Page 25
FIGURE 30
iComfort
®
Thermostat with a
Non-Communicating Outdoor Unit
iComfort
®
ENABLED
FURNACE
iComfort
®
ENABLED
THERMOSTAT
NON-COMMUNICATING
OUTDOOR AIR
CONDITIONING UNIT -
1 OR 2 STAGE
iComforti
®
Thermostat
iComfort
®
-Enabled Indoor Furnace
Non-Communicating Outdoor Air Conditioner
OPTIONAL
OUTDOOR
AIR SENSOR
OPTIONAL
DISCHARGE
AIR SENSOR
iComforti
®
Thermostat with an iComfort
®
ENABLED Outdoor Unit
icomfort
®
Thermostat
iComfort
®
Enabled Indoor Furnace
iComfort
®
Enabled Outdoor Air Conditioner or Heat Pump
iComfort
®
ENABLED
FURNACE
iComfort
®
- ENABLED
OUTDOOR AIR CONDITIONING
OR HEAT PUMP UNIT
OPTIONAL
OUTDOOR
AIR SENSOR
OPTIONAL
DISCHARGE
AIR SENSOR
CLIP ON-BOARD LINK
W915 (Y1 TO Y2) FOR
TWO-STAGE OPERATION
iComfort
®
THERMOSTAT
Communicating systems using the iComfort
®
thermostat require four thermostat wires
between the thermostat and the furnace/air handler control and four wires between the
outdoor unit and the furnace/air handler control. When a thermostat cable with more
than four wires is used, the extra wires must be properly connected to avoid electrical
noise. The wires must not be left disconnected.
Use wire nuts to bundle the four unused wires at each end of the cable. A single wire
should then be connected to the indoor unit end of the wire bundle and attached to the
“C” terminals as shown below.
Indoor Unit Controller
Outdoor Unit
iComfort
®
thermostat
Single wire
to terminal C
Single wire
to terminal C
Unused wires
Unused wires