24

NOTE: DIAGRAMS AND ILLUSTRATIONS ARE NOT TO SCALE

CAUTION:  Label all wires prior to disconnection when servic-

ing controls. Wiring errors can cause improper and dangerous 

operation. 
ATTENTION:    Au  moment  de  l'entretien  des  commandes, 

étiquetez tous les fils avant de les débrancher.  Des erreurs 

de cáblage peuvent entraîner un fonctionnement inadéquat et 

dangereux.

Blower Operation

Your Shoreline gas insert comes equipped with a 150 CFM blower with 

a variable speed control and an automatic temperature activated On/Off 

snap switch.

1. Plug the blower power cord into a grounded (three-prong) outlet. 

Read Warning above.

2. After the fireplace insert warms up, the blower will turn on if the speed 

control (located at the right below the firebox) is left in the "ON" posi-

tion. The blower will not operate until the fireplace insert is warm.

3. Once the blower turns on, turn the knob to the desired speed. No 

further adjustment is necessary.

4. If you do not wish to have the blower on, turn the knob counterclock-

wise until it clicks into the "OFF" position.

       

WARNING

The power cord must be plugged directly into a prop-

erly grounded, 120 Volt, 60 Hz, 3-prong receptacle 

electrical outlet. Do not cut or remove the ground-

ing prong from this plug. It must be routed to avoid 

contact. Do not route power cord under or in front 

of appliance.

       IMPORTANT 

Keep your house well ventilated during the curing 

process.  The odor and haze emitted by the curing 

process can be quite noticeable and may set off a 

smoke detector.

Burn-In Period

This 

Shoreline™

 insert has been painted with a high temperature metal-

lic black stove paint. It leaves the factory dry to the touch, but finishes 

curing as the fireplace insert is used. Fire the fireplace insert four suc-

cessive times for ten minutes each time with a five minute cool down 

between each firing to cure the paint and burn off lubricants used in the 

manufacturing process. Ventilate the house during these first firings as 

the paint gives off an unpleasant odor. It is recommended that persons 

sensitive to an imbalance in the indoor air quality avoid the area where 

the fireplace insert is located during the curing process.  

Do not turn on 

blower during Burn-In period. 

Figure 36 - Blower Wiring Diagram

BLACK

MALE SPADE 

1/4”

FEMALE 

SPADE 1/4”

WHITE

BLOWER RHEOSTAT

BLACK

BLOWER

MALE SPADE 1-4”

FEMALE SPADE 1/4”

POWER CORD

BLACK

GREEN/GROUND

WHITE

MALE SPADE 1/4”

FEMALE SPADE 1/4”

FEMALE SPADE 1/4”

WHITE

BLACK

WHITE

BLOWER SNAP DISC

Quiet Operation

As the Shoreline is burning, a number of normal operational sounds may 

be heard. The flow of gas through the gas valve and orifice may make a 

rushing or whistling noise. If this noise is objectionable, it can be reduced 

by turning down the flame. Turning down the flame can reduce total heat 

output by more than 30%. When the blower turns on, the sound of rushing 

air may be heard. The blower sounds may be reduced by adjusting the 

speed control rheostat (see 

Figure 31

). Also, a slight clicking sound may 

be heard as the gas valve or blower switch turn on and off.

Electrical Requirements

This gas insert operates without an outside power source, however the 

blower requires a 120-Volt electrical service outlet. This appliance, when 

installed, must be electrically grounded in accordance with local codes, 

or in the absence of local codes, the National Electrical Code ANSI/NFPA 

70 - latest edition.  In Canada, the current CSA C22-1 Canadian Electri-

cal  Code  -  latest  edition.  (

See  Shoreline  Main  Burner  Operation

  for 

thermostat and ON/OFF switch information).

BLACK

PLUG INTO 120 VAC 

60 HZ GROUNDED 

OUTLET

Содержание SHRL 33 DV INS

Страница 1: ...uctions du fournis seur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindie L installation et l entretien doivent tre assur s par un installateur ou un service d entretie...

Страница 2: ...e 29 Replacement Parts List Page 30 Part Identification Page 31 Optional Accessories Page 36 Safety Listing Label Page 39 Lighting Instructions Label Page 40 Warranty and Product Reference Information...

Страница 3: ...ler service agency or the gas supplier WARNING Failure to comply with these installation instructions will result in an improperly installed and operating appliance voiding its warranty Any change to...

Страница 4: ...not be connected to a chimney or flue serving a separate solid fuel burning appliance These appliances are vented gas appliances Do not burn wood or other material in these appliances This appliance i...

Страница 5: ...nician if you decide to change orifices Theuseofotherfuelsorcombinationoffuelswilldegradetheperformance of this system and may be dangerous Orifice Size Altitude Adjustment These appliances are tested...

Страница 6: ...tallation requirements These appliances must be vented directly to the outside in accordance with the current edition of the National Fuel Gas Code NFPA 54 in U S A and CAN CSA B149 1 in Canada and mu...

Страница 7: ...centimeters in length The individual manual shut off must be a T handle type valve Massachusetts Horizontal Vent Requirements IntheCommonwealthofMassachusetts horizontalterminationsinstalled less tha...

Страница 8: ...Unit To Intake Collar 7 7 8 200 N O D Width Small 3 pc Flange 36 5 8 930 N O D Width Large 3 pc Flange 41 1041 O O D Height Small 3 pc Flange 25 7 8 657 O O D Height Large 3 pc Flange 28 711 P O D Wi...

Страница 9: ...rfaces to combustible construction etc above the appliance Paint or lacquer used to finish the mantel must be heat resistant in order to avoid discoloration Minimum Clearances to Combustibles Hearth F...

Страница 10: ...tible une fois la conduite de gaz en place IMPORTANT Wheninstallingtheseappliancesintoafactorybuiltfireplace or heat form the air flow within and around the fireplace shall not be altered by the insta...

Страница 11: ...ethod for achieving a positive flue connection between the vent and intake liners and the chimney Air Inlet Liner for combustion air When terminating the air inlet liner at this point a positive flue...

Страница 12: ...seal See Table 5 for the minimum vertical termination height requirements Vertical Termination Height Minimum Factory Built and Masonry Fireplaces The vent air intake termination clearances above the...

Страница 13: ...ocationsontheupperlatchassembly You can then tighten the screws down by turning the wrench or T Handle clockwise SNUG ONLY DO NOT OVERTIGHTEN See Figure 12 4 Figure 13 shows the insert with the door i...

Страница 14: ...refractory brick panels and log set theinsertshouldbeinstalledinthefireplace the venting attached the gas line connected and tested for leaks and the initial burner operation checked Figure 15 Figure...

Страница 15: ...of carbon monoxide CO a colorless orderless toxic gas The size and position of the log set is critical to achieve a safe reliable and attractive flame pattern Any attempt to use a different log set i...

Страница 16: ...ctory in front See Figure 24 C B F pin 5 Locate groove in center log B and place the top of the right log D in groove with the bottom end of the log resting against the right refractory panel See Figu...

Страница 17: ...of its final location Surround Kits Models SHR33 SHR40 Part Cat Description Dimensions 75387 Small 3 sided Flange 36 5 8 W x 25 7 8 H 75385 Small 4 sided Flange 36 5 8 W x 29 3 16 H 75388 Large 3 side...

Страница 18: ...in Picture C Turning the ball screw counter clockwise as you are look ing at it will give you less tension and turning the ball screw clockwise will give you more tension when opening and closing the...

Страница 19: ...ometer and check the pressure Again close the tap gently but securely after completing the check Check the taps for gas leaks with a gas leak test solution and retighten if necessary If the pressure i...

Страница 20: ...thermostat mural voir Figure B et le cas ch ant sur le bo tier delat l commande FigureC Pouracheverl instal lationcorrectedecefoyer proc dezcommesuitavec les tiquettesadh sivesenlangues trang resfourn...

Страница 21: ...d call your service technician or your gas sup plier 8 After pilot is lit turn gas control counterclockwise to ON Knob can only be turned ON if the knob has popped out 9 To turn burner on turn ON OFF...

Страница 22: ...To Turn Off Gas To Appliance above Gas Control Knob Pilot On Off Flame Height Control Knob Hi Lo Piezo Igniter WARNINGS Improper installation adjustment alteration service or maintenance can cause inj...

Страница 23: ...ry while adjusting flame appearance Theairshuttershouldneverbesetsoastomake the tips of the flames sooty or create sooting on the viewing glass logs or heat exchanger If sootbeginstoformafterburning t...

Страница 24: ...t is used Fire the fireplace insert four suc cessive times for ten minutes each time with a five minute cool down between each firing to cure the paint and burn off lubricants used in the manufacturin...

Страница 25: ...manufacturers instructions could result in a malfunction Pay special attention to the thermostat location require ments If the location requirements are not adhered to the appliance erratic operation...

Страница 26: ...roperly size the flames The flames should directly contact the thermopile and extend across the main burner ports Be careful not to back the screw out of its threads Replace the cover and check for ga...

Страница 27: ...the inside of the glass this condensation and fog will usually disappear in a few minutes This can cause lint dust and other airborne particles to cling to the glass surface Initialcuringofthehightemp...

Страница 28: ...chnician Perform the appropriate appliance checkout procedure detailed in this manual Replacing Rockwool Ember Materials Homeowner Qualified Service Technician Remove old ember materials and vacuum th...

Страница 29: ...efective igniter no spark at electrode Defective or misaligned electrode at pilot spark at electrode Check gas supply To purge hold in gas cock on valve for 1 2 minutes and try again Check for spark a...

Страница 30: ...ector 26 H5751 Blower Ducting 27 H5752 Wire Grommets 28 H5753 Burner Support 29 H5754 Front Leveling leg Assembly 30 H5755 Gasket kit 31 H5756 Surround Hinge 32 H5757 Ball Screw Assembly 33 H5758 Ball...

Страница 31: ...26 25 27 2 30 PART IDENTIFICATION Item Description 2 Air Intake Assembly 3 Blower Box Assembly 4 Flue Collar Assembly 5 Blower Snap Switch Assembly 23 Brick Panel Brackets 24 Surround Hanging Brackets...

Страница 32: ...LE Item Description 8 Burner Assembly 9 Pilot Assembly w Shield 10 Main Orifice 11 Bulkhead Assembly 12 Cassette Plate Assembly 13 Valve Assembly 14 Air Shutter Assembly 15 Cassette Assembly 30 Gasket...

Страница 33: ...T TO SCALE 8 PART IDENTIFICATION Item Description 2 Air Intake Assembly 3 Blower Box Assembly w Blower 6 Rear Leveling Leg Assembly 7 Outer Bottom Assembly 8 Burner Assembly 27 Wire Grommets 29 Front...

Страница 34: ...N 22 Ceramic Log Set Item Description 8 Burner Assembly 16 Louver Assembly 17 Blower Rheostat 18 Control Panel Valve Cover 19 On Off Switch Item Description 20 Igniter w nut 21 Door Assembly 22 Cerami...

Страница 35: ...e Surround Assembly Item Description 31 Surround Flange Hinge 32 Ball Screw Assembly 33 Ball Screw Catch Assembly 34 Surround Spacer Kit Small 35 Surround Spacer Kit Large 36 Extrusion Kit 3 Piece Sma...

Страница 36: ...ng the hand held remote control transmitter Screen Panel Kit This screen panel kit can be installed over the glass enclosure panel to help protect from making direct contact with the hot glass surface...

Страница 37: ...piece Small 75388 SHR SP 3P LG Surround Panel Kits 3 piece Large Width Height Cat No Model Description H7987 SHR BRK STD Brick Panel Set Tan H7988 SHR BRK RED Brick Panel Set Red H7989 SHR BRK ARCHSTO...

Страница 38: ...er Kit DVI 3 X 35 requires 2 one for exhaust and one for intake TKDVI TKDVI Termination Kit DVI termination cap and flashing DV3FK35 DV3FK35 Flex Liner and Termination Kit 3 X 35 includes 2 flex liner...

Страница 39: ...devant G le foyer H Distance verticale de la base de H l appareil aux combustibles Note Extension d tre fabriqu avec 1 minimum de mat riaux non combustible ou quivalent poss dant un facteur k de 0 84...

Страница 40: ...ion suppl mentaires contactez un installateur qualifi un agent de service ou un fournisseur de gaz Si vous op rez cet appareil sans qu il ne soit correctement raccord un conduit d vacuation vous pourr...

Страница 41: ...41 NOTES...

Страница 42: ...anufacturer Normally all parts should be ordered through your Lennox distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the follow...

Отзывы: