Lennox SCU14M Series Скачать руководство пользователя страница 12

Page 12

# 504,465M

l

e

d

o

M

e

r

u

t

a

r

e

p

m

e

T

h

c

a

o

r

p

p

A

-

.

p

m

e

T

e

n

i

L

d

i

u

q

i

L

F

°

t

n

e

i

b

m

A

r

o

o

d

t

u

O

4

2

0

-

M

4

1

U

C

S

1

-

/

+

8

0

3

0

-

M

4

1

U

C

S

1

-

/

+

7

6

3

0

-

M

4

1

U

C

S

1

-

/

+

6

2

4

0

-

M

4

1

U

C

S

1

-

/

+

8

8

4

0

-

M

4

1

U

C

S

1

-

/

+

8

0

6

0

-

M

4

1

U

C

S

1

-

/

+

8

Approach Temperatures

Table 6

using the approach method. The difference between
the ambient and liquid temperatures should match
values given in Table 6. Refrigerant must be added to
lower approach temperature and removed to increase
approach temperature. Loss of charge results in low
capacity and efficiency.

5. If the system is low on charge, R410A refrigerant

must be added. Be aware of the R410A refrigerant
cylinder. It will be light maroon colored. Refrigerant
should be added through the suction valve in the
liquid state. 

Some R410A cylinders are equipped

with a dip tube which allows liquid to be drawn
from the bottom of the cylinder without turning
the cylinder upside-down. The cylinder will be
marked if it is equipped with a dip tube.

power from the compressor when suction line pressure
drops below factory setting at 40 ± 5 psi.

Filter Drier

A drier is shipped with each SCU14M unit. The drier must
be field installed in the liquid line between the liquid line
service valve and the expansion valve. 

This drier must

be installed to ensure a clean, moisture-free system.

 A

replacement drier is available through the local distributor.

MAINTENANCE

At the beginning of each cooling season, the system
should be checked as follows:

1. Clean and inspect condenser coil. Coil may be

flushed with a water hose.

2. Condenser fan motor is pre-lubricated and sealed. No

further lubrication is needed.

3. Visually inspect connecting lines and coils for evi-

dence of oil leaks.

4. Check wiring for loose connections.

5. Check for correct voltage at unit (with unit operating).

6. Check amp-draw condenser fan motor.

Unit nameplate _________  Actual _________

NOTE – If owner complains of insufficient cooling, the
unit should be gauged and refrigerant charge
checked. Refer to the 

Charging

 section on page 10.

Evaporator Coil

1. Clean coil, if necessary.

2. Check connecting lines and coils for evidence of oil

leaks.

3. Check condensate line and clean, if necessary.

OPERATION

Condensing unit and indoor blower cycle on demand from
the room thermostat. When the thermostat blower
switched in moved to the ON position, the indoor blower
operates continuously.

High Pressure Switch

SCU14M units are equipped with a high pressure switch
that is located in the discharge line of the compressor.
The switch (SPST, manual reset, normally closed) re-
moves power from the compressor when discharge
pressure rises above factory setting at 640 ± 10 psi.

Low Pressure Switch

SCU14M units are also equipped with a low pressure
switch that is located in the suction line of the compressor.
The switch (SPST, auto-reset, normally closed) removes

Before performing maintenance operations on
system, turn the electric power to unit OFF at
disconnect switch(es). Unit may have multiple
power supplies. Electrical shock could cause
personal injury or death.

  WARNING

Содержание SCU14M Series

Страница 1: ...on and service performed by unqualified persons can result in property damage personal injury or death WARNING Risk of electrical shock Disconnect all remote power supplies before installing or servic...

Страница 2: ...m m 9 5 7 6 1 8 5 6 8 5 0 3 6 7 6 3 7 4 8 4 0 M 4 1 U C S n i 8 7 3 3 8 1 2 3 6 1 1 4 3 3 1 8 5 6 2 8 5 8 1 m m 1 6 8 6 1 8 5 6 8 0 3 3 6 7 6 3 7 4 0 6 0 M 4 1 U C S n i 8 7 9 3 8 1 2 3 6 1 1 4 3 9 1...

Страница 3: ...ation SCU14M condensing units use R410A which is an ozone friendly HFC refrigerant This unit must be installed with a matching indoor coil and line set SCU14M units are designed for use in expansion v...

Страница 4: ...to drafts direct sunshine or other heat sources 3 Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit see Figure 2 on this page and Figure 7 on page 14 4 Ground u...

Страница 5: ...e of nicks or dents and must be deburred I D and O D 2 Before making line set connections use dry nitrogen to purge the refrigerant piping This will help to prevent oxidation and the introduction of m...

Страница 6: ...Tighten to 20 30 ft lbs Use backup wrench on all wrench flats Overtightening will crush the teflon seal and may cause a leak 4 Connect the external equalizer line to the equalizer port on the suction...

Страница 7: ...ng procedures The existing devices are not approved for use with R410A refrigerant and may prevent proper flushing Use a field provided fitting to reconnect the lines 4 Remove the pressure tap valve c...

Страница 8: ...terclockwise until the valve stem just touches the retaining ring 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Liquid or Suction Line Service Valve 1 Remove...

Страница 9: ...oints for leaks Purge nitrogen and R410A mixture Correct any leaks and recheck IMPORTANT The leak detector must be capable of sensing HFC refrigerant Evacuation and Dehydration Evacuating the system o...

Страница 10: ...rant charge contained in condensing unit into system Replace and tighten caps Use a back up wrench on the suction and liquid valves when removing or replacing valve caps 4 To open suction valve remove...

Страница 11: ...2 4 0 M 4 1 U C S L 1 4 2 2 8 2 6 2 3 3 7 3 4 2 4 S 1 3 1 3 3 1 5 3 1 7 3 1 9 3 1 8 4 0 M 4 1 U C S L 6 2 2 6 6 2 0 1 3 6 5 3 7 0 4 S 0 3 1 2 3 1 5 3 1 7 3 1 9 3 1 0 6 0 M 4 1 U C S L 0 4 2 9 7 2 1 2...

Страница 12: ...each cooling season the system should be checked as follows 1 Clean and inspect condenser coil Coil may be flushed with a water hose 2 Condenser fan motor is pre lubricated and sealed No further lubri...

Страница 13: ...rmine the correct blower CFM Refer to the unit information service manual for pressure drop tables and proce dure 3 On belt drive blowers check belt for wear and proper tension 4 Check all wiring for...

Страница 14: ...APACITOR DUAL C12 B4 B4 BLACK RUN ORANGE COMMON K1 S87 S1 ROOM THERMOSTAT TO INDOOR UNIT COMMON 24VAC FAN HEAT W G R Y B1 2 2 2 S4 S1 ROOM THERMOSTAT LOW PRESSURE SWITCH HIGH PRESSURE SWITCH COMPRESSO...

Страница 15: ...n belts fuses or other consumable items 3 Damage caused by misuse failure to maintain properly accidents or acts of God 4 External wiring piping venting or attachment of accessory products not integra...

Отзывы: