background image

Page 36

TABLE 28

OPERATING SEQUENCE

G60UHV, Thermostat with Humidity Control Feature and Two−Speed Outdoor Unit

OPERATING MODE

SYSTEM DEMAND

SYSTEM RESPONSE

System

Condition

Thermostat

Demand

*Relative Humidity

(Efficiency

Plus

 Lights)

****Compressor

Speed

Blower CFM

(COOL)

Comments

Normal operation

Y1

No demand. Acceptable

Low

**42%/46% of

HIGH COOL

Compressor demand and indoor 

blower speed controlled by 

Normal operation

Y2

No demand. Acceptable

High

HIGH COOL

blower speed controlled by 

thermostat demand

Y1

No demand. Acceptable

Low

**42%/46% of

HIGH COOL

Call for humidity 

removal during

Y1

Humidity level rises slightly

(1) above setpoint. Demand

initiated.

Low

**42%/46% of

HIGH COOL

Dehumidification mode does not begin

until after initial thermostat demand is

removal during

1st−stage cooling

demand

Demand

satisfied

Humidity level remains

slightly (1) above setpoint.

Demand continues.

Off

Off

until after initial thermostat demand is

satisfied and new cooling demand is

initiated.

Y1

Humidity level remains

slightly (1) above setpoint.

Demand continues.

High

***65%/60% of

HIGH COOL

Significant increase in

humidity during

Y1

No demand. Acceptable

Low

**42%/46% of

HIGH COOL

If humidity rises significantly above set-

point, or if slide switch is moved signifi-

l

i

ill i

di

l

i

d

humidity during 

thermostat cooling 

demand.

Y1

Humidity level rises signifi-

cantly (2 or more) above

setpoint. Demand initiated.

High

***65%/60% of

HIGH COOL

point, or if slide switch is moved signifi

cantly, unit will immediately go into de-

humidification mode (in presence of

thermostat demand).

Y1

Humidity level

above setpoint.

High

***65%/60% of

HIGH COOL

When humidity demand is satisfied,

Humidity demand

satisfied during

Y1

Humidity level falls below

setpoint. No demand.

High

HIGH COOL

When humidity demand is satisfied,

blower immediately shifts to the COOL

CFM in order to hasten the end of the

cycle Unit can only shift out of high

satisfied during

thermostat demand.

None

No demand. Acceptable

Off

Off

cycle. Unit can only shift out of high

speed compressor operation at begin-

Y1

No demand. Acceptable

Low

**42%/46% of

HIGH COOL

speed compressor operation at begin

ning of next cycle.

Call for humidity

Y2

No demand. Acceptable

High

HIGH COOL

Call for humidity

removal during 2nd

stage thermostat

demand

Y2

Humidity level rises slightly

(1) above setpoint. Demand

initiated.

High

***65%/60% of

HIGH COOL

Blower immediately changes speed in

response to thermostat demand.

demand

Y2

No demand. Acceptable

High

HIGH COOL

*Call for 1st stage

cooling after call for

None

Humidity level is slightly (1)

above setpoint.

Off

Off

Dehumidification mode (high speed

compressor) begins with next thermo-

cooling after call for

humidity removal.

Y1

Humidity level is slightly (1)

above setpoint.

Low

**42%/46% of

HIGH COOL

compressor) begins with next thermo

stat demand after initial demand is sat-

isfied.

Call for 2nd stage

cooling after call for

None

Humidity level is slightly (1)

above setpoint.

Off

Off

Reduced blower speed (dehumidifica-

tion speed) begins immediately with

cooling after call for

humidity removal

Y2

Humidity level is slightly (1)

above setpoint.

High

***65%/60% of

HIGH COOL

tion speed) begins immediately with

thermostat demand

Call for cooling after

significant increase in

None

Humidity level is significantly

above setpoint (2 or more).

Off

Off

If humidity increases significantly over

setpoint, or if slide switch is moved,

unit immediately goes into dehumidifi

significant increase in

humidity

Y1 or Y2

Humidity level is significantly

above setpoint (2 or more).

High

***65%/60% of

HIGH COOL

unit immediately goes into dehumidifi-

cation mode (in presence of thermostat

demand).

Humidity demand
satisfied between

None

Humidity level is slightly (1)

above setpoint.

Off

Off

While unit is not operating (no thermo-

stat demand), slide switch is moved

down and back up Blower and com

satisfied between

thermostat demands

(unit off cycle).

Y1 or Y2

Humidity level falls below

setpoint. No demand.

High

HIGH COOL

down and back up. Blower and com-

pressor operate at high speed until

next thermostat demand.

NOTE − When changing unit mode of operation from cooling to heating, indicating lights that are on will stay on until the first ther-
mostat heating demand.

*IMPORTANT - If power to unit is turned on with thermostat calling for humidity removal, outdoor unit may be locked into high
speed indefinitely. To reset, move humidity slide switch all the way down then back up to desired setpoint (with unit running)
** Reduced blower speed is 42% of HIGH COOL for −36A and −36B units; 46% of HIGH COOL for −60C and −60D series units.
*** Reduced blower speed is 65% of HIGH COOL for −36A and −36B units; 60% of HIGH COOL for −60C and −60D series units. 
****If the two−speed control on a two−speed outdoor unit is set for LATCH 2 (15 minutes) or LATCH 3 (30 minutes), the compres-
sor will latch into high speed after a Y1 demand has occurred for that period of time.

Содержание Signature G60UHV36A-070

Страница 1: ...tion 39 Service 40 Planned Service 42 Repair Parts List 42 Integrated Control Diagnostic Codes 43 Troubleshooting 44 Start Up Performance Check List 50 WHAT TO DO IF YOU SMELL GAS Do not store or use...

Страница 2: ...ingle side with transition which will accommodate 20 x 25 x 1 in 508 x 635 x 25 mm cleanable air filter Required to maintain proper air velocity 2 Return air from single side with optional RAB Return...

Страница 3: ...Ox Insert Primary Limit Door Interlock Switch Two Stage Variable Speed Integrated Control Control Transformer Circuit Breaker Gasket Flue Box Gasket Gas Orifices Ignitor Bracket Burner Box Bottom Limi...

Страница 4: ...ew York NY 10036 In Canada installation must conform with current National Standard of Canada CSA B149 installation codes for natu ral gas and propane gas burning appliances and equip ment local plumb...

Страница 5: ...erature range between 60 F 16 C and 80 F 27 C must be maintained D Air filters must be installed in the system and must be maintained during construction D Air filters must be replaced upon constructi...

Страница 6: ...ents as well as all local codes CAUTION Insufficient combustion air can cause headaches nausea dizziness or asphyxiation It will also cause excess water in the heat exchanger resulting in rust ing and...

Страница 7: ...have a minimum free area of 1 square inch 645 mm2 per 1 000 Btu 29 kW per hour of total input rating of all gas fired equipment in the confined space Each opening must be at least 100 square inches 6...

Страница 8: ...e square inch 645 mm2 per 4 000 Btu 1 17 kW per hour of the total input rating of all equip ment in the enclosure CHIMNEY OR GAS VENT WATER HEATER OUTLET AIR VENTILATION LOUVERS Each end of attic INLE...

Страница 9: ...The bolt and washer must be re moved before the furnace is placed into operation Af ter the bolt and washer have been removed the rigid leg will not touch the blower housing NOTE G60UHV 60D 135 units...

Страница 10: ...ition and filter FIGURE 7 Return Air Plenum Transition 20 X 25 X 1 508mm X635mm X 25mm Cleanable Filter Optional Return Air Base Upflow Applications Only For use with B C and D cabinets only FIGURE 8...

Страница 11: ...tom of the unit 3 Screw another nut onto the bolt on the inside of the fur nace base A flat washer may be added between the nut and the bottom of the unit 4 Adjust the outside nut to the appropriate h...

Страница 12: ...Horizontal Applications Return air can be brought in through the end of a furnace installed in a horizontal application The furnace is equipped with a removable bottom panel to facilitate instal lati...

Страница 13: ...everse flow of the flue gas may result in incom plete combustion and the formation of carbon monoxide gas This toxic gas might then be distributed throughout the house by the furnace duct system In up...

Страница 14: ...e used Drive one self drilling screw through the front and one through each side of the vent pipe and collar See figure 16 Install the first vent connector elbow at a minimum of six inches 152 mm from...

Страница 15: ...embly according to the terms of their respective listings and the vent manufacturer s instructions When inspection reveals that an existing chimney is not safe for the intended purpose it shall be reb...

Страница 16: ...approved means except vent connectors of listed type B vent material which shall be assembled according to the manufacturer s instructions Joints between sections of single wall connector piping shall...

Страница 17: ...0 226 22 339 15 5 22 65 30 130 39 219 49 330 10 29 59 40 121 51 206 64 315 15 35 53 48 112 61 195 76 301 0 0 97 0 202 0 349 0 540 2 10 75 14 149 18 250 20 377 20 5 21 71 29 143 38 242 47 367 20 10 28...

Страница 18: ...36 80 225 115 337 15 5 51 63 75 128 102 216 144 326 10 NR NR 95 116 128 201 182 308 15 NR NR NR NR 158 186 220 290 0 35 96 54 200 78 346 114 537 2 37 74 56 148 78 248 113 375 20 5 50 68 73 140 100 239...

Страница 19: ...6 69 220 1 21 50 33 89 47 142 64 220 15 2 22 53 35 96 49 153 66 235 3 24 55 36 102 51 163 68 248 1 21 54 33 99 46 157 62 246 20 2 22 57 34 105 48 167 64 259 3 23 60 35 110 50 176 66 271 1 20 62 31 113...

Страница 20: ...hile each appliance is operat ing and the other appliances which are not operating re main connected to the common venting system If the vent ing system has been installed improperly you must correct...

Страница 21: ...ff valve and union furnished by the installer external to the unit The union must be of the ground joint type IMPORTANT Compounds used on threaded joints of gas piping must be resistant to the actions...

Страница 22: ...suresless than or equal to 1 2 psig 3 48 kPa 14 inches w c IMPORTANT When testing pressure of gas lines gas valve must be disconnected and isolated See figure 20 Gas valves can be damaged if subjected...

Страница 23: ...ntrol Any electronic air cleaner rated up to one amp can be connected to this terminal with the neutral leg of the circuit being con nected to the one of the provided neutral terminals See figure 25 f...

Страница 24: ...ge heat ON delay OFF 10 min utes ON 15 minutes ON Intact Intact Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 1 Heat 2 Cool NOTE Use DIP switch 2 to set second stage heat ON delay OFF 10 min utes O...

Страница 25: ...oling W914 Dehu midification or Harmony III W951 Heat Pumps Wiring Connections 2 Heat 2 Cool OFF Cut Intact Intact S1 T STAT CONTROL TERM STRIP OUTDOOR UNIT 2 Heat 2 Cool with t stat with humidity con...

Страница 26: ...Page 26 G60UHV X Schematic Wiring Diagram FIGURE 23...

Страница 27: ...tment 9 and 10 Cooling Mode Blower Ramping Profile 11 and 12 Heating Mode Blower Speed INDOOR BLOWER DIP SWITCHES HEATING DIP SWITCHES DIAGNOSTIC LEDs ON BOARD LINKS 1 T stat Heat Stages single or two...

Страница 28: ...affects comfort and is adjustable to satisfy individ ual applications Adjust the blower off delay to achieve a supply air temperature between 90 and 110 F at the exact moment that the blower is de en...

Страница 29: ...able connection between ter minals DS and R on the integrated control W914 must be cut when the furnace is installed with either the Harmony IIIt zone control or a thermostat which features humidity c...

Страница 30: ...Zone Control Applications Minimum blower speed is 426 cfm 200 L s TABLE 17 G60UHV 36B 090 BLOWER MOTOR PERFORMANCE 0 0 to 0 8 w g 0 through 200 Pa External Static Pressure Range Factory Settings Heati...

Страница 31: ...speed is 478 cfm 225 L s TABLE 19 G60UHV 60C 090 BLOWER MOTOR PERFORMANCE 0 0 to 0 8 w g 0 through 200 Pa External Static Pressure Range Factory Settings Heating Speed 2 Cooling Speed 4 Speed Adjust N...

Страница 32: ...minimum 500 cfm 235 L s Lennox Harmony IIIt Zone Control Applications Minimum blower speed is 478 cfm 225 L s TABLE 21 G60UHV 60C 110 BLOWER MOTOR PERFORMANCE 0 0 to 0 8 w g 0 through 200 Pa External...

Страница 33: ...cond stage COOL speed position minimum 500 cfm 235 L s Lennox Harmony IIIt Zone Control Applications Minimum blower speed is 483 cfm 230 L s TABLE 23 G60UHV 60C 110 BLOWER MOTOR PERFORMANCE 0 0 to 0 8...

Страница 34: ...er speed is 495 cfm 235 L s TABLE 25 G60UHV 60D 135 BLOWER MOTOR PERFORMANCE 0 0 to 0 8 w g 0 through 200 Pa External Static Pressure Range Factory Settings Heating Speed 2 Cooling Speed 4 Speed Adjus...

Страница 35: ...l Applications Minimum blower speed is 495 cfm 235 L s TABLE 27 OPERATING SEQUENCE G60UHV Thermostat with Humidity Control Feature and Single Speed Outdoor Unit OPERATING MODE SYSTEM DEMAND SYSTEM RES...

Страница 36: ...d High 65 60 of HIGH COOL Blower immediately changes speed in response to thermostat demand demand Y2 No demand Acceptable High HIGH COOL Call for 1st stage cooling after call for None Humidity level...

Страница 37: ...alls for heat the burn ers will automatically light The ignitor does not get hot when there is no call for heat on units with an automatic ignition system WARNING If you do not follow these instructio...

Страница 38: ...to the changeover kit installation instruction for the conversion procedure Other Unit Adjustments Primary and Secondary Limits The primary limit is located on the heating compartment vestibule panel...

Страница 39: ...warm up period begins The combustion air in ducer continues to operate at low speed 4 After the 20 second warm up period has ended the gas valve is energized on low fire first stage and igni tion occ...

Страница 40: ...sizes Flue And Chimney Check the flue pipe chimney and all connections for tight ness and to make sure there is no blockage Electrical 1 Check all wiring for loose connections 2 Check for the correct...

Страница 41: ...er the face of burners Visually in spect inside the burners and crossovers for any block age caused by foreign matter Remove any blockage 16 NOx units only Reattach the NOx inserts to the cor bels at...

Страница 42: ...oducts must be analyzed and compared to the unit specifications Problems detected during the inspection may make it nec essary to temporarily shut down the furnace until the items can be repaired or r...

Страница 43: ...itch failed closed 2 7 Low pressure switch opened during ignition trial or heating demand LIMIT CODE 3 1 Limit switch open WATCHGUARD CODES 4 1 Watchguard Exceeded maximum number of retries 4 2 Watchg...

Страница 44: ...COMBUSTION AIR INDUCER ON INDOOR BLOWER ON STATUS ERROR CODE 5 1 SEQUENCE HOLDS UNTIL ROLLOUT SWITCH IS RESET AND MAIN POWER IS INTERRUPTED OR T STAT IS CYCLED OFF ON FOR 3 SEC MINIMUM NO YES FIRST L...

Страница 45: ...CONNECTED STATUS ERROR CODE 4 7 YES AT END OF IGNITOR 20 SECOND WARM UP PERIOD 4 SECOND TRIAL FOR IGNITION GAS VALVE OPENS IGNITOR ENERGIZED DURING 4 SECOND TRIAL UNTIL FLAME SENSED YES 4 SECOND FLAME...

Страница 46: ...IRST STAGE HEAT DEMAND SATISFIED GAS VALVE OFF COMBUSTION AIR INDUCER OFF FOLLOWING POST PURGE INDOOR BLOWER OFF WITH DELAY STATUS LED PULSE YES SECOND STAGE HEAT DEMAND SECOND STAGE HEAT DEMAND REQUI...

Страница 47: ...ODE DIP SWITCH SET AT SINGLE YES YES FIRST AND SECOND STAGE HEAT DEMAND SATISFIED SIMULTANEOUSLY STATUS LED HEARTBEAT YES GAS VALVE OFF COMBUSTION AIR INDUCER OFF AFTER 5 SECOND LOW SPEED POST PURGE P...

Страница 48: ...ZED NO IS THERE PROPER GROUND YES NO INDOOR BLOWER ENERGIZED ON FIRST STAGE COOL SPEED AFTER 2 SECOND DELAY FIRST STAGE DEMAND FOR COOL SATISFIED NO THERMOSTAT CALLS FOR SECOND STAGE COOL COMPRESSOR A...

Страница 49: ...TO LOW HEAT SPEED FIRST STAGE HEAT DEMAND SATISFIED YES NO THERMOSTAT CALLS FOR SECOND STAGE HEAT YES INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED AFTER 30 SECOND RECOGNITION PERIOD SECOND STAGE HEAT DE...

Страница 50: ...ht Heating Section Thermostat Heat Anticipator Setting Thermostat Level Fuel Type Natural Gas Blower Motor Amps Blower Motor H P Gas Piping Connections Tight Leak Tested Proper Draft State Blower OFF...

Отзывы: