Installing Indoor Metering Device 

This outdoor unit is designed for use in systems that use a
expansion valve metering device at the indoor coil.
See the

 Lennox SSB*H4

 

Product Specification bulletin

 for

approved expansion valve kit match-ups. The expansion
valve unit can be installed either internal or external to the

indoor coil. In applications where an uncased coil is being
installed in a field-provided plenum, install the expansion
valve in a manner that will provide access for field servicing
of the expansion valve. Refer to below illustration for
reference during installation of expansion valve unit.

A

Attach the vapor line sensing bulb in the proper
orientation as illustrated to the right using the clamp and
screws provided.

NOTE -

 Confirm proper thermal contact between vapor line

and expansion valve sensing bulb before insulating the
sensing bulb once installed.

B

Connect the equalizer line from the expansion valve to
the equalizer vapor port on the vapor line. Finger tighten
the flare nut plus 1/8 turn (7 ft-lbs) as illustrated below.

TWO PIECE

PATCH PLATE

(UNCASED

COIL ONLY)

VAPOR

LINE

LIQUID LINE

ORIFICE

HOUSING

DISTRIBUTOR

TUBES

LIQUID LINE

MALE EQUALIZER LINE

FITTING (SEE

EQUALIZER LINE

INSTALLATION FOR
FURTHER DETAILS)

SENSING

LINE

EQUALIZER
LINE

EXPANSION

VALVE

TEFLON

®

RING

(Uncased Coil Shown)

Sensing bulb insulation is required if
mounted external to the coil casing. sensing
bulb installation for bulb positioning.

STUB

END

TEFLON

®

RING

LIQUID LINE

ASSEMBLY WITH

BRASS NUT

DISTRIBUTOR

ASSEMBLY

C

Install one of the provided Teflon

®

 rings around the

stubbed end of the expansion valve and lightly lubricate
the connector threads and expose surface of the Teflon

®

ring with refrigerant oil.

D

Attach the stubbed end of the expansion valve to the
liquid line orifice housing. Finger tighten and use an
appropriately sized wrench to turn an additional 1/2 turn
clockwise as illustrated in the figure above, or tighten to
20 ft-lb.

E

Place the remaining Teflon

®

 washer around the other

end of the expansion valve. Lightly lubricate connector
threads and expose surface of the Teflon

®

 ring with

refrigerant oil.

F

Attach the liquid line assembly to the expansion valve.
Finger tighten and use an appropriately sized wrench to
turn an additional 1/2 turn clockwise as illustrated in the
figure above or tighten to 20 ft-lb.

ON 7/8” AND LARGER LINES,
MOUNT SENSING BULB AT
EITHER THE 4 OR 8 O'CLOCK
POSITION. NEVER MOUNT
THE SENSING BULB ON
BOTTOM OF LINE.

12

ON LINES SMALLER THAN
7/8”, MOUNT SENSING
BULB BETWEEN THE 9 AND
3 O'CLOCK POSITIONS.

12

BULB

VAPOR LINE

VAPOR LINE

NOTE - NEVER MOUNT THE SENSING BULB ON

BOTTOM OF LINE.

BULB

BULB

BULB

VAPOR LINE

FLARE NUT

COPPER FLARE
SEAL BONNET

MALE BRASS EQUALIZER
LINE FITTING

FLARE SEAL CAP

OR

1

2

3

4

5

6

7

8

9

10

11 12

1/2 Turn

SENSING BULB INSTALLATION

EQUALIZER LINE INSTALLATION

1

2

3

4

5

6

7

8

9

10

11 12

1/8 Turn

A

Remove and discard either the flare seal cap or flare nut
with copper flare seal bonnet from the equalizer line port
on the vapor line as illustrated in the figure to the right.

B

Remove the field-provided fitting that temporarily recon­
nected the liquid line to the indoor unit's distributor assem­
bly

INDOOR EXPANSION VALVE INSTALLATION

9 O'CLOCK TO

3 O'CLOCK

Figure 11. Installing Indoor Expansion Valve

Содержание SSB036H4S4

Страница 1: ...page 12 to avoid damaging the service valve s internal seals INSTALLATION INSTRUCTIONS S CLASS SSB H4 Units AIR CONDITIONER UNITS 507163 01 6 2013 Supersedes 506641 01 TABLE OF CONTENTS Shipping and...

Страница 2: ...45 1143 35 1 2 902 39 3 8 1001 16 7 8 429 8 3 4 222 3 1 8 79 30 3 4 781 4 5 8 117 3 3 4 95 26 7 8 683 Model Number Identification S S B Y 1 036 H 4 4 S Major Design Sequence A 1st Generation B 2nd Ge...

Страница 3: ...R DRIER SINGLE FLOW FIELD CONNECTION FOR LIQUID LINE SET LIQUID LINE SERVICE VALVE SUCTION LINE SERVICE VALVE FIELD CONNECTION FOR SUCTION LINE HIGH PRESSURE SWITCH MANUAL RESET S4 COMPRESSOR HARNESS...

Страница 4: ...nt loss during shipping and handling Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench or stripping the valve stem recess See the Lennox Service and Application N...

Страница 5: ...Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately sized wrench 2 Connect gaug...

Страница 6: ...ressure ratio meets a certain value or when the suction pressure is as high as 20 psig Compressor suction pressures should never be allowed to go into a vacuum Prolonged operation at low suction press...

Страница 7: ...tion to a window see the provided illustration in figure 5 detail A PLACING UNIT ON SLAB When installing unit at grade level the top of the slab should be high enough above grade so that water from hi...

Страница 8: ...of two 2 degrees or two inches per five feet 50 mm per 1 5 m away from building structure MOUNTING SLAB BUILDING STRUCTURE GROUND LEVEL Outside Unit Placement Slab Mounting at Ground Level SAME FASTEN...

Страница 9: ...VERED PANEL REMOVAL Remove the louvered panels as follows 1 Remove two screws allowing the panel to swing open slightly 2 Hold the panel firmly throughout this procedure Rotate bottom corner of panel...

Страница 10: ...erant line sizes as listed in table 2 NOTE When installing refrigerant lines longer than 50 feet see the Lennox Refrigerant Piping Design and Fabrication Guidelines CORP 9351 L9 or contact Lennox Tech...

Страница 11: ...OR RAFTER AT 8 FEET 2 43 METERS INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices sh...

Страница 12: ...Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns Wash hands with soap and water after handling brazing alloys and flux IMPORT...

Страница 13: ...AWAY FROM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve...

Страница 14: ...ICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a wet cloth around both liquid and suction l...

Страница 15: ...ion valve and the two Teflon rings H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD I...

Страница 16: ...one of the provided Teflon rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil D Attach the stub...

Страница 17: ...inder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the l...

Страница 18: ...and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F...

Страница 19: ...efer to the unit nameplate for minimum circuit ampacity and maximum fuse or circuit breaker HACR per NEC Install power wiring and properly sized disconnect switch NOTE Units are approved for use only...

Страница 20: ...Page 20 507163 01 05 13 Figure 14 Typical Wiring Diagram Y Voltage Figure 15 SSB H4 Typical Factory Diagram Y Voltage...

Страница 21: ...arge If the outdoor unit is void of refrigerant clean the system using the procedure described below 1 Leak check system using procedure outlined on page 17 2 Evacuate the system using procedure outli...

Страница 22: ...ition has been corrected 6 Set the thermostat for a cooling demand Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit 7 Recheck voltage while the un...

Страница 23: ...ir flow All temperatures are expressed in F Figure 19 Checking Indoor Airflow over Evaporator Coil using Delta T Chart WHEN TO CHARGE Warm weather best Can charge in colder weather CHARGE METHOD Deter...

Страница 24: ...t based upon line length SC Subcooling Values F 1 0 C 0 6 BLOCK OUTDOOR COIL sometimes necessary with lower temperatures Use cardboard or plastic sheet to restrict the airflow through the outdoor coil...

Страница 25: ...ions could mean that the system is not properly charged or that a problem exists with some component in the system Model SSB036H4S4 SSB048H4S4 SSB060H4S4 5F 5C Liquid Suction Liquid Suction Liquid Suc...

Страница 26: ...ry order another of like design and capacity The replacement filter drier must be suitable for use with HFC 410A refrigerant Maintenance DEALER Maintenance and service must be performed by a qualified...

Страница 27: ...r units are equipped with reusable foam filters Clean foam filters with a mild soap and water solution rinse thoroughly allow filter to dry completely before returning it to the unit or grille NOTE Th...

Страница 28: ...Liquid Higher Start Up and Performance Checklist Job Name Job no Date Job Location City State Installer City State Unit Model No Serial No Service Technician Nameplate Voltage Rated Load Ampacity Comp...

Отзывы: