WARNING

Electric Shock Hazard. Can cause injury
or death. Unit must be grounded in
accordance with national and local
codes.

Line voltage is present at all components
when unit is not in operation on units with
single‐pole contactors. Disconnect all
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.

CAUTION

Physical contact with metal edges and corners while
applying excessive force or rapid motion can result in
personal injury. Be aware of, and use caution when
working near these areas during installation or while
servicing this equipment.

Operating Gauge Set and Service Valves

These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
who have jurisdiction before installation.

TORQUE REQUIREMENTS

When servicing or repairing heating, ventilating, and air
conditioning components, ensure the fasteners are
appropriately tightened. Table 1 lists torque values for
fasteners.

IMPORTANT

Only use Allen wrenches of sufficient hardness (50Rc -
Rockwell Harness Scale minimum). Fully insert the
wrench into the valve stem recess.

Service valve stems are factory-torqued (from 9 ft-lbs for
small valves, to 25 ft-lbs for large valves) to prevent
refrigerant loss during shipping and handling. Using an
Allen wrench rated at less than 50Rc risks rounding or
breaking off the wrench, or stripping the valve stem
recess.

See the Lennox Service and Application Notes #C-08-1
for further details and information.

IMPORTANT

To prevent stripping of the various caps used, the
appropriately sized wrench should be used and fitted
snugly over the cap before tightening.

Table 1. Torque Requirements

Parts

Recommended Torque

Service valve cap

8 ft.- lb.

11 NM

Sheet metal screws

16 in.- lb.

2 NM

Machine screws #10

28 in.- lb.

3 NM

Compressor bolts

90 in.- lb.

10 NM

Gauge port seal cap

8 ft.- lb.

11 NM

USING MANIFOLD GAUGE SET

When checking the system charge, only use a manifold
gauge set that features low loss anti-blow back fittings.

Manifold gauge set used with HFC-410A refrigerant
systems must be capable of handling the higher system
operating pressures. The gauges should be rated for use
with pressures of 0 - 800 psig on the high side and a low
side of 30” vacuum to 250 psig with dampened speed to
500 psi. Gauge hoses must be rated for use at up to 800
psig of pressure with a 4000 psig burst rating.

OPERATING SERVICE VALVES

The liquid and vapor line service valves are used for
removing refrigerant, flushing, leak testing, evacuating,
checking charge and charging.

Each valve is equipped with a service port which has a
factory-installed valve stem. Figure 2 provides information
on how to access and operating both angle and ball service
valves.

Содержание SSB036H4S4

Страница 1: ...page 12 to avoid damaging the service valve s internal seals INSTALLATION INSTRUCTIONS S CLASS SSB H4 Units AIR CONDITIONER UNITS 507163 01 6 2013 Supersedes 506641 01 TABLE OF CONTENTS Shipping and...

Страница 2: ...45 1143 35 1 2 902 39 3 8 1001 16 7 8 429 8 3 4 222 3 1 8 79 30 3 4 781 4 5 8 117 3 3 4 95 26 7 8 683 Model Number Identification S S B Y 1 036 H 4 4 S Major Design Sequence A 1st Generation B 2nd Ge...

Страница 3: ...R DRIER SINGLE FLOW FIELD CONNECTION FOR LIQUID LINE SET LIQUID LINE SERVICE VALVE SUCTION LINE SERVICE VALVE FIELD CONNECTION FOR SUCTION LINE HIGH PRESSURE SWITCH MANUAL RESET S4 COMPRESSOR HARNESS...

Страница 4: ...nt loss during shipping and handling Using an Allen wrench rated at less than 50Rc risks rounding or breaking off the wrench or stripping the valve stem recess See the Lennox Service and Application N...

Страница 5: ...Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately sized wrench 2 Connect gaug...

Страница 6: ...ressure ratio meets a certain value or when the suction pressure is as high as 20 psig Compressor suction pressures should never be allowed to go into a vacuum Prolonged operation at low suction press...

Страница 7: ...tion to a window see the provided illustration in figure 5 detail A PLACING UNIT ON SLAB When installing unit at grade level the top of the slab should be high enough above grade so that water from hi...

Страница 8: ...of two 2 degrees or two inches per five feet 50 mm per 1 5 m away from building structure MOUNTING SLAB BUILDING STRUCTURE GROUND LEVEL Outside Unit Placement Slab Mounting at Ground Level SAME FASTEN...

Страница 9: ...VERED PANEL REMOVAL Remove the louvered panels as follows 1 Remove two screws allowing the panel to swing open slightly 2 Hold the panel firmly throughout this procedure Rotate bottom corner of panel...

Страница 10: ...erant line sizes as listed in table 2 NOTE When installing refrigerant lines longer than 50 feet see the Lennox Refrigerant Piping Design and Fabrication Guidelines CORP 9351 L9 or contact Lennox Tech...

Страница 11: ...OR RAFTER AT 8 FEET 2 43 METERS INTERVALS THEN STRAP THE LIQUID LINE TO THE VAPOR LINE FLOOR JOIST OR ROOF RAFTER REFRIGERANT LINE SET INSTALLING HORIZONTAL RUNS NOTE Similar installation practices sh...

Страница 12: ...Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns Wash hands with soap and water after handling brazing alloys and flux IMPORT...

Страница 13: ...AWAY FROM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve...

Страница 14: ...ICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE will result if you do not wrap a wet cloth around both liquid and suction l...

Страница 15: ...ion valve and the two Teflon rings H Use a field provided fitting to temporary reconnect the liquid line to the indoor unit s liquid line orifice housing LOW HIGH EXISTING INDOOR UNIT GAUGE MANIFOLD I...

Страница 16: ...one of the provided Teflon rings around the stubbed end of the expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant oil D Attach the stub...

Страница 17: ...inder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allow HFC 410A into the l...

Страница 18: ...and indoor unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F...

Страница 19: ...efer to the unit nameplate for minimum circuit ampacity and maximum fuse or circuit breaker HACR per NEC Install power wiring and properly sized disconnect switch NOTE Units are approved for use only...

Страница 20: ...Page 20 507163 01 05 13 Figure 14 Typical Wiring Diagram Y Voltage Figure 15 SSB H4 Typical Factory Diagram Y Voltage...

Страница 21: ...arge If the outdoor unit is void of refrigerant clean the system using the procedure described below 1 Leak check system using procedure outlined on page 17 2 Evacuate the system using procedure outli...

Страница 22: ...ition has been corrected 6 Set the thermostat for a cooling demand Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit 7 Recheck voltage while the un...

Страница 23: ...ir flow All temperatures are expressed in F Figure 19 Checking Indoor Airflow over Evaporator Coil using Delta T Chart WHEN TO CHARGE Warm weather best Can charge in colder weather CHARGE METHOD Deter...

Страница 24: ...t based upon line length SC Subcooling Values F 1 0 C 0 6 BLOCK OUTDOOR COIL sometimes necessary with lower temperatures Use cardboard or plastic sheet to restrict the airflow through the outdoor coil...

Страница 25: ...ions could mean that the system is not properly charged or that a problem exists with some component in the system Model SSB036H4S4 SSB048H4S4 SSB060H4S4 5F 5C Liquid Suction Liquid Suction Liquid Suc...

Страница 26: ...ry order another of like design and capacity The replacement filter drier must be suitable for use with HFC 410A refrigerant Maintenance DEALER Maintenance and service must be performed by a qualified...

Страница 27: ...r units are equipped with reusable foam filters Clean foam filters with a mild soap and water solution rinse thoroughly allow filter to dry completely before returning it to the unit or grille NOTE Th...

Страница 28: ...Liquid Higher Start Up and Performance Checklist Job Name Job no Date Job Location City State Installer City State Unit Model No Serial No Service Technician Nameplate Voltage Rated Load Ampacity Comp...

Отзывы: