background image

Page 5

Position and Install Panel

Position the panel almost par-

allel with the unit (figure 2, Detail D) with the screw side" as
close to the unit as possible. Then, in a continuous motion:
Slightly rotate and guide the lip of top tab inward (figure 2,

Details A and C); then upward into the top slot of the
hinge corner post.

Rotate panel to vertical to fully engage all tabs.
Holding the panel’s hinged side firmly in place, close the

right−hand side of the panel, aligning the screw holes.

When panel is correctly positioned and aligned, insert the
screws and tighten.

A − Control Box (Figure 3)

SSB*H4 units are not equipped with a 24V transformer. All
24 VAC controls are powered by the indoor unit. Refer to
wiring diagram.

Electrical openings are provided under the control box cov-
er. Field thermostat wiring is made to color-coded pigtail
connections.

ELECTROSTATIC DISCHARGE (ESD)

Precautions and Procedures

CAUTION

Electrostatic discharge can affect electronic com-
ponents. Take precautions during unit installation
and service to protect the unit’s electronic controls.
Precautions will help to avoid control exposure to
electrostatic discharge by putting the unit, the con-
trol and the technician at the same electrostatic po-
tential. Neutralize electrostatic charge by touching
hand and all tools on an unpainted unit surface be-
fore performing any service procedure.

FIGURE 3

DUAL CAPACITOR

(C12)

COMPRESSOR

CONTACTOR

(K1)

CONTROL BOX

GROUNDING

LUG

1 − Compressor Contactor K1

The compressor is energized by a single−pole contactor lo-
cated in the control box. See figure 3. K1 is energized by the
indoor thermostat terminal Y1 (24V) when thermostat de-
mand is present.

2 − Dual Capacitor C12

The compressor and fan in SSB*H4 series units use per-
manent split capacitor motors. The capacitor is located
inside the unit control box (see figure 3). A single dual"
capacitor (C12) is used for both the fan motor and the
compressor (see unit wiring diagram). The fan side and
the compressor side of the capacitor have different MFD
ratings. See side of capacitor for ratings.

CAUTION

In order to avoid injury, take precaution when
lifting heavy objects.

B − Two−Stage Scroll Compressor (B1)

FIGURE 1

TWO−STAGE MODULATED SCROLL

solenoid actuator coil

slider ring

The scroll compressor design is simple, efficient  and re-
quires few moving parts.  A cutaway diagram of the scroll
compressor is shown in figure 1.The scrolls are located in
the top of the compressor can and the motor is located just
below. The oil level is immediately below the motor.
The scroll is a simple compression concept centered around
the unique spiral shape of the scroll and its inherent proper-
ties. Figure 2 shows the basic scroll form. Two identical
scrolls are mated together forming concentric spiral shapes
(figure 3 ).  One scroll remains stationary, while the other is
allowed to orbit" (figure 4).  Note that the orbiting scroll does
not rotate or turn but merely orbits" the stationary scroll.

Содержание SSB*H4

Страница 1: ...e must be performed by a qualified installer or service agency WARNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect...

Страница 2: ...oor Fan Diameter in 22 22 26 Fan No of blades 4 4 3 Motor hp 1 6 1 4 1 3 Cfm 3060 3955 4380 Rpm 845 835 850 Watts 215 320 280 Shipping Data lbs 1 pkg 229 257 309 ELECTRICAL DATA Line voltage data 60hz...

Страница 3: ...Delay Relay 58M81 NOTE Extremes of operating range are plus 10 and minus 5 of line voltage 1 Refrigerant charge sufficient for 15 ft length of refrigerant lines 2 HACR type breaker or fuse 3 Refer to...

Страница 4: ...panels consider any weather conditions especially windy conditions that may cause panels to be blown around and battered Remove the louvered panels as follows 1 Remove 2 screws allowing the panel to s...

Страница 5: ...RE 3 DUAL CAPACITOR C12 COMPRESSOR CONTACTOR K1 CONTROL BOX GROUNDING LUG 1 Compressor Contactor K1 The compressor is energized by a single pole contactor lo cated in the control box See figure 3 K1 i...

Страница 6: ...ssor can be used to pump down refrigerant as long as the pressure is not reduced below 7 psig NOTE During operation the head of a scroll compressor may be hot since it is in constant contact with disc...

Страница 7: ...RBIT STATIONARY SCROLL ORBITING CRESCENT SHAPED GAS POCKET HIGH PRESSURE GAS DISCHARGE POCKET FLANKS SEALED BY CENTRIFUGAL FORCE 1 2 3 4 SUCTION INTERMEDIATE PRESSURE GAS SUCTION POCKET FIGURE 5 Bypas...

Страница 8: ...Procedure 1 Turn main power OFF to outdoor unit 2 Adjust room thermostat set point above heating opera tion on heat pump or below cooling operation the room temperature 5 F 3 Remove control access pa...

Страница 9: ...nector end of the full wave rectifier plug The DC voltage reading should be 1 5 to 3 volts lower than the input voltage to the plug wire leads EX Input volt age is 24VAC output voltage is 22VDC See fi...

Страница 10: ...h is closed during normal operating pressure conditions and is permanently adjusted to trip open at 40 5 psi The switch automatically resets when suction line pressure rises above 90 5 psi Under certa...

Страница 11: ...ure 3 years refrigerated 10N44 Moisture Test Tubes Checkmate RT751 Tubes three pack 6 12 months room temperature 2 years refrigerated 74N40 Easy Oil Test Tubes Checkmate RT752C Tubes three pack 2 3 ye...

Страница 12: ...th a hex head extension to back the stem out counterclockwise as far as it will go NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16 extension for large line sizes 3 Replace the stem cap...

Страница 13: ...of the manifold to allow the R 410A into the line set and indoor unit Weigh in a trace amount of R 410A A trace amount is a maximum of 2 ounces 57 g or 3 pounds 31 kPa pressure Close the valve on the...

Страница 14: ...en met disconnect the manifold hose from the vacu um pump and connect it to an upright cylinder of R 410A refrigerant Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive press...

Страница 15: ...al thermometer to record the liquid line temperature 6 The outdoor temperature will determine which charging method to use Proceed with the appropriate charging procedure Charge Using Weigh in Method...

Страница 16: ...ble 8 Normal Operating Pressures Pressures high er than those listed indicate that the system is over charged Pressures lower than those listed indicate that the system is undercharged A temperature p...

Страница 17: ...oil Drier must be replaced to eliminate mois ture from POE oil VI MAINTENANCE WARNING Electric shock hazard Can cause inju ry or death Before attempting to per form any service or maintenance turn the...

Страница 18: ...K1 compressor contactor passes through S87 low pressure switch and returns to common side of the 24VAC power 3 K1 closes energizing B1 compressor and B4 outdoor fan 4 Solenoid L34 is NOT energized so...

Страница 19: ...passes through S87 low pressure switch and returns to common side of the 24VAC power 3 K1 closes energizing B1 compressor and B4 outdoor fan 4 Solenoid L34 is NOT energized so the slider ring remains...

Отзывы: