background image

Page 12

III − REFRIGERANT SYSTEM

A − Plumbing

Field refrigerant piping consists of liquid and suction lines
from the condensing unit (sweat connections) to the indoor
evaporator coil (sweat connections). Use Lennox  L15
(sweat) series line sets as shown in table 3.

TABLE 3

 Unit

Liquid

Line

Suction

Line

L15 Line Sets

−036,

−048

3/8 in.

(10 mm)

7/8 in.

(22 mm)

L15−65

15 ft. − 50 ft.

(4.6 m − 15 m)

−060

3/8 in.

(10 mm)

1−1/8 in.

(29 mm)

Field

Fabricated

The liquid line and vapor line service valves (figures 6 and 7)
and gauge ports are accessible from the outside of the unit.
Use the service ports for leak testing, evacuating, charging
and checking charge.

Each valve is equipped with a service port which has a facto-
ry−installed Schrader valve. A service port cap protects the
Schrader valve from contamination and serves as the pri-
mary leak seal.

 Service valves are not rebuildable. If a valve

has failed, you must replace it.

To Access Schrader Port:

 1 − Remove service port cap with an adjustable wrench.
 2 − Connect gauge to the service port.
 3 − When testing is complete, replace service port cap. Tight-

en finger tight, then an additional 1/6 turn.

To Open Service Valve:

 1 − Remove the stem cap with an adjustable wrench.
 2 − Using the adjustable wrench to keep the valve station-

ary, use a service wrench with a hex−head extension to
back the stem out counterclockwise as far as it will go.

NOTE − Use a 3/16" hex head extension for 3/8" line
sizes or a 5/16" extension for large line sizes.

 3 − Replace the stem cap. Tighten finger tight, then tighten

an additional 1/6 turn.

To Close Service Valve:

 1 − Remove the stem cap with an adjustable wrench.
 2 − Using the adjustable wrench to keep the valve station-

ary, use a service wrench with a hex−head extension to
turn the stem clockwise to seat the valve. Tighten the
stem firmly.

NOTE − Use a 3/16" hex head extension for 3/8" line
sizes or a 5/16" extension for large line sizes.

 3 − Replace the stem cap. Tighten finger tight, then tighten an

additional 1/6 turn.

NOTE − Stem cap must be replaced to help prevent
valve leakage.

Service Valve

(Valve Closed)

Schrader valve open

to line set when valve is

closed (front seated)

service

port

service

port cap

stem cap

insert hex

wrench here

(valve front seated)

to outdoor coil

to indoor coil

Service Valve

(Valve Open)

Schrader

valve

service

port

service port

cap

insert hex

wrench here

to indoor coil

to outdoor coil

stem cap

FIGURE  6

Vapor Line Ball Valve – 5 Ton Units Only

Vapor line service valves function the same way as the other
valves, the difference is in the construction.  A ball valve is
illustrated in figure 7.
The ball valve is equipped with a service port with a factory−
installed Schrader valve. A service port cap protects the
Schrader valve from contamination and assures a leak−free
seal.

Содержание SSB*H4

Страница 1: ...e must be performed by a qualified installer or service agency WARNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect...

Страница 2: ...oor Fan Diameter in 22 22 26 Fan No of blades 4 4 3 Motor hp 1 6 1 4 1 3 Cfm 3060 3955 4380 Rpm 845 835 850 Watts 215 320 280 Shipping Data lbs 1 pkg 229 257 309 ELECTRICAL DATA Line voltage data 60hz...

Страница 3: ...Delay Relay 58M81 NOTE Extremes of operating range are plus 10 and minus 5 of line voltage 1 Refrigerant charge sufficient for 15 ft length of refrigerant lines 2 HACR type breaker or fuse 3 Refer to...

Страница 4: ...panels consider any weather conditions especially windy conditions that may cause panels to be blown around and battered Remove the louvered panels as follows 1 Remove 2 screws allowing the panel to s...

Страница 5: ...RE 3 DUAL CAPACITOR C12 COMPRESSOR CONTACTOR K1 CONTROL BOX GROUNDING LUG 1 Compressor Contactor K1 The compressor is energized by a single pole contactor lo cated in the control box See figure 3 K1 i...

Страница 6: ...ssor can be used to pump down refrigerant as long as the pressure is not reduced below 7 psig NOTE During operation the head of a scroll compressor may be hot since it is in constant contact with disc...

Страница 7: ...RBIT STATIONARY SCROLL ORBITING CRESCENT SHAPED GAS POCKET HIGH PRESSURE GAS DISCHARGE POCKET FLANKS SEALED BY CENTRIFUGAL FORCE 1 2 3 4 SUCTION INTERMEDIATE PRESSURE GAS SUCTION POCKET FIGURE 5 Bypas...

Страница 8: ...Procedure 1 Turn main power OFF to outdoor unit 2 Adjust room thermostat set point above heating opera tion on heat pump or below cooling operation the room temperature 5 F 3 Remove control access pa...

Страница 9: ...nector end of the full wave rectifier plug The DC voltage reading should be 1 5 to 3 volts lower than the input voltage to the plug wire leads EX Input volt age is 24VAC output voltage is 22VDC See fi...

Страница 10: ...h is closed during normal operating pressure conditions and is permanently adjusted to trip open at 40 5 psi The switch automatically resets when suction line pressure rises above 90 5 psi Under certa...

Страница 11: ...ure 3 years refrigerated 10N44 Moisture Test Tubes Checkmate RT751 Tubes three pack 6 12 months room temperature 2 years refrigerated 74N40 Easy Oil Test Tubes Checkmate RT752C Tubes three pack 2 3 ye...

Страница 12: ...th a hex head extension to back the stem out counterclockwise as far as it will go NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16 extension for large line sizes 3 Replace the stem cap...

Страница 13: ...of the manifold to allow the R 410A into the line set and indoor unit Weigh in a trace amount of R 410A A trace amount is a maximum of 2 ounces 57 g or 3 pounds 31 kPa pressure Close the valve on the...

Страница 14: ...en met disconnect the manifold hose from the vacu um pump and connect it to an upright cylinder of R 410A refrigerant Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive press...

Страница 15: ...al thermometer to record the liquid line temperature 6 The outdoor temperature will determine which charging method to use Proceed with the appropriate charging procedure Charge Using Weigh in Method...

Страница 16: ...ble 8 Normal Operating Pressures Pressures high er than those listed indicate that the system is over charged Pressures lower than those listed indicate that the system is undercharged A temperature p...

Страница 17: ...oil Drier must be replaced to eliminate mois ture from POE oil VI MAINTENANCE WARNING Electric shock hazard Can cause inju ry or death Before attempting to per form any service or maintenance turn the...

Страница 18: ...K1 compressor contactor passes through S87 low pressure switch and returns to common side of the 24VAC power 3 K1 closes energizing B1 compressor and B4 outdoor fan 4 Solenoid L34 is NOT energized so...

Страница 19: ...passes through S87 low pressure switch and returns to common side of the 24VAC power 3 K1 closes energizing B1 compressor and B4 outdoor fan 4 Solenoid L34 is NOT energized so the slider ring remains...

Отзывы: