background image

Page 5

Locate & Level the Unit

The compact design of this furnace makes it ideal for a
basement or utility room installation. Choose a central
location for the furnace so that supply air ducts approxi-
mately the same length. This will allow each room to re-
ceive the proper amount of heat. The furnace should be
placed so that the flue connection to the chimney will be of
minimum length and have a minimum number of elbows.

 1− Set the unit in desired location keeping in mind the

clearances listed in table 2. Also keep in mind oil sup-
ply connections, electrical supply, flue connections
and sufficient clearance for installing and servicing
unit.

 2− Level the unit from side to side and from front to rear. If

the furnace is not level, place fireproof wedges or
shims between the low side of the furnace and the
floor. Make sure the weight of the furnace is distributed
evenly on all four corners. Strain on sides of cabinet
causing cracking and popping noises may occur if
weight of furnace is not evenly distributed.

Unit Adjustments

Neither the nozzle setting nor the air adjustments are facto-
ry set. The furnace is fire tested and the limit control is
checked to make sure it functions properly; no factory set-
tings are made. During installation, the furnace must be
set up." The installing dealer/contractor must have and
use proper test equipment in order to correctly set up the oil
furnace. Proper testing equipment is required to ensure
correct operation of the unit. The use of test equipment is
now more critical than ever due to tighter tolerances need-
ed to keep the furnace operating efficiently.
Among the test equipment for an oil furnace, the proper
combustion test kit should contain the following:

D

Draft gauge

D

CO

2

 or O

2

 Analyzer

D

Smoke tester

D

Pressure gauge

D

High temperature thermometer

D

Oil vacuum gauge

D

Beckett T−500 gauge

D

Knowledge of proper test equipment operation

CAUTION

Improper nozzle and/or air adjustment of this unit
may result in sooting problems. Refer to the follow-
ing section for correct adjustment procedures.

Nozzle Adjustment

Proper adjustment of the nozzle assembly is critical because
alignment may have changed during shipping. Before the fur-
nace and oil lines are installed, the nozzle assembly must be
checked. This may easily be done by removing the entire
burner assembly (not just the nozzle) from the furnace. The
lower firing nozzle is factory installed. This should be verified
by the installer. Inspect the spark transformer leads also to
ensure they are still attached to the electrodes. 

Note that

OF23−105/120 and OF23−140/154 series units use the
Beckett AFII burner. OF23−175/210R series units use the
Beckett AFG burner.

The burner assembly is attached to the vestibule panel by
three nuts. Slots are provided in the mounting flange for re-
moving the burner assembly from the vestibule. By loosen-
ing the nuts and by turning the whole burner assembly coun-
terclockwise (figure 3), the entire burner assembly will come
out of the furnace. There is adequate wire to remove the
burner without disconnecting wires. Once removed, just turn
the burner around in the vest panel area.

Figure 3

OF23 Series Burner Removal

First, loosen three nuts which

attach burner to vest panel.

Next, rotate burner counter-

clockwise on slots then pull

toward you.

To correctly adjust the nozzle, use a Beckett #T−500 gauge.

Insert the small end of the gauge into the end of the cone
and measure from the flat of the end cone to the tip of the
nozzle. When nozzle depth is correct, the tip of the nozzle
should just touch the end of the gauge. Refer to the illustra-
tion sheet provided with the gauge. Note that the scale side
of the gauge is not used for this purpose. Corrections are
made by sliding the entire nozzle assembly forward or
backward within the blast tube (figure 4). At the same time,
nozzle alignment must be checked.

To check nozzle alignment, again insert the small end of
gauge into the end cone and measure the nozzle and
electrode alignment against the center lines marked on
the gauge (again refer to enclosed illustration sheet). If
the nozzle is not centered, but found to be too far left or
right, a new nozzle assembly will need to be ordered. Do
not attempt to adjust by bending the 90 degree elbow in
the oil line.

Содержание OF23Q3/4-105

Страница 1: ...OF23 Oil AFII Burner Parts Arrangement 4 Requirements 4 Locate Level Unit 4 Unit Adjustments 5 Venting 6 Flue Connect ions 11 Supply Return Air Plenums 11 Oil Supply Lines Sizing 11 Connect Oil Supply...

Страница 2: ...1 2 1334 27 686 18 x 21 457 x 533 18 x 16 457 x 406 OF23Q5 140 154 22 1 2 572 37 940 52 1 2 1334 27 686 21 x 21 533 x 533 21 x 16 533 x 406 OF23Q5 140 154R 22 1 2 572 37 940 52 1 2 1334 27 686 21 x 2...

Страница 3: ...EAD HEAD INSULATOR CLIP RETAINING 1 4 HEX HEAD SCREW FB HEADS ASSY FOR AIR TUBE ASSY ELECTRODE HEAD NOZZLE LINE PEDESTAL ADAPTER NOZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET MOTOR 4X4 BOX IGNITOR...

Страница 4: ...re inch per 1 000 Btu per hour input This combustion air should be brought into the area containing the furnace below the level of the furnace burner IMPORTANT An opening to the outside for combustion...

Страница 5: ...ct adjustment procedures Nozzle Adjustment Proper adjustment of the nozzle assembly is critical because alignment may have changed during shipping Before the fur nace and oil lines are installed the n...

Страница 6: ...ed accord ing to the requirements of the National Fire Protection Asso ciation The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector Make sure t...

Страница 7: ...pipe shall not be connected to a chimney vent serving a solid fuel appliance or any mechanical draft system 14 All unused chimney openings should be closed 15 All vent pipe run through unconditioned...

Страница 8: ...Space An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet 1 4 cubic meters per 1 000 Btu 293 W per hour of the combined input rating of...

Страница 9: ...Vent Figure 11 NOTE Each air duct opening shall have a free area of at least one square inch 6 4 square centimeters per 2 000 Btu 586 W per hour of the total input rating of all equipment in the enclo...

Страница 10: ...common venting system Turn on any exhaust fans such as range hoods and bathroom ex hausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace damp ers 4 Followin...

Страница 11: ...pace to install the draft control in the flue pipe it may be installed in the vent above the flue pipe Follow the instructions packed with the draft control Alternate Side Flue Connections The vent pi...

Страница 12: ...or near walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings All fittings must be accessible Do not use compression fittings IMPORTANT...

Страница 13: ...asy maintenance Table 4 lists the filters for the OF23 furnace Consult the burner manufacturer s instructions that are in cluded with the unit for further details concerning oil supply pipe connection...

Страница 14: ...Page 14 Figure 16 Fan Control Board thermostat terminal strip Figure 17 Typical OF23 Wiring Diagram...

Страница 15: ...Page 15 Figure 18 Typical OF23 Wiring Diagram...

Страница 16: ...eat exchanger to prevent it from picking up radiant heat Set thermostat to its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the re...

Страница 17: ...should still be 0 02 less than the draft pres sure reading taken at the breach You may need to increase the stack draft by adjusting the barometric draft control 7 Stack Temperature Take a stack tempe...

Страница 18: ...ergized Circulating fan is energized at the cool speed Cooling compressor turns on immediately Thermostat ends call for cool G and Y terminals are de energized Circulating fan and cooling compressor t...

Страница 19: ...y control If the burner starts fault is in the Flame detector exposed to light Seal off false source of light the burner starts fault is in the detector circuit short circuit in the flame detec tor Re...

Страница 20: ...le for plugged Nozzle strainer plugged Replace nozzle with the same size spray angle and spray type spect t e o e o p ugged orifice or carbon build up around orifice Poor or off center spray type Foul...

Страница 21: ...inues to run d t l k Too much air lean short fire Reduce combustion air check combustion Poor Fire does not lock out of safety fault may be Too little air long dirty fire Increase combustion air check...

Страница 22: ...operly rotating wheel Restrictions in return or supply air system Correct cause of restriction Adjustable limit control set too low Reset limit to maximum stop setting Power If voltage fluctuates faul...

Страница 23: ...ack tem reading more than a trace Incorrect burner head adjust ment Correct burner setting CO2 stack tem perature and smoke Too little combustion air Increase combustion air smoke Too little blower ai...

Отзывы: