Integrated Control Diagnostic Modes

Code

Diagnostic Codes/Status of Equipment

Action Required to Clear and Recover

E271

Soft lockout - Exceeded maximum number of re-

tries. Last retry failed due to the pressure switch 

opening.

Check pressure (inches w.c.) of low pressure switch clos-

ing on heat call. Measure operating pressure (inches w.c.). 

Inspect vent and combustion air inducer for correct oper-

ation  and  restriction.  Clears  when  heat  call  finishes  suc

-

cessfully.

E272

Soft lockout - Exceeded maximum number of re-

cycles. Last recycle due to the pressure switch 

opening.

Check operation of low pressure switch to see if it is stuck 

closed on heat call. Check pressure (inches w.c.) of high 

pressure switch closing on heat call. Measure operating 

pressure (inches w.c.). Inspect vent and combustion air 

inducer for correct operation and restriction. Clears when 

heat call finishes successfully.

E273

Soft lockout - Exceeded maximum number of re-

cycles. Last recycle due to flame failure.

Check micro-amperes of flame sensor using control diag

-

nostics  or  field-installed  mode.  Clean  or  replace  sensor. 

Measure voltage of neutral to ground to ensure good unit 

ground. Clears when heat call finishes successfully.

E274

Soft lockout - Exceeded maximum number of re-

cycles. Last recycle failed due to the limit circuit 

opening or limit remained open longer than 3 min-

utes

Shut down system. 1-hour soft lockout. Check firing rate 

and  air  flow.  Check  for  blockage.  Clears  when  heat  call 

finishes successfully.

E275

Soft lockout - Flame sensed out of sequence. 

Flame signal is gone.

Shut off gas. Check for gas valve leak. 1-hour soft lockout. 

Clears when flame has been proven stable.

E276

Watchguard calibration failure.

Unable to perform pressure switch calibration. Check vent 

system and pressure switch wiring connections. 1-hour soft 

lockout. Clears when calibration has finished successfully.

E290

Ignitor circuit fault - Failed ignitor or triggering cir-

cuitry.

Measure resistance of hot surface ignitor. Replace if open 

or  not  within  specifications.  1-hour  soft  lockout.  Clears 

when flame has been proven stable.

E291

Heat air flow restricted below the minimum.

Check for dirty filter and air flow restriction. Check blower 

performance. 1-hour soft lockout. Cleared when heat call 

finishes successfully.

E292

Indoor blower motor unable to start due to ob-

structed wheel, seized
bearings.

Indoor blower motor unable to start (seized bearing, stuck 

wheel, etc.). Replace motor or wheel if assembly does not 

operate or meet performance standards. 1-hour soft lock-

out. Clears after circulator successfully starts.

E294

Combustion air inducer over current.

Check combustion blower bearings, wiring and amps. Re-

place if does not operate or does not meet performance 

standards. Clears after inducer current is sensed to be in-

range after the ignition following the soft lockout or reset.

E295

Indoor blower motor temperature is too high.

Indoor blower motor over temperature (motor tripped on 

internal protector). Check motor bearings and amps. Re-

place if necessary. Cleared after blower demand is satis-

fied.

E310

Discharge error temperature sensor failure. Only 

shown if shorted or
out of range.

Compare outdoor sensor resistance to temperature/ re-

sistance charts in installation instructions. Replace sensor 

if necessary. Cleared in Communicating mode: 30 sec-

onds after fault recovered. In Non- Communicating mode: 

Cleared after the current heat call is completed.

E311

Heat rate reduced to match indoor blower air flow.

Warning Only. Furnace blower in cutback mode due to 

restricted airflow. Reduce firing rate every 60 seconds to 

match  available  CFM.  Check  filter  and  duct  system.  To 

clear, replace filter if needed or repair/ add duct. 2-stage 

controls  will  reduce  firing  rate  to  1st  stage.  Clears  when 

heat call finishes successfully.

Содержание SL280135V60D

Страница 1: ...ommunicating applications In non communicating applications the Lennox ComfortSense 7500 thermostat may be used as well as other non communicating thermostats In all cases setup is critical to ensure...

Страница 2: ...9 14 356 9 16 14 3 76 Right 7 178 Left 2 FLUE OUTLET Either Side 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Side 16 406 14 3 4 375 3 OPTIONAL EXTERNAL SIDE RETURN AIR FILTER KIT Either Side...

Страница 3: ...STION AIR INDUCER BLOWER ASSEMBLY BURNER BOX INNER BLOWER ACCESS PANEL ACCESS PANEL SIGHT GLASS COMBUSTION AIR INDUCER PRESSURE SWITCH GAS VALVE CONTROL BOX Includes two stage integrated control trans...

Страница 4: ...d protective clothing Certifications SL280UHV units are CSA International certified to ANSI Z21 47 In the USA installation of gas furnaces must conform with local building codes In the absence of loca...

Страница 5: ...ter during any phase of construc tion Very low return air temperatures harmful vapors and operation of the unit with clogged or misplaced filters will damage the unit SL280UHV units may be used for he...

Страница 6: ...information has been reprinted with permission from the National Fuel Gas Code ANSI Z223 1 This reprinted material is not the complete and official position of the ANSI on the referenced subject whic...

Страница 7: ...FIGURE 3 Air from Inside If the confined space that houses the furnace adjoins a space categorized as unconfined air can be brought in by providing two permanent openings between the two spac es Each...

Страница 8: ...the total input rating of all equipment in the enclosure If the equipment room is located against an outside wall and the air openings ing shall have a free area of at least one square inch 645 mm2 pe...

Страница 9: ...The bolt and washer must be removed before the furnace is placed into opera tion After the bolt and washer have been removed the rigid leg will not touch the blower housing RIGID LEG remove shipping b...

Страница 10: ...OW Single Side Return Air with transition and filter FIGURE 9 FIGURE 10 Optional Return Air Base Upflow Applications Only For use with A B C and D cabinets NOTE Optional Side Return Air Filter Kits ar...

Страница 11: ...ce Either suspend the furnace from roof rafters or floor joists as shown in figure 13 or install the furnace on a platform as shown in figure 14 Typical Horizontal Application Unit Suspended in Attic...

Страница 12: ...more frequently during the winter and the indoor coil to freeze in the summer resulting in an increase in the number of service calls Before using any filter with this system check the specifications...

Страница 13: ...it is installed the flue transition must be in the 9 o clock 12 o clock or 3 o clock position If necessary reposition the combustion air inducer pres sure switch and or make up box as needed per the f...

Страница 14: ...re switch HORIZONTAL LEFT POSITION Side Vent Discharge Disconnect pressure switch hose from barbed fitting on the pressure switch assembly Remove pressure switch assembly 1 screw and cut wire tie to f...

Страница 15: ...The exhaust vent for this furnace must be securely connected to the furnace flue transition at all times FLUE TRANSITION COLLAR VENT CONNECTION VENT PIPE min 6 length DISCONNECTED VENT WARNING STICKE...

Страница 16: ...s been sized according to the provided venting tables and the vent pipe manufacturer s instructions A fan assisted furnace may be commonly vented into an existing lined masonry chimney if the followin...

Страница 17: ...xceed 7 times the smallest listed appliance categorized vent area drafthood outlet area or flue collar area unless designed according to approved engineering methods 6 The entire length of single wall...

Страница 18: ...he provided venting tables If the existing venting system does not meet these requirements it must be resized TABLE 3 Capacity of Type B Double Wall Vents with Type B Double Wall Connectors Serving a...

Страница 19: ...51 128 66 195 3 24 47 37 87 53 139 67 210 10 1 22 43 34 78 49 123 65 189 2 23 47 36 86 51 136 67 206 3 24 50 37 92 52 146 69 220 15 1 21 50 33 89 47 142 64 220 2 22 53 35 96 49 153 66 235 3 24 55 36 1...

Страница 20: ...es which could cause an unsafe condition 3 Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and...

Страница 21: ...require the installation of a manual main shut off valve and union furnished by the installer external to the unit The union must be of the ground joint type IMPORTANT Compounds used on threaded join...

Страница 22: ...en testing pressure of gas lines gas valve must be disconnected and isolated See figure 28 Gas valves can be damaged if subjected to pressures greater than 1 2 psig 3 48 kPa 14 inches w c MANUAL MAIN...

Страница 23: ...mage Size wiring and circuit breaker s per Product Specifications bulletin EHB and unit rating plate NOTE Unit nameplate states maximum current draw Maximum over current protection allowed is shown in...

Страница 24: ...on the C terminal of the icomfort communication terminal strip RSBus Using an additiona wire come off C terminal and wire nut all the extra wires together Termination on the outdoor control must match...

Страница 25: ...PTIONAL DISCHARGE AIR SENSOR CLIP ON BOARD LINK W915 Y1 TO Y2 FOR TWO STAGE OPERATION iComfort THERMOSTAT Communicating systems using the iComfort thermostat require four thermostat wires between the...

Страница 26: ...wire is 18 RSBus Rf W Gh Gs Cf HVAC EQUIP DEHUMIDIFIER CONTROL HVAC EQUIPMENT DH STANDARD 1 OR 2 STAGE AC OR HP UNIT 24V IN JUMPER iComfort ENABLED FURNACE iComfort ENABLED FURNACE iComfort THERMOSTA...

Страница 27: ...N DO NOT CUT ANY ON BOARD LINKS S1 T STAT FURNACE TERM STRIP OUTDOOR UNIT 1 Heat 2 Cool NOTE Use DIP switch 2 to set second stage heat ON delay OFF 7 minutes ON 12 minutes ON CUT ON BOARD LINK W915 2...

Страница 28: ...915 2 STAGE COMPR S1 T STAT FURNACE TERM STRIP OUTDOOR UNIT 2 Heat 2 Cool with t stat with humidity control OFF CUT ON BOARD LINK W915 2 STAGE COMPR CUT ON BOARD LINK W914 DEHUM OR HARMONY S1 T STAT F...

Страница 29: ...T ON BOARD LINK W951 HEAT PUMP T STAT FURNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump ComfortSense thermostat w bilities Capable of 2 stage gas he...

Страница 30: ...BOARD LINK W914 DEHUM OR HARMONY T STAT FURNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump ComfortSense thermostat w bilities Capable of 2 stage gas...

Страница 31: ...Page 31 FIGURE 32 SL280UHV Schematic Wiring Diagram...

Страница 32: ...HEAT DEMAND FROM 1ST STAGE T STAT R CLASS 2 VOLTAGE TO THERMOSTAT G MANUAL FAN FROM T STAT C THERMOSTAT SIGNAL GROUND CONNECTED TO TRANSFORMER GRD TR CHASIS GROUND GRD Y1 THERMOSTAT 1ST STAGE COOL SI...

Страница 33: ...lay time that the blower operates after the heating de mand has been satisfied can be adjusted by moving switches 3 and 4 on the integrated control The unit is shipped from the factory with a blower o...

Страница 34: ...at 100 until demand is satisfied Once demand is met motor ramps down to stop OFF OFF 100 CFM COMPRESSOR DEMAND Switches 11 12 and 13 Heating Mode Blower Speed The switches are factory set to the OFF...

Страница 35: ...board link W915 is a clippable connection between terminals Y1 and Y2 on the integrated control W915 must be cut if two stage cooling will be used If the Y1 to Y2 link is not cut the outdoor unit wil...

Страница 36: ...Heating Speed cfm Second Stage Heating Speed cfm 24 1300 1420 18 1250 1335 12 1185 1285 6 1145 1240 Factory Default 1070 1170 6 1015 1100 12 970 1035 18 880 980 COOLING 1 Cooling Speed DIP Switch Set...

Страница 37: ...DIP Switch Settings First Stage Heating Speed cfm Second Stage Heating Speed cfm 24 1420 1565 18 1355 1490 12 1285 1415 6 1215 1335 Factory Default 1145 1260 6 1080 1185 12 1010 1110 18 940 1035 COOL...

Страница 38: ...Pressure Range HEATING 1 Heating Speed DIP Switch Settings First Stage Heating Speed cfm Second Stage Heating Speed cfm 24 1875 2065 18 1785 1965 12 1695 1865 6 1605 1765 Factory Default 1515 1665 6...

Страница 39: ...PRECISION MODE operates independent of a Y1 demand Normal Operation 1 On On On Acceptable 24 VAC High 100 Dehumidification mode begins when humidity is greater than set point Dehumidification Call 2 O...

Страница 40: ...oom space to maintain a cooler room thermostat setpoint ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE COOLING BASIC MODE only active on a Y1 thermostat demand Normal Operation 1 On On On On Accepta...

Страница 41: ...rners will automatically light The ignitor does not get hot when there is no call for heat on units with an automat ic ignition system WARNING If you do not follow these instructions exactly a fire or...

Страница 42: ...al 2 cu ft Dial 045 80 160 200 400 070 55 110 136 272 090 41 82 102 204 110 33 66 82 164 135 27 54 68 136 Supply Line Pressure White Rodgers Gas Valve An inlet post located on the gas valve provides a...

Страница 43: ...3 034 032 4 9 10 0 4 9 10 0 4 9 10 0 11 0 1 This is the only permissible derate for these units 2 Natural gas high altitude orifice kit required 3 A natural to L P propane gas changeover kit is necess...

Страница 44: ...trol The integrated control runs a self diagnostic program and checks high temperature limit switches for normally closed contacts and pressure switches for normally open contacts The combustion air i...

Страница 45: ...nitiates a second stage on delay factory set at 7 minutes adjustable to 12 minutes 5 If the heating demand continues beyond the secondstage on delay the integrated control energizes the combustion air...

Страница 46: ...h air grilles and louvers on the unit and in the room where the furnace is installed must be properly sized open and unobstructed to provide combustion air 10 Inspect the furnace venting system to mak...

Страница 47: ...he burner manifold assembly to the vestibule panel and remove theassembly from the unit 4 To clean burners run a vacuum cleaner with a soft brush attachment over the face of burners Visually inspect i...

Страница 48: ...rts Upper access panel Blower panel Top cap Control Panel Parts Transformer Two stage variable speed integrated control Door interlock switch Circuit breaker Blower Parts Blower wheel Blower housing M...

Страница 49: ...ss the flame signal mode The integrated control will display the flame current on 7 segment LED in in micro amps uA Flame signal mode is exited after any of the following Power is reset Pressing and h...

Страница 50: ...clears 5 seconds after fault recovered E111 Low line voltage Reverse line power voltage wiring System resumes normal operation 5 seconds after fault recovered E112 Ground not detected System shuts dow...

Страница 51: ...riate feature will be set as installed and that could be seen in About screen In normal operation after control recognizes sensors alarm will be sent if valid temperature reading is lost To get rid of...

Страница 52: ...ect operation and restriction Resumes normal operation after fault is cleared E227 Low pressure switch open during trial for ignition or run mode Check pressure inches w c of low pressure switch closi...

Страница 53: ...ctions 1 hour soft lockout Clears when calibration has finished successfully E290 Ignitor circuit fault Failed ignitor or triggering cir cuitry Measure resistance of hot surface ignitor Replace if ope...

Страница 54: ...tween R O on integrated control with non communicating outdoor unit Dual fuel module required for heat pump application Configuration link R to O needs to be restored Replace link or hard wire Applica...

Страница 55: ...button next to 7 segment LED display until solid P symbol appears Release button Turn room thermostat to OFF Solid P starts blinking on 7 Segment LED Push and hold button Integrated control will disp...

Страница 56: ...OFF NO INDUCER OFF AFTER POST PURGE HARD LOCKOUT ERROR CODE FLASHES YES YES YES 1 2 1 LOW PRESSURE SWITCH OPENS 1 2 HARD LOCKOUT REQUIRES THERMOSTAT RESET OR CYCLING OF POWER TO RESET THE LOCKOUT 3 IN...

Страница 57: ...ZED ONLY FOR 1ST REQUEST FOR 2ND STAGE HEAT YES CALL FOR HEAT SATISFIED INDUCER SWITCHED TO HIGH SPEED SINGLE STAGE THERMOSTAT 2 STAGE THERMOSTAT NO INDUCER SWITCHED TO LOW SPEED 5 MINUTE DELAY ERROR...

Страница 58: ...2ND STAGE CALL FOR HEAT SATISFIED NO YES DE ENERGIZE 2ND STAGE GAS VALVE INDUCER SPEED SWITCHED TO LOW SPEED 1 2 3 1ST STAGE HEAT 1ST STAGE CALL FOR HEAT SATISFIED NO YES GAS VALVE DE ENERGIZED INDUC...

Страница 59: ...RAMPING PROFILES THE SPECIFIC PROFILE IS SELECTED USING THE 1 1 2 2 1 1 1 2 2 DE ENERGIZE 1ST STAGE COOLING CONTACTOR COMPRESSOR FAN 2ND STAGE COOLING REQUEST STILL ACTIVE COOLING REQUEST STILL ACTIV...

Страница 60: ...ST FOR HEAT RECEIVED REQUEST FOR COOLING RECEIVED GO TO CALL FOR 1ST STAGE HEAT YES GO TO CALL FOR COOLING 1 1 1 4 YES NO CALL FOR FAN INDOOR BLOWER ON CONTINUOUS FAN SPEED MAINTAIN INDOOR BLOWER AT C...

Отзывы: