background image

6

Step 3.

  Keep the combustion air damper and 

the by-pass damper opened for 10 minutes 

before closing it. It will ensure sufficient tem-

peratures for combustor light-off. 
To refuel the Villa Vista™ fireplace when the 

unit is still hot (Some burning fuel remaining 

or a glowing combustor)

Step 1.

 Open the by-pass and air controls 

fully. 

Step 2.

  Open the door approximately 1 inch, 

wait five seconds until the draft is stable and 

then open it completely. load the fuel, close 

the door and by-pass (temperatures within the 

firebox should be enough to maintain catalytic 

operation)

Smoking – Causes and Troubleshooting

To reduce the likelihood of smoking when 

opening the doors, set the air damper to the 

“accelerated combustion” position and open 

the by-pass damper before opening the doors. 

Your fireplace has been designed and tested to 

provide smoke free operation. Occasionally, 

there may be a small amount of smoking upon 

lighting the fire, until the chimney heats up but 

this should not continue.  If the fireplace does 

continue to smoke, it is probably for one of the 

following reasons:

A.  The door is partly open - 

Open the door 

fully.

B.   Negative pressure in the house - 

As the 

fire burns, air goes up the chimney.  This 

air must be replaced through leakage into 

the house or through the outside air duct.  

When operating the Villa Vista fireplace, 

open a nearby window temporarily to check 

if there is adequate air replacement.

C.  Fans operating (e.g. range hood) - 

These 

fans draw air out of the house and may 

actually cause a negative pressure in the 

house.  Turn off all fans and open a nearby 

window to determine if this is the cause of 

the problem.

D.  Wet wood - 

Wet or tarred wood will smoul-

der and smoke instead of burn properly. 

Your dealer can help you determine if you 

have properly seasoned wood for burn-

ing.

E.   Dirty or blocked chimney - 

Check to make 

sure the chimney is clear and reasonably 

clean. If dirty call a certified chimney sweep 

or use a properly sized chimney brush to 

clean.

F.   Chimney not long enough - 

The minimum 

chimney height is 12 feet, not including the 

fireplace height.  The chimney must extend 

at least 3 feet (915 mm) above its point of 

contact with the roof and at least 2 feet (610 

mm) higher than any roof or wall within 10 

feet (3 m) of it.  

G.  Poor chimney draft - 

With no fire, there 

should be sufficient draft to exhaust cigarette 

smoke introduced under the baffle.  Chim-

neys installed against an outside wall without 

protection may generate back draft problems 

which will cause start-up problems. To 

prevent this, open a nearby window, roll up 

a piece of paper and light it. 

Then, hold it in the upper part of the firebox 

to warm up the chimney.  Wait until the draft 

is sufficient, then start the fire.

H.   Blower for forced air kit operating  -

 Make 

sure that the blower is at the “off” position 

when you open the fireplace door for reload-

ing.

IMPORTANT CAUTIONS

A. Do not block the hot air vents to the fire-

place as this will cause the fireplace to 

overheat.

B. Never use gasoline, gasoline-type lantern 

fuel, kerosene, charcoal lighter fluid, or 

similar liquids to start or ‘freshen up’ a fire 

in this fireplace.  Keep all such liquids well 

away from the fireplace while it is in use.

C. Do not burn coal.  The sulphur in coal will 

corrode the firebox and chimney.

D. Do not burn driftwood which has been in the 

ocean or salt water.  The salt will corrode 

the firebox and chimney.

E. Do not operate the unit with the door partly 

open since this may cause smoke to be 

drawn into the room.

F.  Do not burn wood in the area in front of the 

log retainers.

G. Do not abuse the unit by burning paper, or 

cardboard or construction material such as 

pressed wood, plywood or lumber.

H. Do not allow the wood to smoulder or burn 

without flame, since this will produce exces-

sive creosote in the unit as well as increased 

particulate emissions.

MAINTAINING YOUR FIREPLACE

Creosote

When wood is burned slowly, it produces tar 

and other organic vapors which combine with 

expelled moisture to form a black deposit called 

creosote which accumulates on the flue lining.  

When ignited, this creosote makes an extremely 

hot fire.  If the creosote accumulation is large, 

a creosote fire in the chimney can damage the 

chimney and overheat the surrounding wood 

framing.  Creosote formation in a chimney can 

be minimized by making small hot fires rather 

than slow burning, smouldering fires and by 

proper refuelling techniques.

Chimney Maintenance

Regular chimney inspection and maintenance 

combined with proper operation will prevent 

chimney fires. Keep your chimney clean.  Do not 

allow more than 1/16" creosote build up in your 

chimney.  The amount of creosote will depend 

on variables such as frequency of use and type 

of fire.  We recommend that you:

1.

  Initially inspect the chimney system weekly.  

From this, you will learn how often it will 

be necessary to clean your chimney.

2.

  Have your chimney cleaned by a qualified 

chimney sweep.  If you wish to clean it 

yourself, we recommend using a stiff plastic 

       WARNING 

To prevent damage to your com-

bustor, do not:

• 

 

Drop the combustor (which is 

fragile compared to the rest 

of the unit – so handle with 

care)

• 

 

Run water or compressed air 

through the combustor

• 

 

Try to clean the combustor 

with any sharp tool

or non-metallic brush.  If a metal brush is 

used, its size should be slightly smaller than 

the flue to avoid damaging the chimney.  

Do not use a brush that will scratch the 

stainless steel interior of the chimney.

3.

  Do not expect chemical cleaners to keep 

your chimney clean.  The rain cap can be 

removed for inspection and/or cleaning of 

the chimney.  Using gloves, firmly grip the 

lower portion of the rain cap.  Turn the cap 

1/8 of a turn counter-clockwise and lift it 

off the chimney.

 

Before performing chimney sweep, open 

the by-pass and remove the combustor. 

Remove dust accumulation after chimney 

sweep and put the combustor back in place.

Dealing With A Chimney Fire

Regular chimney maintenance and inspection 

can prevent chimney fires.  If you have a chimney 

fire, follow these steps:

1.  Close the fireplace doors and the combus-

tion air damper.

2.  Alert your family of the possible danger.

3.  If you require assistance, alert your fire 

department.

4.  If possible, use a dry chemical fire extin-

guisher, baking soda or sand to control the 

fire.  Do not use water as it may cause a 

dangerous steam explosion.

5.  Check outside to ensure that sparks and hot 

embers coming out of the chimney are not 

igniting the roof.

6.  Do not use the fireplace again until your 

chimney and fireplace have been inspected 

by a qualified chimney sweep or a Fire 

Department Inspector.

Catalytic Combustor

The Villa Vista™ fireplace is designed with a 

catalytic combustor which will reduce pollution 

emissions and creosote build up while improv-

ing thermal efficiency.  In order to optimize and 

maintain the combustor performance, it is im-

portant to visually check the combustor at least 

3 times during the heating season to determine 

if physical degradation has occurred.
Catalytic combustors require little maintenance.  

Cleaning the combustor once a year, preferably 

when your flue system is serviced, is sufficient 

for most users.  

Содержание VILLA VISTA 850028M

Страница 1: ...safety gate or barrier screen A French manual is available upon request Order P N 850028CF Ce manuel d installation est disponible en francais simplement en faire la demande Numéro de la pièce 850028CF Wood Burning Fireplaces P N 850028M REV L 05 2013 Villa Vista VILLA VISTA This installation manual will enable you to obtain a safe efficient and dependable installation of your fireplace system Ple...

Страница 2: ...ructionconditions inadequate chimney heights adverse wind conditions and or unusualenvironmentalfactorsor conditions beyond our control WARNING The Villa Vista fireplace must be installed with an outside air kitintake whichisincludedwith the fireplace WARNING THE FIREPLACE MUST BE OPER ATED WITH THE DOORS FULLY OPENEDORDOORSFULLYCLOSED IF THE DOORS ARE LEFT PARTLY OPENED GASANDFLAMEMAYBE DRAWN OUT...

Страница 3: ...on Page 20 Chimney Chase And Multiple Terminations Page 20 Masonry Applications Page 21 Installation Accessories Page 22 Replacement Parts Page 23 Specifications Page 23 Clearance To Combustible Page 23 Chimney Components Lists Page 24 Product Reference Information Page 26 THE FIREPLACE INTRODUCTION The Villa Vista fireplace is an energy efficient heat circulating close combustion fireplace using ...

Страница 4: ... or 6 fires should be small fires of short duration about 30 to 60 minutes This will help cure the refractory bricks Ashes that will accumulate in the ashtray will protect it from intense heat During the first few fires of this appliance there may be some odor and smoke due to the curing of the paint dust ac cumulation and burning off of lubricants used in the manufacturing process It may set off ...

Страница 5: ...ors includingchimney length and the moisture content of the wood This method of burning should be used only after operating the Villa Vista fireplace with the aircontrolopenedtoproduceahotfireforabout an hour Slow combustion can be used at night in order to reduce the heat output and prolong the burn The loading time will be between 6 10 hours Be aware that the glass will get dirty using this sett...

Страница 6: ...e this may cause smoke to be drawn into the room F Do not burn wood in the area in front of the log retainers G Do not abuse the unit by burning paper or cardboard or construction material such as pressed wood plywood or lumber H Do not allow the wood to smoulder or burn withoutflame sincethiswillproduceexces sivecreosoteintheunitaswellasincreased particulate emissions MAINTAINING YOUR FIREPLACE C...

Страница 7: ...c gases Figure 7 5 4 1 2 3 1 Front Refractory 2 Bottom Refractory 3 Left Side Refractory 4 Right Side Refractory 5 Back Refractory Refractory Replacement The intense heat of the fire will normally cause hairline cracks in the refractory These cracks canbeminimizedbypropercuringasdescribed in First Fires They will not normally dimin ish the effectiveness of the refractory If large cracks develop th...

Страница 8: ...the door using the hinge screws see Figure 9 Figure 8 HINGE SCREWS GASKET ADJUSTEMENT SCREW DOOR HINGE SCREWS Figure 9 DO NOT USE CHEMICAL GLASS CLEANERS ON PAINTED SURFACES AS IT MAY CAUSE THE PAINT TO PEEL CAUTION DONOTALLOWWINDOWCLEANER TO GET IN CONTACT WITH DOOR GASKET OR PAINT ON FACADE OR DOOR ONCE CLOSED CONTACT OF GLASS CLEANER WITH THE FIREPLACE FACADE CAN PROVOKE PAINT PEELING OFF Gaske...

Страница 9: ...Vista fireplace may be installed directly on a combustible floor The supplied safety metal strip must be positioned as fol lows One half under the front of the fireplace and the other half must extend on the floor over which the hearth extension will be built see Figure 10A The safety metal strip must cover the entire width of the fireplace The combustible floor in front of the fireplace must be c...

Страница 10: ...e 11 Framing Dimensions Notes Diagrams illustrations and photographs are nottoscale consultinstallationinstructions Product designs materials dimensions specifications colorsandpricesaresubjectto change or discontinuance without notice Allframingdimensionscalculatedfor1 2 dry wallatthefireplaceface Ifsheathingthechase or finishing with other thickness materials calculations will need to be made Th...

Страница 11: ...ion materials must not be in contact with the fireplace or in theenclosureframeasdescribedin Enclosure section NOTE Localcodesmaynotrequirefirestopping at the ceiling levels for outside chase installa tions However it is recommended for safety and the reduction of heat loss WARNING Ifinsulationisused thefireplace must not be placed directly against it Insulation or vapor barriers if used must firs...

Страница 12: ...the unit 38 and a height of 54 from the base of the appliance see Figure 15 3 Non combustible materials such as brick stone or ceramic tile may project in front of and onto the fireplace facing see Figure 14 2 x 3 MIN 54 1 2 GYPSUMBOARD SPACER MANTEL Figure 14 2 x 3 MIN SPACER 1 2 GYPSUMBOARD NON COMBUSTIBLE FACING Figure 15 COMBUSTIBLE CAN NOT PROJECT OVER OR IN FRONT OF THE FIREPLACE 38 54 Mante...

Страница 13: ...imum length See Figure 17 The height of the louver must be measured from the base of the Villa Vista fireplace to the middle point of the louver When installing the double outlet system the hotairoutletscanbeinstalledinthesameroom as the fireplace or one or both of the outlets can be installed in adjacent or upper rooms Installing the ducts at different elevations will tend to exhaust more heat ou...

Страница 14: ...al heating system Malfunction of the heating system s fan will cause the furnace duct to overheat A furnace duct is only single wall and not double wall as is required for the Villa Vista fireplace hot air exhaust 7 Use only IHP grills and components as described in this manual Other grills or registers forexample maybetoorestrictive and may overheat the fireplace or ceiling 8 Do not use insulated...

Страница 15: ... basement or garage 4 The air intake register should be installed where it is not likely to be blocked by snow or exposed to extreme wind and well away fromautomobileexhaustfumes gasmeters and other vents 5 Theductandregistermaybeinstalledabove or below floor level Outside Air Installation Make a 4 1 4 110 mm hole in the outside wall of the house at the chosen location From outside place the outsi...

Страница 16: ...o the chimney for every 2000 feet 600 m above sea level 5 All chimney installations must include at least one support The maxi mum chimney length that can be supported by the fireplace is 20 feet 8m for ACBI chimney and 12 feet 3 7 m for ASHT chimney 6 The chimney must extend at least 3 feet 915 mm above its point of contact with the roof and at least 2 feet 610 mm higher than any wall roof or bui...

Страница 17: ...stallauniversalsupportfasteningthestrapsto thesurroundingjoists ASHT Installsupport as required see Chimney Support Installation Section on Page 20 4 Puttheroofflashinginplaceandsealthejoint between the roof and the flashing with roofing pitch seeFigures25and26 Forslopingroofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashing to the roof using roofing n...

Страница 18: ... 3 8 545mm 19 483mm 21 3 8 545mm CrossSlopeHoleSize Putthechimneycapinto place Washtheroofflashingwithasolvent or vinegar thenpaintitwithrust proof paint Table 2 1 Install the first elbow Turn it in the required direction ACBI To lock it in place turn 1 8 of a turn Fasten the straps attached to the elbow to the surrounding frame using nails or drywall screws ASHT and S2100 Fasten it to the chimney...

Страница 19: ...SHT 15º Deviation 3 5 16 84 mm 4 5 16 110 mm 5 7 8 149 mm 7 7 16 189 mm 10 1 2 268 mm 13 5 8 346 mm 15 3 8 391 mm 16 7 16 418 mm 18 457 mm 19 1 2 495 mm 22 5 8 575 mm Length 15 11 16 398 mm 19 9 16 497 mm 25 3 8 645 mm 31 3 16 792 mm 42 3 4 1086 mm 54 3 8 1381 mm 60 15 16 1548 mm 64 13 16 1646 mm 70 9 16 1792 mm 76 3 8 1940 mm 87 2210 mm 30º Deviation 7 7 16 189 mm 9 7 16 240 mm 12 7 16 316 mm 15 ...

Страница 20: ...pport When installing a support slightly lift the chim neysystemsotheweightwilllieonthesupport notonthefireplacetoreduceexpansionnoises This support has two possible uses 1 For ASHT it must be used on a roof to support the chimney 2 It may be used on a floor ceiling or roof above an offset to support the chimney above the offset 3 It may be used on a floor ceiling or roof above as a supplementary ...

Страница 21: ...he middle of the oval drill a hole in the masonry chimney at 45 or 30 NOTE 45 offsets allowed in Canada only 3 Increase the size of the hole until a 45º or 30º Tubinox liner elbow can be easily slipped through 4 Slide the liner down from the top of the masonry chimney until you reach the hole level 5 Slip through the hole a 45 or 30 liner elbow and connect it to the liner 6 Add a small liner secti...

Страница 22: ...himney for Relining Masonry Chimneys Tubinox chimney or Projet SS 7 diameter with adaptor for installation in a masonry chimney NOTES j Projet Nova Temp HT6000 is equivalent to S2100 k Projet Nova Temp HT6103 is equivalent to ASHT l This appliance is equipped with the ASHT Chimney Adaptor When other chimney is used a chimney adaptor for the chimney will be required m Chimney Adaptor S2100 HT6000 f...

Страница 23: ...r BISZY VRUW VRUW Thermo disk on offblowercontrol forBISZY VTU VTU Blower to flexible pipe adaptor BISAVF BISAVF Backdraft damper BISBD BISBD Fireplace to Flex adaptor and 2 clamps BISAF BISAF CLEARANCE TO COMBUSTIBLES The following clearances meet the minimum requirements for a safe installation Side wall 24 610 mm measured from the doors edge Ceiling 6 8 2032 mm measured from the base of the fir...

Страница 24: ...rts Support Section 10 long ACBI7SL H3263 Universal Support AC10SU H3265 Roof Flashings 1 12 7 12 5 30 Adjustable ACBI7FAR H3276 8 12 12 12 30 45 Adjustable ACBI7FBR H3277 Flat Roof Flashing includes spacer and collar ACBI7FR H3275 Misc Description Cat Part No Firestop ACBI7BF H3268 Radiation Shield ACBI7RS H3269 Attic Radiation Shield ACBI7RSA H3270 Telescopic Attic Radiation Shield ACBI7RST H327...

Страница 25: ...lbow 30 7LE30 7LE30 Elbow 45 7LE45 7LE45 Elbow 90 7LE90 7LE90 Rain Termination Cap regular 7LCS 7LCS Rain Termination Cap deluxe 7LCC 7LCC Supports Top Support 7LST 7LST Support Assembly 7LSA 7LSA Interior Support 7LSB 7LSB Adaptor Flexible Pipe male 7LAAM 7LAAM Adaptor Flexible Pipe female 7LAAF 7LAAF Stainless Steel Flex 5 Ft Long 7LLFLEX 7LLFLEX Adjustable Insulated Wall Radiation Shield 6 to 1...

Страница 26: ...s list Use only parts sup plied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the appliance 2 The serial number of the appliance 3 The part number 4 The description of the part 5 The quantity required ...

Отзывы: