Lennox SCU14M Series Скачать руководство пользователя страница 5

# 504,465M

Page 5

Plumbing

If the SCU14M unit is being installed with a new indoor
coil and line set, the plumbing connections should be
made as outlined in the section that follows. If an existing
line set and/or indoor coil will be used to complete the
system, refer to the section entitled 

Flushing Existing

Line Set and Indoor Coil

 on page 6. 

If this unit is being

matched with an approved line set or indoor coil
which was previously charged with R22 refrigerant,
the line set and coil must be flushed prior to installa-
tion.

Field refrigerant piping consists of liquid and suction lines
from the condensing unit (sweat connections).

Plumbing Connections Using New Indoor Coil and
Line Set

If refrigerant lines are to be routed through a wall, seal
and isolate the opening so vibration is not transmitted to
the building.

NOTE

 – Line length should be no greater than 50'. Use

Table 2 to select line set diameters to ensure oil return to
the compressor.

l

e

d

o

M

d

i

u

q

i

L

e

n

i

L

n

o

i

t

c

u

S

e

n

i

L

4

2

0

-

M

4

1

U

C

S

0

3

0

-

M

4

1

U

C

S

6

3

0

-

M

4

1

U

C

S

.

n

i

8

/

3

)

m

m

0

1

(

.

n

i

4

/

3

)

m

m

9

1

(

2

4

0

-

M

4

1

U

C

S

8

4

0

-

M

4

1

U

C

S

.

n

i

8

/

3

)

m

m

0

1

(

.

n

i

8

/

7

)

m

m

2

2

(

0

6

0

-

M

4

1

U

C

S

.

n

i

8

/

3

)

m

m

0

1

(

.

n

i

8

/

1

-

1

)

m

m

9

2

(

Refrigerant Line Kits

Table 2

Polyol ester (POE) oils used with R410A
refrigerant absorb moisture very quickly. It is
very important that the refrigerant system be
kept closed as much as possible. DO NOT
remove line set caps or service valve stub
caps until ready to make connections.

  WARNING

Brazing Connection Procedure

1. The end of the refrigerant line must be cut square and

its internal shape must remain round. The line must
be free of nicks or dents and must be deburred (I.D.
and O.D.).

2. Before making line set connections, use dry nitrogen

to purge the refrigerant piping. This will help to
prevent oxidation and the introduction of moisture into
the system.

3. Use silver alloy brazing rods (5% or 6% silver alloy for

copper-to-copper brazing or 45% silver alloy for
copper-to-brass or copper-to-steel brazing) which are
rated for use with R410A refrigerant. Wrap a wet cloth
around the valve body and the copper tube stub.
Remove light maroon washers from service valves
and shield light maroon stickers to protect them
during brazing. Braze the line set to the service valve.

4. Quench the joint with water or a wet cloth to prevent

heat damage to the valve core and opening port. 

The

tube end must stay bottomed in the fitting during
final assembly to ensure proper seating, sealing,
and rigidity.

5. Flush line set and evaporator if required (refer to

Flushing Existing Line Set and Indoor Coil 

on page

6).

6. Install the provided thermal expansion valve

(approved for use with R410A refrigerant) in the liquid
line at the indoor coil. (See the 

Installing Thermo

Expansion Valve

 section that follows.)

7. Install the provided filter drier (approved for use with

R410A refrigerant) in the liquid line as close as
possible to the expansion device. 

Do not leave the

drier uncapped for more than 10 – 15 minutes
prior to brazing, evacuation, and leak testing.

Installing Thermo Expansion Valve

Before opening any system, make sure the
pressure in the system is brought to and
remains at atmospheric pressure. Failure to
comply can result in system damage and/or
personal injury.

  WARNING

1. Insert suction line splice between evaporator and

suction line with the equalizer port pointing upwards.

To prevent plugging the equalizer line with oil, the
equalizer port must be between a 10:00 and 2:00
position.

Содержание SCU14M Series

Страница 1: ...on and service performed by unqualified persons can result in property damage personal injury or death WARNING Risk of electrical shock Disconnect all remote power supplies before installing or servic...

Страница 2: ...m m 9 5 7 6 1 8 5 6 8 5 0 3 6 7 6 3 7 4 8 4 0 M 4 1 U C S n i 8 7 3 3 8 1 2 3 6 1 1 4 3 3 1 8 5 6 2 8 5 8 1 m m 1 6 8 6 1 8 5 6 8 0 3 3 6 7 6 3 7 4 0 6 0 M 4 1 U C S n i 8 7 9 3 8 1 2 3 6 1 1 4 3 9 1...

Страница 3: ...ation SCU14M condensing units use R410A which is an ozone friendly HFC refrigerant This unit must be installed with a matching indoor coil and line set SCU14M units are designed for use in expansion v...

Страница 4: ...to drafts direct sunshine or other heat sources 3 Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit see Figure 2 on this page and Figure 7 on page 14 4 Ground u...

Страница 5: ...e of nicks or dents and must be deburred I D and O D 2 Before making line set connections use dry nitrogen to purge the refrigerant piping This will help to prevent oxidation and the introduction of m...

Страница 6: ...Tighten to 20 30 ft lbs Use backup wrench on all wrench flats Overtightening will crush the teflon seal and may cause a leak 4 Connect the external equalizer line to the equalizer port on the suction...

Страница 7: ...ng procedures The existing devices are not approved for use with R410A refrigerant and may prevent proper flushing Use a field provided fitting to reconnect the lines 4 Remove the pressure tap valve c...

Страница 8: ...terclockwise until the valve stem just touches the retaining ring 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Liquid or Suction Line Service Valve 1 Remove...

Страница 9: ...oints for leaks Purge nitrogen and R410A mixture Correct any leaks and recheck IMPORTANT The leak detector must be capable of sensing HFC refrigerant Evacuation and Dehydration Evacuating the system o...

Страница 10: ...rant charge contained in condensing unit into system Replace and tighten caps Use a back up wrench on the suction and liquid valves when removing or replacing valve caps 4 To open suction valve remove...

Страница 11: ...2 4 0 M 4 1 U C S L 1 4 2 2 8 2 6 2 3 3 7 3 4 2 4 S 1 3 1 3 3 1 5 3 1 7 3 1 9 3 1 8 4 0 M 4 1 U C S L 6 2 2 6 6 2 0 1 3 6 5 3 7 0 4 S 0 3 1 2 3 1 5 3 1 7 3 1 9 3 1 0 6 0 M 4 1 U C S L 0 4 2 9 7 2 1 2...

Страница 12: ...each cooling season the system should be checked as follows 1 Clean and inspect condenser coil Coil may be flushed with a water hose 2 Condenser fan motor is pre lubricated and sealed No further lubri...

Страница 13: ...rmine the correct blower CFM Refer to the unit information service manual for pressure drop tables and proce dure 3 On belt drive blowers check belt for wear and proper tension 4 Check all wiring for...

Страница 14: ...APACITOR DUAL C12 B4 B4 BLACK RUN ORANGE COMMON K1 S87 S1 ROOM THERMOSTAT TO INDOOR UNIT COMMON 24VAC FAN HEAT W G R Y B1 2 2 2 S4 S1 ROOM THERMOSTAT LOW PRESSURE SWITCH HIGH PRESSURE SWITCH COMPRESSO...

Страница 15: ...n belts fuses or other consumable items 3 Damage caused by misuse failure to maintain properly accidents or acts of God 4 External wiring piping venting or attachment of accessory products not integra...

Отзывы: