background image

Page 9

Revised 05−2009

TPA*S4

A − Plumbing

Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections). Use Lennox
L15 (sweat) series line sets as shown in table 2.

TABLE 2

Refrigerant Line Sets

Model

Field
Connections

Recommended Line Set

Liquid
Line

Vapor
Line

Liquid
Line

Vapor
Line

L15
Line Sets

−036
−048

3/8 in.
(10 mm)

7/8 in
(22 mm)

3/8 in.
(10
mm)

7/8 in
(22 mm)

L15−65
15 ft. − 50 ft.
(4.6 m − 15
m)

−060

3/8 in.
(10 mm)

1−1/8 in.
(29 mm)

3/8 in.
(10
mm)

1−1/8 in.
(29 mm)

Field
Fabricated

B − Service Valves

The liquid and vapor line service valves (figures 12 and 13)
and gauge ports are accessible from outside the unit.

Each valve is equipped with a service port. The service ports
are used for leak testing, evacuating, charging and checking
charge. A Schrader

®

 valve is factory installed. A service port

cap is supplied to protect the Schrader

®

 valve from

contamination and serve as the primary leak seal.

NOTE-Always keep valve stem caps clean.

To Access Schrader

®

 Port:

 1 −  Remove service port cap with an adjustable wrench.

 2 −  Connect gauge to the service port.

 3 −  When  testing  is  completed,  replace  service  port  cap.

Tighten finger tight, then an additional 1/6 turn.

To Open Liquid or Vapor Line Service Valve:

 1 −  Remove stem cap with an adjustable wrench.

 2 −  Using service wrench and hex head extension (5/16 for

vapor line and 3/16 for liquid line), back the stem out
counterclockwise until the valve stem just touches the
retaining ring.

 3 −  Replace stem cap and tighten finger tight, then tighten an

additional 1/6 turn.

Do not attempt to backseat this valve. Attempts to
backseat this valve will cause snap ring to explode
from valve body under pressure of refrigerant.
Personal injury and unit damage will result.

DANGER

To Close Liquid or Vapor Line Service Valve:

 1 −  Remove stem cap with an adjustable wrench.

 2 − Using service wrench and hex head extension (5/16 for

vapor line and 3/16 for liquid line), turn stem clockwise to
seat the valve. Tighten firmly.

 3 −  Replace stem cap. Tighten finger tight, then tighten an

additional 1/6 turn.

FIGURE 12

LIQUID LINE SERVICE VALVE (VALVE OPEN)

SCHRADER

®

VALVE

SERVICE

PORT

SERVICE

PORT

CAP

INSERT HEX

WRENCH HERE

TO INDOOR COIL

TO COMPRESSOR

STEM CAP

SCHRADER

®

 VALVE OPEN

TO LINE SET WHEN VALVE IS

CLOSED (FRONT SEATED)

SERVICE

PORT

SERVICE

PORT CAP

RETAINING RING

STEM CAP

TO

COMPRESSOR

INSERT HEX

WRENCH HERE

LIQUID LINE SERVICE VALVE (VALVE CLOSED)

VALVE FRONT

SEATED

TO INDOOR COIL

SUCTION LINE (BALL TYPE) SERVICE VALVE

(VALVE OPEN)

FIGURE 13

SCHRADER

®

 CORE

SERVICE PORT

SERVICE

PORT

CAP

STEM CAP

FROM INDOOR COIL

TO COMPRESSOR

STEM

USE ADJUSTABLE WRENCH

ROTATE STEM CLOCKWISE 90

_

 TO CLOSE

ROTATE STEM COUNTER-CLOCKWISE 90

_

 TO OPEN

BALL

(SHOWN OPEN)

Содержание T?CLASS TPA S4

Страница 1: ...allation adjustment alteration service or maintenance can cause personal injury loss of life or damage to property Installation and service must be performed by a licensed professional installer or eq...

Страница 2: ...tdoor Fan Diameter in No of Blades 18 4 22 4 22 4 22 4 Motor hp 208 230V 1 5 460V 1 6 1 3 1 3 1 4 Cfm 2450 3890 3890 3830 Rpm 1100 1080 1085 830 Watts 190 400 375 330 Shipping Data lbs 1 package 180 2...

Страница 3: ...harge sufficient for 15 ft length of refrigerant lines 2 HACR type circuit breaker or fuse 3 Refer to National or Canadian Electrical Code manual to determine wire fuse and disconnect size requirement...

Страница 4: ...box See figure 3 24V THERMOSTAT TERMINAL STRIP FIGURE 3 W1 C L R O Y1 1 Compressor Contactor K1 The compressor is energized by a contactor located in the control box See figure 2 Three pole contactor...

Страница 5: ...utes have passed If the jumper is not removed until after the additional 5 second period has elapsed the defrost will terminate and the test option will not function again until the jumper is removed...

Страница 6: ...ESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls figure 8 1 The centrifugal action of the orbiting scroll s...

Страница 7: ...OTOR SHAFT D Reversing Valve L1 and Solenoid A refrigerant reversing valve with electro mechanical solenoid is used to reverse refrigerant flow during unit operation The reversing valve requires no ma...

Страница 8: ...EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD DISTRIBUTOR INDOOR COIL TO HFC 410A DRUM FIGURE 11 TPA S4 HEATING CYCLE SHOWING MANIFOLD GAUGE CONNECTIONS OUTDOO...

Страница 9: ...n adjustable wrench 2 Using service wrench and hex head extension 5 16 for vapor line and 3 16 for liquid line back the stem out counterclockwise until the valve stem just touches the retaining ring 3...

Страница 10: ...es and within the system Regulator setting must not exceed 150 psig 1034 kpa Failure to use a regulator can cause equipment failure resulting in injury or death C Evacuating the System 1 Attach gauge...

Страница 11: ...ough the outdoor coil to achieve pressures in the 200 250 psig 1379 1724 kPa range These higher pressures are necessary for checking the charge Block equal sections of air intake panels and move obstr...

Страница 12: ...290 74 307 73 300 73 309 62 20 7 283 58 298 61 286 60 300 56 1 These are most popular match up pressures Indoor match up indoor air quality and indoor load cause pressures to vary 2 Temperature of th...

Страница 13: ...23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20 19 18 17 17 16 15 15 1...

Страница 14: ...per 1 5m NOTE If line length is greater than 15 ft 4 6 m add this amount If line length is less than 15 ft 4 6 m subtract this amount Subcooling Charging Method Requirements these items are required f...

Страница 15: ...temperature record in the LIQ space 7 Read the liquid line pressure then find its corresponding temperature in the temperature pressure table 13 and record it in the SAT space 8 Subtract LIQ temp fro...

Страница 16: ...32 100 8 67 190 9 102 326 4 4 43 1 33 102 9 68 194 1 103 331 2 45 6 34 105 69 197 3 104 335 7 0 48 2 35 107 1 70 200 6 105 340 5 1 49 5 36 109 2 71 203 9 106 345 3 2 50 9 37 111 4 72 207 2 107 350 1 3...

Страница 17: ...rgizing the reversing valve L1 See steps 1 2 and 3 End of FIRST STAGE HEAT See steps 4 5 and 6 DEFROST MODE During heating operation when outdoor coil temperature drops below 35 F 2 C or 42 F 5 5 C de...

Страница 18: ...valve L1 See steps 1 2 and 3 End of FIRST STAGE HEAT See steps 4 5 and 6 DEFROST MODE During heating operation when outdoor coil temperature drops below 35 F 2 C or 42 F 5 5 C defrost switch thermost...

Отзывы: