background image

Page 11

Revised 05−2009

TPA*S4

D − Charging  TPA*S4N41Y through

TPA*S4N42Y

The outdoor unit should be charged during warm weather.
However, applications arise in which charging must occur
in the colder months. 

The method of charging is

determined by the unit’s 

refrigerant metering device

 and

the 

outdoor ambient temperature

.

Measure the liquid line temperature and the outdoor
ambient temperature as outlined below:

1.. Close manifold gauge set valves. Connect the

manifold gauge set to the service valves.

D

low pressure gauge to 

vapor 

valve service port

D

high pressure gauge to 

liquid 

valve service port

2.. Connect the center manifold hose to an upright

cylinder of HFC−410A.

3.. Set the room thermostat to call for heat. This will create

the necessary load for properly charging the system in
the cooling cycle.

4.. Use a digital thermometer to record the outdoor

ambient temperature.

5.. When the heating demand has been satisfied, switch

the thermostat to cooling mode with a set point of 68

_

F

(20

_

C). When pressures have stabilized, use a digital

thermometer to record the liquid line temperature.

6.. The outdoor temperature will determine which

charging method to use. Proceed with the appropriate
charging procedure.

Charge using the Weigh−In Method − Outdoor
Temperature < 65

_

F (18

_

C)

If the system is void of refrigerant, or if the outdoor ambient
temperature is cool, first, locate and repair any leaks and
then weigh in the refrigerant charge into the unit.

1.. Recover the refrigerant from the unit.

2.. Conduct leak check; evacuate as previously outlined.

3.. Weigh in the unit nameplate charge. If weighing

facilities are not available or if charging the unit during
warm weather, use one of the following procedures.

Charge using the Subcooling Method − Outdoor
Temperature  < 65°F (18°C)

When the outdoor ambient temperature is below 65°F
(18°C), use the subcooling method to charge the unit. It
may be necessary to restrict the air flow through the
outdoor coil to achieve pressures in the 200−250 psig
(1379−1724 kPa) range. These higher pressures are
necessary for checking the charge. Block equal sections of
air intake panels and move obstructions sideways until the
liquid pressure is in the 200−250 psig (1379−1724 kPa)
range. See figure 14.

Blocking Outdoor Coil

*Outdoor coil should be blocked one
side at a time with cardboard or plastic
sheet until proper testing pressures are
reached.

cardboard or plastic sheet

*Four−sided unit shown.

FIGURE 14

1.. With the manifold gauge hose still on the liquid service

port and the unit’s pressure stabilized, use a digital
thermometer to record the liquid line temperature.

2.. At the same time, record the liquid line pressure reading.

3.. Use a temperature/pressure chart for HFC−410A to

determine the saturation temperature for the liquid line
pressure reading.

4.. Subtract the liquid line temperature from the saturation

temperature (according to the chart) to determine
subcooling.

5.. Compare the subcooling value results with those in

table 3. If subcooling is greater than shown, recover
some refrigerant. If subcooling is less than shown, add
some refrigerant.

TABLE 3

TPA*S4N41Y through TPA*S4N42Y 

TPA036S4 Subcooling Values for Charging

_

Saturation Temperature

_

Liquid Line Temperature

=

_

Subcooling Value

Model

−036

−042

−048

−060

°F (°C)*

8 (4.4)

6 (3.3)

11 (6.1)

11 (6.1)

*F: +/−1.0°; C: +/−0.5°

Charge using the Approach Method − Outdoor
Temperature > 65

_

F (18

_

C)

The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
indoor temperature should be 70°F (21°C) to 80°F (26°C).
Monitor system pressures while charging.

1.. Record outdoor ambient temperature using a digital

thermometer.

2.. Attach high pressure gauge set and operate unit for

several minutes to allow system pressures to stabilize.

3.. Compare stabilized pressures with those provided in

table 4, Normal Operating Pressures." Pressures
higher than those listed indicate that the system is
overcharged. Pressures lower than those listed
indicate that the system is undercharged. Verify
adjusted charge using the approach method.

Содержание T?CLASS TPA S4

Страница 1: ...allation adjustment alteration service or maintenance can cause personal injury loss of life or damage to property Installation and service must be performed by a licensed professional installer or eq...

Страница 2: ...tdoor Fan Diameter in No of Blades 18 4 22 4 22 4 22 4 Motor hp 208 230V 1 5 460V 1 6 1 3 1 3 1 4 Cfm 2450 3890 3890 3830 Rpm 1100 1080 1085 830 Watts 190 400 375 330 Shipping Data lbs 1 package 180 2...

Страница 3: ...harge sufficient for 15 ft length of refrigerant lines 2 HACR type circuit breaker or fuse 3 Refer to National or Canadian Electrical Code manual to determine wire fuse and disconnect size requirement...

Страница 4: ...box See figure 3 24V THERMOSTAT TERMINAL STRIP FIGURE 3 W1 C L R O Y1 1 Compressor Contactor K1 The compressor is energized by a contactor located in the control box See figure 2 Three pole contactor...

Страница 5: ...utes have passed If the jumper is not removed until after the additional 5 second period has elapsed the defrost will terminate and the test option will not function again until the jumper is removed...

Страница 6: ...ESSURE DISCHARGE PRESSURE The counterclockwise orbiting scroll draws gas into the outer crescent shaped gas pocket created by the two scrolls figure 8 1 The centrifugal action of the orbiting scroll s...

Страница 7: ...OTOR SHAFT D Reversing Valve L1 and Solenoid A refrigerant reversing valve with electro mechanical solenoid is used to reverse refrigerant flow during unit operation The reversing valve requires no ma...

Страница 8: ...EXPANSION CHECK VALVE INDOOR UNIT OUTDOOR UNIT LIQUID LINE SERVICE PORT GAUGE MANIFOLD DISTRIBUTOR INDOOR COIL TO HFC 410A DRUM FIGURE 11 TPA S4 HEATING CYCLE SHOWING MANIFOLD GAUGE CONNECTIONS OUTDOO...

Страница 9: ...n adjustable wrench 2 Using service wrench and hex head extension 5 16 for vapor line and 3 16 for liquid line back the stem out counterclockwise until the valve stem just touches the retaining ring 3...

Страница 10: ...es and within the system Regulator setting must not exceed 150 psig 1034 kpa Failure to use a regulator can cause equipment failure resulting in injury or death C Evacuating the System 1 Attach gauge...

Страница 11: ...ough the outdoor coil to achieve pressures in the 200 250 psig 1379 1724 kPa range These higher pressures are necessary for checking the charge Block equal sections of air intake panels and move obstr...

Страница 12: ...290 74 307 73 300 73 309 62 20 7 283 58 298 61 286 60 300 56 1 These are most popular match up pressures Indoor match up indoor air quality and indoor load cause pressures to vary 2 Temperature of th...

Страница 13: ...23 23 22 22 22 20 19 18 17 16 15 78 23 23 23 22 22 21 21 20 19 18 17 16 15 14 76 22 22 22 21 21 20 19 19 18 17 16 15 14 13 74 21 21 21 20 19 19 18 17 16 16 15 14 13 12 72 20 20 19 18 17 17 16 15 15 1...

Страница 14: ...per 1 5m NOTE If line length is greater than 15 ft 4 6 m add this amount If line length is less than 15 ft 4 6 m subtract this amount Subcooling Charging Method Requirements these items are required f...

Страница 15: ...temperature record in the LIQ space 7 Read the liquid line pressure then find its corresponding temperature in the temperature pressure table 13 and record it in the SAT space 8 Subtract LIQ temp fro...

Страница 16: ...32 100 8 67 190 9 102 326 4 4 43 1 33 102 9 68 194 1 103 331 2 45 6 34 105 69 197 3 104 335 7 0 48 2 35 107 1 70 200 6 105 340 5 1 49 5 36 109 2 71 203 9 106 345 3 2 50 9 37 111 4 72 207 2 107 350 1 3...

Страница 17: ...rgizing the reversing valve L1 See steps 1 2 and 3 End of FIRST STAGE HEAT See steps 4 5 and 6 DEFROST MODE During heating operation when outdoor coil temperature drops below 35 F 2 C or 42 F 5 5 C de...

Страница 18: ...valve L1 See steps 1 2 and 3 End of FIRST STAGE HEAT See steps 4 5 and 6 DEFROST MODE During heating operation when outdoor coil temperature drops below 35 F 2 C or 42 F 5 5 C defrost switch thermost...

Отзывы: