Lennox SCU14M Series Скачать руководство пользователя страница 9

# 504,465M

Page 9

Using an Electronic Leak Detector

1. Connect the high pressure hose of the manifold

gauge set to the suction valve service port. (Normally
the high pressure hose is connected to the liquid line
port; however, connecting it to the suction ports helps
to protect the manifold gauge set from damage
caused by high pressure.)

2. With both manifold valves closed, connect the cylin-

der of R410A refrigerant. Open the valve on the
R410A cylinder (vapor only).

3. Open the high pressure side of the manifold to allow

R410A into the line set and indoor unit. Weigh in a
trace amount of R410A. (A trace amount is a maxi-
mum of 2 oz. of refrigerant or 3 lbs. pressure.) Close
the valve on the R410A cylinder and the valve on the
high pressure side of the manifold gauge set. Discon-
nect the R410A cylinder.

Do not attempt to backseat this valve. At-
tempts to backseat this valve will cause snap
ring to explode from valve body under pres-
sure of refrigerant. Personal injury and unit
damage will result.

  WARNING

3. Replace the stem cap. Tighten finger tight, then

tighten an additional 1/6 turn.

Leak Testing

After the line set has been connected to the indoor and
outdoor units, the line set connections and indoor unit
must be checked for leaks.

4. Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

When using high pressure gas such as nitrogen
for this purpose, be sure to use a regulator that
can control the pressure  down to 1 or 2 psig.

5. Adjust nitrogen pressure to 150 psig. Open the valve

on the high side of the manifold gauge set to pressur-
ize the line set and the indoor coil.

6. After a short period of time, open a refrigerant port to

make sure that an adequate amount of refrigerant has
been added for detection (refrigerant requirements will
vary with lengths). Check all joints for leaks. Purge
nitrogen and R410A mixture. Correct any leaks and
recheck.

IMPORTANT: The leak detector must be capable of
sensing HFC refrigerant.

Evacuation and Dehydration

Evacuating the system of non-condensables is critical for
proper operation of the unit. Non-condensables are
defined as any gas that will not condense under tempera-
tures and pressures present during operation of an air
conditioning system. Non-condensables and water vapor
combine with refrigerant to produce substances that
corrode copper piping and compressor parts.

1. Connect the manifold gauge set to the service valve

ports as follows: low pressure gauge to suction line
service valve and high pressure gauge to liquid line
service valve.

IMPORTANT

 – Compliant scroll compressors (as with

any refrigerant compressor) should never be used to
evacuate a refrigeration or air conditioning system.

NOTE

 – A temperature vacuum gauge, mercury

vacuum, or thermocouple gauge should be used. The
usual bourdon tube gauges are inaccurate in the
vacuum range.

2. Connect the vacuum pump (with vacuum gauge) to

the center port of the manifold gauge set.

3. Open both manifold valves and start vacuum pump.

4. Evacuate the line set and indoor unit to an absolute

pressure of 23mm (23,000 microns) of mercury
(approximately 1 in. of mercury). During the early
stages of evacuation, it is desirable to close the
manifold gauge valve at least once to determine if
there is a rapid rise in absolute pressure. A rapid rise
in pressure indicates a relatively large leak. If this
occurs, the leak testing procedure must be repeated.

NOTE

 – The term 

absolute pressure

 means the total

actual pressure with a given volume or system, above

Never use oxygen to pressurize refrigeration
or air conditioning systems. Oxygen will ex-
plode on contact with oil and could cause
personal injury or death.

  WARNING

Refrigerant can be harmful if inhaled. Refriger-
ant must always be used and recovered re-
sponsibly. Incorrect or irresponsible use of
refrigerant can result in personal injury or
death.

  WARNING

Содержание SCU14M Series

Страница 1: ...on and service performed by unqualified persons can result in property damage personal injury or death WARNING Risk of electrical shock Disconnect all remote power supplies before installing or servic...

Страница 2: ...m m 9 5 7 6 1 8 5 6 8 5 0 3 6 7 6 3 7 4 8 4 0 M 4 1 U C S n i 8 7 3 3 8 1 2 3 6 1 1 4 3 3 1 8 5 6 2 8 5 8 1 m m 1 6 8 6 1 8 5 6 8 0 3 3 6 7 6 3 7 4 0 6 0 M 4 1 U C S n i 8 7 9 3 8 1 2 3 6 1 1 4 3 9 1...

Страница 3: ...ation SCU14M condensing units use R410A which is an ozone friendly HFC refrigerant This unit must be installed with a matching indoor coil and line set SCU14M units are designed for use in expansion v...

Страница 4: ...to drafts direct sunshine or other heat sources 3 Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit see Figure 2 on this page and Figure 7 on page 14 4 Ground u...

Страница 5: ...e of nicks or dents and must be deburred I D and O D 2 Before making line set connections use dry nitrogen to purge the refrigerant piping This will help to prevent oxidation and the introduction of m...

Страница 6: ...Tighten to 20 30 ft lbs Use backup wrench on all wrench flats Overtightening will crush the teflon seal and may cause a leak 4 Connect the external equalizer line to the equalizer port on the suction...

Страница 7: ...ng procedures The existing devices are not approved for use with R410A refrigerant and may prevent proper flushing Use a field provided fitting to reconnect the lines 4 Remove the pressure tap valve c...

Страница 8: ...terclockwise until the valve stem just touches the retaining ring 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Liquid or Suction Line Service Valve 1 Remove...

Страница 9: ...oints for leaks Purge nitrogen and R410A mixture Correct any leaks and recheck IMPORTANT The leak detector must be capable of sensing HFC refrigerant Evacuation and Dehydration Evacuating the system o...

Страница 10: ...rant charge contained in condensing unit into system Replace and tighten caps Use a back up wrench on the suction and liquid valves when removing or replacing valve caps 4 To open suction valve remove...

Страница 11: ...2 4 0 M 4 1 U C S L 1 4 2 2 8 2 6 2 3 3 7 3 4 2 4 S 1 3 1 3 3 1 5 3 1 7 3 1 9 3 1 8 4 0 M 4 1 U C S L 6 2 2 6 6 2 0 1 3 6 5 3 7 0 4 S 0 3 1 2 3 1 5 3 1 7 3 1 9 3 1 0 6 0 M 4 1 U C S L 0 4 2 9 7 2 1 2...

Страница 12: ...each cooling season the system should be checked as follows 1 Clean and inspect condenser coil Coil may be flushed with a water hose 2 Condenser fan motor is pre lubricated and sealed No further lubri...

Страница 13: ...rmine the correct blower CFM Refer to the unit information service manual for pressure drop tables and proce dure 3 On belt drive blowers check belt for wear and proper tension 4 Check all wiring for...

Страница 14: ...APACITOR DUAL C12 B4 B4 BLACK RUN ORANGE COMMON K1 S87 S1 ROOM THERMOSTAT TO INDOOR UNIT COMMON 24VAC FAN HEAT W G R Y B1 2 2 2 S4 S1 ROOM THERMOSTAT LOW PRESSURE SWITCH HIGH PRESSURE SWITCH COMPRESSO...

Страница 15: ...n belts fuses or other consumable items 3 Damage caused by misuse failure to maintain properly accidents or acts of God 4 External wiring piping venting or attachment of accessory products not integra...

Отзывы: