Issue
: One of the wires from the top cap switch had pulled off one of the TP termin
als on the outdoor control board.
Corrective Action
: Reconnected wire onto top cap terminal.
E 442
Critical
The top cap switch has opened 5
times within one hour. As a result,
the outdoor unit is locked out
.
When compressor thermal protection sensor opens 5 times within 1 hour, outdoor stops
working. To clear, disconnect power to outdoor unit and restart.
Reactor Operations, Checkout and Status / Error Codes
OPERATION:
Reactor (Inductor or choke) is a passive twoterminal electrical component that stores energy in its magnetic field. Reactors
are one of the basic components used in electronics where current and voltage change with time, due to the ability of induct
ors to delay and reshape alternating currents.
CHECKOUT
:
Main Power
ON –
Voltage
IN
reactor should be the same as the voltage
OUT
. With main power
OFF
and reactor disconnec
ted from system; resistance between leads should be the same (brown
IN
to brown
OUT
, blue
IN
to blue
OUT
).
STATUS CODES
:
None
ERROR CODES:
None
Voltage “IN” same as Voltage “OUT”
Figure 42. XC/XP 20-024 and -036 Reactor
208/240
Voltage
“IN”
208/240
Voltage
“OUT”
Figure 43. XC/XP 20-048 and -060 Reactor
Содержание XC20-024-230-01
Страница 45: ...45 XC20 Unit Wiring Diagrams Figure 22 Typical Unit Wiring XC20 024 and 036...
Страница 46: ...46 XC20 Figure 23 Typical Unit Wiring XC20 048 and 060...
Страница 48: ...48 XC20 Factory Wiring Diagrams Figure 25 Typical Factory Wiring XC20 024 and 036...
Страница 49: ...49 XC20 Figure 26 Typical Factory Wiring XC20 048 and 060...