Lennox SCU14M Series Скачать руководство пользователя страница 10

Page 10

# 504,465M

Do not use a compressor to evacuate a sys-
tem. Avoid deep vacuum operation. Extremely
low vacuums can cause internal arcing and
compressor failure. Danger of equipment
damage. Damage caused by deep vacuum
operation will void warranty.

  WARNING

START-UP

the absolute zero of pressure. Absolute pressure in a
vacuum is equal to atmospheric pressure minus
vacuum pressure.

5. When the absolute pressure reaches 23mm of

mercury, close the manifold gauge valves, turn off the
vacuum pump, and disconnect the manifold gauge
center port hose from the vacuum pump. Attach the
manifold gauge center port hose to a nitrogen cylinder
with pressure regulator set to 150 psig and purge the
hose. Open the manifold gauge  valves to break the
vacuum in the line set and indoor unit. Close the
manifold gauge valves.

6. Shut off the nitrogen cylinder and remove the manifold

gauge hose from the cylinder. Open the manifold
gauge valves to release the nitrogen from the line set
and indoor unit.

7. Reconnect the manifold gauge to the vacuum pump,

turn the pump on, and continue to evacuate the line
set and indoor unit until the absolute pressure does
not rise above .5mm (500 microns) of mercury within
a 20-minute period after shutting off the vacuum
pump and closing the manifold gauge valves.

8. When the absolute pressure requirement above has

been met, disconnect the manifold hose from the
vacuum pump and connect it to an upright cylinder of
R410A refrigerant. Open the manifold gauge valves to
break the vacuum in the line set and indoor unit.
Close manifold gauge valves and shut off R410A
cylinder and remove manifold gauge set.

1. Rotate fan to check for frozen bearings or binding.

2. Inspect all factory and field-installed wiring for loose

connections.

3. Open liquid line and suction line service valves to

release refrigerant charge (contained in condensing
unit) into system. Replace and tighten caps. Use a
back-up wrench on the suction and liquid valves when
removing or replacing valve caps.

4. To open suction valve, remove hex cap and turn valve

stem fully open using an Allen (hex) wrench. To open

Mineral oils are not compatible with R410A. If
oil must be added, it must be a polyol ester oil.

  IMPORTANT

t

e

S

e

n

i

L

d

i

u

q

i

L

r

e

t

e

m

a

i

D

t

s

u

j

d

a

.

t

f

5

r

e

p

.

z

O

*

t

e

s

e

n

i

l

.

t

f

0

2

m

o

r

f

.

n

i

6

1

/

5

.

t

f

5

r

e

p

.

z

o

2

.

n

i

8

/

3

.

t

f

5

r

e

p

.

z

o

3

Refrigerant Charge Adjustment

* If line length is 

greater than 20 ft.

, add this amount.

If line length is 

less than 20 ft.

, remove this amount.

Table 3

liquid valve, remove cap and turn valve stem until it is
fully open.

NOTE:

 When replacing valve caps, the caps should

be finger tight then tightened an additional 1/6 of a
turn.

5. Check voltage supply at the disconnect switch. the

voltage must be within the range listed on the unit
nameplate. If not, do not start equipment until the
power company has been consulted and the voltage
condition corrected.

6. Set thermostat for cooling demand, turn on power to

blower and close the condensing unit disconnect
switch to start.

7. Recheck unit voltage with unit running. Power must be

within range shown on unit nameplate. Check amper-
age draw of unit. Refer to unit nameplate for correct
running amps.

Charging

This system is charged with R410A refrigerant which
operates at much higher pressures than R22. the expan-
sion valve and liquid line drier provided with the unit are
approved for use with R410A. Do not replace them with
components designed for use with R22. This unit is NOT
approved for use with coils which include metering orifices
or capillary tubes.

Processing Procedure

Units are factory charged with the amount of R410A
refrigerant indicated on the unit rating plate. This charge is
based on a matching indoor coil and outdoor coil with 20'
line set. For varying lengths of line set, refer to Table 3 for
refrigerant charge adjustment.

Содержание SCU14M Series

Страница 1: ...on and service performed by unqualified persons can result in property damage personal injury or death WARNING Risk of electrical shock Disconnect all remote power supplies before installing or servic...

Страница 2: ...m m 9 5 7 6 1 8 5 6 8 5 0 3 6 7 6 3 7 4 8 4 0 M 4 1 U C S n i 8 7 3 3 8 1 2 3 6 1 1 4 3 3 1 8 5 6 2 8 5 8 1 m m 1 6 8 6 1 8 5 6 8 0 3 3 6 7 6 3 7 4 0 6 0 M 4 1 U C S n i 8 7 9 3 8 1 2 3 6 1 1 4 3 9 1...

Страница 3: ...ation SCU14M condensing units use R410A which is an ozone friendly HFC refrigerant This unit must be installed with a matching indoor coil and line set SCU14M units are designed for use in expansion v...

Страница 4: ...to drafts direct sunshine or other heat sources 3 Install low voltage wiring from outdoor to indoor unit and from thermostat to indoor unit see Figure 2 on this page and Figure 7 on page 14 4 Ground u...

Страница 5: ...e of nicks or dents and must be deburred I D and O D 2 Before making line set connections use dry nitrogen to purge the refrigerant piping This will help to prevent oxidation and the introduction of m...

Страница 6: ...Tighten to 20 30 ft lbs Use backup wrench on all wrench flats Overtightening will crush the teflon seal and may cause a leak 4 Connect the external equalizer line to the equalizer port on the suction...

Страница 7: ...ng procedures The existing devices are not approved for use with R410A refrigerant and may prevent proper flushing Use a field provided fitting to reconnect the lines 4 Remove the pressure tap valve c...

Страница 8: ...terclockwise until the valve stem just touches the retaining ring 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Liquid or Suction Line Service Valve 1 Remove...

Страница 9: ...oints for leaks Purge nitrogen and R410A mixture Correct any leaks and recheck IMPORTANT The leak detector must be capable of sensing HFC refrigerant Evacuation and Dehydration Evacuating the system o...

Страница 10: ...rant charge contained in condensing unit into system Replace and tighten caps Use a back up wrench on the suction and liquid valves when removing or replacing valve caps 4 To open suction valve remove...

Страница 11: ...2 4 0 M 4 1 U C S L 1 4 2 2 8 2 6 2 3 3 7 3 4 2 4 S 1 3 1 3 3 1 5 3 1 7 3 1 9 3 1 8 4 0 M 4 1 U C S L 6 2 2 6 6 2 0 1 3 6 5 3 7 0 4 S 0 3 1 2 3 1 5 3 1 7 3 1 9 3 1 0 6 0 M 4 1 U C S L 0 4 2 9 7 2 1 2...

Страница 12: ...each cooling season the system should be checked as follows 1 Clean and inspect condenser coil Coil may be flushed with a water hose 2 Condenser fan motor is pre lubricated and sealed No further lubri...

Страница 13: ...rmine the correct blower CFM Refer to the unit information service manual for pressure drop tables and proce dure 3 On belt drive blowers check belt for wear and proper tension 4 Check all wiring for...

Страница 14: ...APACITOR DUAL C12 B4 B4 BLACK RUN ORANGE COMMON K1 S87 S1 ROOM THERMOSTAT TO INDOOR UNIT COMMON 24VAC FAN HEAT W G R Y B1 2 2 2 S4 S1 ROOM THERMOSTAT LOW PRESSURE SWITCH HIGH PRESSURE SWITCH COMPRESSO...

Страница 15: ...n belts fuses or other consumable items 3 Damage caused by misuse failure to maintain properly accidents or acts of God 4 External wiring piping venting or attachment of accessory products not integra...

Отзывы: