background image

Page 14

 1 − Connect manifold gauge set to the service valve ports :

 

 

low pressure gauge to 

vapor 

line service valve

 

 

high pressure gauge to 

liquid 

line service valve

 2 − Connect micron gauge.

 3 − Connect the vacuum pump (with vacuum gauge) to the

center port of the manifold gauge set.

 4 − Open both manifold valves and start the vacuum

pump.

 5 − Evacuate the line set and indoor unit to an 

absolute

pressure

 of 23,000 microns (29.01 inches  of mercury).

During the early stages of evacuation, it is desirable to
close the manifold gauge valve at least once to deter-
mine if there is a rapid rise in 

absolute pressure

. A rap-

id rise in pressure indicates a relatively large leak. If this
occurs, repeat the leak testing procedure.

NOTE − The term 

absolute pressure

 means the total

actual pressure within a given volume or system, above
the absolute zero of pressure. Absolute pressure in a
vacuum is equal to atmospheric pressure minus vacu-
um pressure.

 6 − When the absolute pressure reaches 23,000 microns

(29.01 inches  of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cylin-
der with pressure regulator set to 150 psig (1034 kPa)
and purge the air from the hose with nitrogen. Open the
manifold gauge valves to break the vacuum in the line
set and indoor unit. Close the manifold gauge valves.

CAUTION

Danger of Equipment Damage.
Avoid deep vacuum operation. Do not use compres-
sors to evacuate a system.
Extremely low vacuums can cause internal arcing and
compressor failure.
Damage caused by deep vacuum operation will void
warranty.

 7 − Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold gauge
valves to release the nitrogen from the line set and in-
door unit.

 8 − Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line set
and indoor unit until the absolute pressure does not rise
above 500 microns (29.9 inches of mercury) within a
20−minute period after shutting off the vacuum pump
and closing the manifold gauge valves.

 9 − When  the  absolute  pressure  requirement  above  has

been met, disconnect the manifold hose from the vacu-
um pump and connect it to an upright cylinder of R−410A
refrigerant. Open the manifold gauge valves to break the

vacuum from 1 to 2 psig positive pressure in the line set
and indoor unit. Close manifold gauge valves and shut
off the R−410A cylinder and remove the manifold gauge
set.

C − Charging

NOTES −

R−410A refrigerant cylinders are rose−colored. Re-
frigerant should be added through the vapor valve
in the liquid state. 

Certain R−410A cylinders are identified as being
equipped with a dip tube. These allow liquid refrig-
erant to be drawn from the bottom of the cylinder
without inverting the cylinder. DO NOT turn this type
cylinder upside−down to draw refrigerant.

IMPORTANT

Use table NO TAG to perform maintenance checks.
Table NO TAG is not a procedure for charging the sys-
tem. Minor variations in these pressures may be due to
differences in installations. Significant deviations
could mean that the system is not properly charged or
that a problem exists with some component in the sys-
tem.

This system is charged with R−410A refrigerant which oper-
ates at much higher pressures than R−22. The installed liq-
uid line filter drier is approved for use with R−410A. Do not
replace it with components designed for use with R−22. This
unit is NOT approved for use with coils which use

 

capillary

tubes as a refrigerant metering device.

Factory Charge

Units are factory charged with the amount of R−410A refrig-
erant indicated on the unit rating plate. This charge is based
on a matching indoor coil and outdoor coil with 15 ft. (4.6 m)
line set. For varying lengths of line set, refer to table 4 for re-
frigerant charge adjustment.

TABLE 4

Refrigerant Charge per Line Set Lengths

Liquid Line
Set Diameter

Oz. per 5 ft. (g per 1.5 m) adjust
from 15 ft. (4.6 m) line set*

3/8 in. (9.5 mm)

3 ounce per 5 ft. (85 g per 1.5 m)

*If line length is greater than 15 ft. (4.6 m), add this amount.
If line length is less than 15 ft. (4.6 m), subtract this
amount.

IMPORTANT

Mineral oils are not compatible with R−410A. If oil
must be added, it must be a polyol ester oil.

The compressor is charged with sufficient polyol es-
ter oil for approved  line set lengths.

Units Delivered Void of Charge

If the system is void of refrigerant,

 clean the system using

the procedure described below.

1 − Use dry nitrogen to pressurize the system and check for

leaks. Repair leaks, if possible.

Содержание SSB*H4

Страница 1: ...e must be performed by a qualified installer or service agency WARNING Warranty will be voided if covered equipment is re moved from original installation site Warranty will not cover damage or defect...

Страница 2: ...oor Fan Diameter in 22 22 26 Fan No of blades 4 4 3 Motor hp 1 6 1 4 1 3 Cfm 3060 3955 4380 Rpm 845 835 850 Watts 215 320 280 Shipping Data lbs 1 pkg 229 257 309 ELECTRICAL DATA Line voltage data 60hz...

Страница 3: ...Delay Relay 58M81 NOTE Extremes of operating range are plus 10 and minus 5 of line voltage 1 Refrigerant charge sufficient for 15 ft length of refrigerant lines 2 HACR type breaker or fuse 3 Refer to...

Страница 4: ...panels consider any weather conditions especially windy conditions that may cause panels to be blown around and battered Remove the louvered panels as follows 1 Remove 2 screws allowing the panel to s...

Страница 5: ...RE 3 DUAL CAPACITOR C12 COMPRESSOR CONTACTOR K1 CONTROL BOX GROUNDING LUG 1 Compressor Contactor K1 The compressor is energized by a single pole contactor lo cated in the control box See figure 3 K1 i...

Страница 6: ...ssor can be used to pump down refrigerant as long as the pressure is not reduced below 7 psig NOTE During operation the head of a scroll compressor may be hot since it is in constant contact with disc...

Страница 7: ...RBIT STATIONARY SCROLL ORBITING CRESCENT SHAPED GAS POCKET HIGH PRESSURE GAS DISCHARGE POCKET FLANKS SEALED BY CENTRIFUGAL FORCE 1 2 3 4 SUCTION INTERMEDIATE PRESSURE GAS SUCTION POCKET FIGURE 5 Bypas...

Страница 8: ...Procedure 1 Turn main power OFF to outdoor unit 2 Adjust room thermostat set point above heating opera tion on heat pump or below cooling operation the room temperature 5 F 3 Remove control access pa...

Страница 9: ...nector end of the full wave rectifier plug The DC voltage reading should be 1 5 to 3 volts lower than the input voltage to the plug wire leads EX Input volt age is 24VAC output voltage is 22VDC See fi...

Страница 10: ...h is closed during normal operating pressure conditions and is permanently adjusted to trip open at 40 5 psi The switch automatically resets when suction line pressure rises above 90 5 psi Under certa...

Страница 11: ...ure 3 years refrigerated 10N44 Moisture Test Tubes Checkmate RT751 Tubes three pack 6 12 months room temperature 2 years refrigerated 74N40 Easy Oil Test Tubes Checkmate RT752C Tubes three pack 2 3 ye...

Страница 12: ...th a hex head extension to back the stem out counterclockwise as far as it will go NOTE Use a 3 16 hex head extension for 3 8 line sizes or a 5 16 extension for large line sizes 3 Replace the stem cap...

Страница 13: ...of the manifold to allow the R 410A into the line set and indoor unit Weigh in a trace amount of R 410A A trace amount is a maximum of 2 ounces 57 g or 3 pounds 31 kPa pressure Close the valve on the...

Страница 14: ...en met disconnect the manifold hose from the vacu um pump and connect it to an upright cylinder of R 410A refrigerant Open the manifold gauge valves to break the vacuum from 1 to 2 psig positive press...

Страница 15: ...al thermometer to record the liquid line temperature 6 The outdoor temperature will determine which charging method to use Proceed with the appropriate charging procedure Charge Using Weigh in Method...

Страница 16: ...ble 8 Normal Operating Pressures Pressures high er than those listed indicate that the system is over charged Pressures lower than those listed indicate that the system is undercharged A temperature p...

Страница 17: ...oil Drier must be replaced to eliminate mois ture from POE oil VI MAINTENANCE WARNING Electric shock hazard Can cause inju ry or death Before attempting to per form any service or maintenance turn the...

Страница 18: ...K1 compressor contactor passes through S87 low pressure switch and returns to common side of the 24VAC power 3 K1 closes energizing B1 compressor and B4 outdoor fan 4 Solenoid L34 is NOT energized so...

Страница 19: ...passes through S87 low pressure switch and returns to common side of the 24VAC power 3 K1 closes energizing B1 compressor and B4 outdoor fan 4 Solenoid L34 is NOT energized so the slider ring remains...

Отзывы: