Venting Options

The SLP99DF is shipped with vent exhaust / air intake 

connection at the top cap. See FIGURE 15. Using parts 

provided, the furnace may be field modified to have these 

connections on the right side of the furnace cabinet. See 

FIGURE 17 and follow the steps below. For left side vent-

ing order kit 87W73.

1 -  Remove inner blower door.
2 - 

 Loosen hose clamps which attach rubber fittings to 

the white PVC pipes inside the vestibule area. See 

FIGURE 15.

3 -   Loosen the clamp which secures the pipes at the 

blower deck. See FIGURE 15.

4 -   Remove white PVC pipes, slide up and out thru the 

top cap.

5 -   Remove the remaining parts of the pipe clamp at 

the blower deck.

6 - 

 Remove  the  black  plastic  fitting  in  top  cap  which 

previously aligned the PVC pipes.

7 -   Remove the sheet metal patch plate on the side 

of the cabinet which covers the openings for side 

venting option. Save screws for reuse.

8 -   Re-use the patch plate to cover the hole in the top 

cap. See FIGURE 16. Remove the 2 screws which 

secure the top cap to the furnace on the right side 

and re-install securing the right edge of the patch 

plate and the right side of the top cap to the furnace. 

Use 2 self-drilling sheet metal screws (provided) to 

finish securing the left edge of the patch plate on 

the left side.

9 -   Use a utility knife to cut out the cabinet insulation for 

the right side vent / air intake.

10 -  Install the two 90° street elbows (provided) through 

the side of the cabinet. The male side of each 

elbow should extend down through the blower deck 

and connect to the rubber fittings below. Once the 

elbows are properly positioned, tighten each clamp.

11 -  Peel protective backing from side vent sealing 

gaskets (2) and apply to side vent sealing plates (2) 

as shown in FIGURE 17.

12 -  Install the side vent sealing plates and gaskets 

on  the  exterior  of  the  cabinet  as  shown  in  figure 

15. Secure with six mounting screws (four reused 

and two provided from bag assembly). Holes are 

pre-punched in the parts and cabinet, no drilling is 

required.

13 -  Install sheet metal screws (provided) to seal extra 

two holes in cabinet not used with side vent clamps.

 IMPORTANT

Side vent sealing plates and side vent sealing gaskets 

must be used when converting to right side venting. 

Failure to use gaskets and plates may lead to improper 

operation of unit.

Top Vent Configuration

Exhaust/Air

Intake Connections

Pipe Clamp

Hose Clamp

FIGURE 15

 

Sheet Metal

Patch Plate

Patch Plate Top Cap

FIGURE 16

 

Содержание SIGNATURE SLP99DF070V36

Страница 1: ...cations the Lennox ComfortSense 7500 thermostat may be used as well as other non communicating thermostats In all cases setup is critical to ensure proper system operation Field wiring for both commun...

Страница 2: ...ly Air Supply Air 9 16 14 9 16 14 9 16 14 9 16 14 19 7 16 494 3 4 19 CONDENSATE TRAP CONNECTION 5 127 6 7 16 163 Either Side 9 229 Either Side 2 1 4 57 Either Side 1 1 2 38 Front Panel Flue Condensate...

Страница 3: ...PANEL COMBUSTION AIR INDUCER BLOWER ACCESS PANEL BLOWER ASSEMBLY Variable Speed Blower Motor Is Hidden BAG ASSEMBLY CONTROL BOX includes variable capacity integrated control transformer circuit breake...

Страница 4: ...ipment and wear gloves and protective clothing Use only the type of gas approved for use with this fur nace Refer to unit nameplate Building Codes In the USA installation of gas furnaces must conform...

Страница 5: ...signed for installation in mobile homes recreational vehicles or outdoors Never use an open flame to test for gas leaks Check all connections using a commercially available soap solution made specific...

Страница 6: ...in an unconditioned space consider provisions required to prevent freezing of condensate drain system Installation Setting Equipment WARNING Do not install the furnace on its front back or in the hor...

Страница 7: ...system The base must provide a stable support and an airtight seal to the furnace Allow absolutely no sagging cracks gaps etc For no reason should return and supply air duct systems ever be connected...

Страница 8: ...1 2 11M60 22 559 18 3 4 476 C Cabinet 21 11M61 22 559 22 3 4 578 FURNACE SUPPLY AIR PLENUM COMBUSTIBLE FLOORING BASE PROPERLY SIZED FLOOR OPENING FIGURE 9 2 After opening is cut set combustible floori...

Страница 9: ...Specifications bulletin Additional information is provided in Service and Application Note ACC002 August 2000 TABLE 3 Furnace Cabinet Width Fillter Size B Cabinet 17 1 2 16 X 25 X 1 1 C Cabinet 21 1 2...

Страница 10: ...ion Downflow SLP99DF Model a b 1 Mounting Surface 070XV36B 6 Center Plenum Duct 090XV36C 090XV48C 090XV60C 110XV60C Discharge Air Sensor Location and Wiring Downflow AIR FLOW DISCHARGE AIR SENSOR TERM...

Страница 11: ...and intake connections are made of PVC Use PVC primer and solvent cement when using PVC vent pipe When using ABS vent pipe use transitional solvent cement to make connections to the PVC fittings in t...

Страница 12: ...rnal to the structure Any vent pipe or elbows external to the structure must be included in total vent length calculations See vent length tables Kits must be properly installed according to kit instr...

Страница 13: ...side of the top cap to the furnace Use 2 self drilling sheet metal screws provided to finish securing the left edge of the patch plate on the left side 9 Use a utility knife to cut out the cabinet ins...

Страница 14: ...eral coat of PVC primer for PVC or use a clean dry cloth for ABS to clean inside socket surface of fitting and male end of pipe to depth of fitting socket 6 Promptly apply solvent cement to end of pip...

Страница 15: ...azard Cutting or altering exhaust or air intake pipes which are located in the blower compartment could result in Carbon Monoxide Poisoning or Death CAUTION Do not discharge exhaust into an existing s...

Страница 16: ...ing of vent systems which include multiple pipe sizes NOTE If right side venting option is used you must in clude the elbow at the furnace in the elbow count If tran sitioning to 3 dia pipe this elbow...

Страница 17: ...9 51 29 100 53 122 103 78 10 46 24 95 48 117 98 73 Standard Termination at Elevation 4501 7500 Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Model Model Model Model 070 090 110 070 090...

Страница 18: ...2 85 44 101 94 69 Concentric Termination at Elevation 4501 7500 Number of 90 Elbows Used 1 1 2 Pipe 2 Pipe 2 1 2 Pipe 3 Pipe Model Model Model Model 070 090 110 070 090 110 070 090 110 070 090 110 1 N...

Страница 19: ...upling The provided flue coupling must be attached to the exhaust coupling on the furnace top panel Use provided bands See steps below and FIGURE 22 1 Remove the caution tag from the flue coupling 2 F...

Страница 20: ...must be the same diameter Pipe Length 4 Maximum Not Furnished 2 2 Plate Furnished Street Ell Not Furnished FIGURE 23 TRANSITION 2 3 TOP VIEW 2 When transitioning up in pipe size use the shortest leng...

Страница 21: ...e under veranda porch deck or balcony 12 7 feet 2 1m 3 feet 9m within a height 15 feet 4 5m above the meter regulator assembly 3 feet 9m 6 inches 152mm for appliances 10 000 pliances 10 000 Btuh 3kw a...

Страница 22: ...the average snow accu mulation At vent termination care must be taken to maintain protec tive coatings over building materials prolonged exposure to exhaust condensate can destroy protective coatings...

Страница 23: ...o 99 Minimum Design Temperature table provided in the current edition of the ASHRAE Fundamentals Handbook 2 Poly Propylene vent pipe PP by Duravent and Centrotherm 3Vent lengths in table are equivalen...

Страница 24: ...separation requirement of intake and exhaust pipe DOES NOT apply 3 On roof terminations the intake piping should terminate straight down using two 90 elbows See FIGURE 28 4 Exhaust piping must termina...

Страница 25: ...RMINATION 71M80 69M29 or 60L46 US 44W92 or 44W93 Canada INTAKE AIR EXHAUST AIR INTAKE AIR INTAKE AIR EXHAUST AIR OUTSIDE WALL GRADE CLAMP Not Furnished FIELD PROVIDED REDUCER MAY BE REQUIRED TO ADAPT...

Страница 26: ...7 mm Min 12 305 mm Min 16 405 mm Max 6 152 mm Max 6 152 mm Min 24 610 mm Max 9 227 mm Min 12 305 mm Min 20 508 mm Max 6 152 mm Max Intake Elbow WALL SUPPORT B A D E B D E A ALTERNATE TERMINATIONS TEE...

Страница 27: ...Install the cap over the clean out opening at the base of the trap Secure with clamp See FIGURE 43 3 Install drain trap using appropriate PVC fittings glue all joints Glue the provided drain trap as s...

Страница 28: ...or Coil Using a Separate Drain Drain Field Provided Vent 1 min 2 max above condensate drain Condensate Drain Connection Evaporator Drain Line vent required FIGURE 40 IMPORTANT When combining the furna...

Страница 29: ...rain Connection In Unit Condensate Drain Connection In Unit Vent To Drain Condensate Drain Connection In Unit Optional Condensate Drain Connection OptionalDrainPipingFromTrap DrainTrapAssembly Furnish...

Страница 30: ...tate test gauge connection See FIGURE 51 6 In some localities codes may require installation of a manual main shut off valve and union furnished by installer external to the unit Union must be of the...

Страница 31: ...930 360 10 19 247 7 000 199 5 63 170 4 81 151 4 23 137 3 87 126 3 56 117 3 31 110 3 11 104 2 94 1 25 4 1 049 26 645 678 19 19 466 13 19 374 10 59 320 9 06 284 8 04 257 7 27 237 6 71 220 6 23 207 5 86...

Страница 32: ...or other deficiencies which could cause an unsafe condition 3 Close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting sy...

Страница 33: ...hermostat wiring in communicating applications TABLE 15 shows DIP switch and on board link settings for non communicating thermostat applica tions 1 The power supply wiring must meet Class I restricti...

Страница 34: ...9DFV is designed to operate in a variable rate capacity mode using a two stage thermostat The SLP99DFV will automatically adjust firing rate based upon thermostat cycle times A communicating thermosta...

Страница 35: ...icating Thermostat Single wire to terminal C Single wire to terminal C Unused wires Unused wires Communicating systems using the a communicating thermostat require four thermostat wires between the th...

Страница 36: ...S BUILT INTO ALL COMMUNICATING OUTDOOR UNITS COMMUNICATING ENABLED FURNACE HEPA BYPASS FILTER X2680 HEPA INTERLOCK KIT PASS INDOOR BLOWER MOTOR COMMON WIRE THROUGH CURRENT LOOP SEE HEPA INTERLOCK KIT...

Страница 37: ...set second stage heat ON delay OFF 7 minutes ON 12 minutes ON Intact Intact Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 1 Heat 2 Cool NOTE Use DIP switch 3 to set second stage heat ON delay OFF 7...

Страница 38: ...itch 1 W915 Y1 to Y2 Two Stage Cooling W914 DS to R cation or Harmony III W951 O to R Heat Pumps 2 Heat 2 Cool OFF Cut Intact Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 2 Heat 2 Cool with t stat...

Страница 39: ...2 stage gas heat control DIP Switch 1 OFF Intact Intact Cut L7742U T STAT CONTROL TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump ComfortSense 7000 L7742U...

Страница 40: ...Page 40 FIGURE 49...

Страница 41: ...IDIFICATION SIGNAL W2 HEAT DEMAND FROM 2ND STAGE T STAT W1 HEAT DEMAND FROM 1ST STAGE T STAT R CLASS 2 VOLTAGE TO THERMOSTAT G MANUAL FAN FROM T STAT C THERMOSTAT SIGNAL GROUND CONNECTED TO TRANSFORME...

Страница 42: ...rate of the unit is varied to maximize comfort Conventional two stage mode is the factory default set ting See TABLE 16 Switch 3 Second Stage Heat On Delay If a single stage thermostat is used the in...

Страница 43: ...ing Blower speed ramping may be used to enhance dehumidification performance The switches are factory set at option A which has the greatest effect on blower motor performance TABLE 21 provides the co...

Страница 44: ...e in second stage cooling only Diagnostic LED FIGURE 50 The seven segment diagnostic LED displays operating status target airflow error codes and other information See Integrated Control Diagnostic Co...

Страница 45: ...fault Heat CFM 629 669 749 829 910 990 1070 1150 Decrease 7 5 Heat CFM 559 599 681 763 845 927 1009 1091 Decrease 15 Heat CFM 488 530 614 697 781 865 948 1032 COOLING BLOWER PERFORMANCE 0 through 1 0...

Страница 46: ...ult Heat CFM 553 618 748 878 1009 1139 1269 1399 Decrease 7 5 Heat CFM 510 570 690 811 931 1051 1171 1292 Decrease 15 Heat CFM 467 522 632 743 853 963 1074 1184 COOLING BLOWER PERFORMANCE 0 through 1...

Страница 47: ...470 1655 1845 The effect of static pressure is included in air volumes shown The following control configurations are available See Installation Instructions for details and DIP switch settings Heat M...

Страница 48: ...on a call for de humidification Dehumidification call 2 On On On Demand 0 VAC High 70 PRECISION MODE operates independent of a Y1 demand Normal Operation 1 On On On Acceptable 24 VAC High 100 Dehumidi...

Страница 49: ...High 70 Thermostat will keep outdoor unit energized after cooling temperature setpoint has been reached in order to maintain room humidity setpoint ROOM THERMOSTAT CALLS FOR FIRST AND SECOND STAGE CO...

Страница 50: ...to stop At this point the trap should be primed with sufficient water to ensure proper condensate drain operation BEFORE BEFORE PLACING THE UNIT INTO OPERA TION smell all around the furnace area for g...

Страница 51: ...level Units installed at altitude of 7 501 to 10 000 feet 2287 to 3048m require a pressure switch change and conversion kit See TABLE 31 The combustion air pressure switch is factory set and re quires...

Страница 52: ...tude Pressure Switch 0 10 000 ft 0 3048m 0 7500 ft 0 2286m 7501 ft 10 000 ft 287 3048m 070 65W77 Not Required 14T67 090 110 Operating Pressure Signal Delta P Measurement FIGURE 53 Operating pressure s...

Страница 53: ...Installed Gas Valve MANIFOLD PRESSURE MEASUREMENT FIGURE 52 Negative Port Positive Port Gas Valve Measuring Device Field Installed Operating Signal Delta P Measurement Black Tubing Red and Black Tubi...

Страница 54: ...r the correct voltage at the furnace furnace operating Correct voltage is 120VAC 10 3 Check amp draw on the blower motor with innerlower panel in place Motor Nameplate__________Actual__________ Electr...

Страница 55: ...20 second warm up period has ended the gas valve is energized and ignition occurs At the same time the control module begins an indoor blower 45 second ON delay When the delay ends the indoor blower m...

Страница 56: ...ance At the beginning of each heating season and to compl ith the Lennox Limited Warranty your system should be checked as follows 1 Check wiring for loose connections voltage at indoor unit and amper...

Страница 57: ...er box cover 4 Disconnect the gas supply line from the gas valve Remove gas valve manifold assembly 5 Mark and disconnect sensor wire from the sensor Disconnect2 pin plug from the ignitor at the burne...

Страница 58: ...horizontal bars will display Steps to follow if the damper control module is displaying the soft disable code Confirm proper wiring between all devices thermostat damper control module indoor and out...

Страница 59: ...water column pressure of high pressure switch on heat call measure inches of water column of operating pressure inspect vent and combustion air inducer for correct operation and restriction E226 High...

Страница 60: ...de is lower than cfm setting Restricted airflow Indoor blower is running at a reduced cubic feet per minute Cutback Mode The variable speed motor has pre set speed and torque limiters to protect the m...

Страница 61: ...e solid P symbol is displayed on the 7 segment LED Release button This mode allows the user to select a unit size code number that matches the furnace model size and capacity Solid P starts blinking o...

Страница 62: ...rial Wait For Ignition Stabilization Delay Post Purge 20Seconds Soft Lockout Error Code Flashes YES NO NO YES Call For Heat Ends NO YES YES NO C A L L F O R 1 S T S T A G E H E A T 3A 2 1 1 OR Call Fo...

Страница 63: ...Closes Within 10 Seconds NO Error Code Flashes NO YES Wait 5 Minutes 3A 2 1 2 1 System will always light at 70 even if 2nd stage call for heat is in place If the high pressure switch does not close w...

Страница 64: ...Closes Within 10 Seconds NO Error Code Flashes NO YES Wait 5 Minutes 3A 2 1 2 1 System will always light at 70 even if 2nd stage call for heat is in place If the high pressure switch does not close w...

Страница 65: ...20 Seconds Soft Lockout Error Code Flashes YES NO NO YES Call For Heat Ends NO YES YES NO C A L L F O R H E A T 3B 1 4 Move to Mid Firing Rate and High Firing Rate after 2nd and 3rd Stage Delays base...

Страница 66: ...gize and Low Cooling mode High Cooling mode High Cooling mode Per Ramping Profile NO NO YES NO 5 1 2 1 2 2 2 1 Indoor Blower On After 2 second delay Energize Indoor Blower Per Ramping Profile Energize...

Страница 67: ...S NO YES Go to Call for Cooling 6 1 4 5 1 Call for Continuous Blower Indoor Blower On Maintain Indoor Blower at set speed Maintain Indoor Blower at set speed OR Maintain Indoor Blower at set speed Ind...

Страница 68: ...ng at a minimum height of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print si...

Страница 69: ...rovinces of Canada Lennox approves the following termination for use in all provices of Canada C 12 D B A 2 51MM Vent Pipe 3 76MM Vent Pipe 12 305 mm Min 12 305 mm Min 6 152 mm Min 24 610 mm Max 6 152...

Страница 70: ...pes Supported Condensate Trap Primed Line Sloped Heat Cable Installed and Operable if applicable 2 2 2 1 Horizontal Pipes Sloped if applicable UNIT SET UP typical 3 4 Flter RETURN AIR Furnace Model Nu...

Страница 71: ...5 Supply External Static _______ Return External Static ______ Total External Static _______ CONDENSATE LINE 6 Leak Free VENT PIPE 7 Leak Free COOLING MODE INDOOR BLOWER AMPS______ 3 TEMPERATURE DROP...

Отзывы: