background image

Page 4

Requirements

WARNING

Product contains fiberglass wool.

Disturbing the insulation in this product during
installation, maintenance, or repair will expose you
to fiberglass wool dust. Breathing this may cause
lung cancer. (Fiberglass wool is known to the State
of California to cause cancer.)

Fiberglass wool may also cause respiratory, skin,
and eye irritation.

To reduce exposure to this substance or for further
information, consult material safety data sheets
available from address shown below, or contact your
supervisor.

Lennox Industries Inc.

P.O. Box 799900
Dallas, TX 75379−9900

Installation of Lennox oil−fired furnaces must conform with
the National Fire Protection Association Standard for the
Installation of Oil Burning Equipment, NFPA No. 31, the
National Electrical Code, ANSI/NFPA No.70 (in the
U.S.A.), CSA Standard CAN/CSA−B139 (in Canada),
Installation Code for Oil Burning Equipment, the Canadian
Electrical Code Part1, CSA 22.1 (Canada), the recommen-
dations of the National Environmental Systems Contrac-
tors Association and any state or provincial laws or local or-
dinances. Authorities having jurisdiction should be
consulted before installation. Such applicable regulations
or requirements take precedence over general instructions
in this manual.
Chimneys and chimney connectors must be of the type and
construction outlined in section 160 of NFPA No. 31.
Air for combustion and ventilation must conform to stan-
dards outlined in section 140 of NFPA No. 31 or, in Canada,
CSA Standard B139. When installing OF23 units in con-
fined spaces such as utility rooms, two combustion air
openings are required. Dimensions of combustion air
openings are shown in table 1. One opening shall be below
burner level and the other opening shall be no more than 6"
(152 mm) from the room’s ceiling.
The combustion air opening should provide a minimum free
area one-half square inch per 1,000 Btu per hour input. This
combustion air should be brought into the area containing the
furnace below the level of the furnace burner.

IMPORTANT

An opening to the outside for combustion air is
strongly recommended, especially in new homes.
Refer to table 1 or the unit plate for specific combus-
tion air opening dimensions.

Table 1

Combustion Air Opening Dimensions

Model No.

Combustion Air Opening

Dimensions (2 required)

O23−105/120

O23−105R/120R

10" X 20" (254 mm X 508 mm)

O23−140/154

O23−140R/154R

11" X 22" (279 mm X 559 mm)

O23−175R/210R
O23−175R/210R

20" X 40" (508 mm X 1016 mm)

This unit is approved for use on combustible flooring and for
clearances to combustible material as listed on unit rating
plate and in table 2. Unit service and accessibility clearances
take precedence over fire protection clearances.

Table 2

Installation Clearances

Clearances

All Unit Sizes 

inches (mm)

top of plenum and duct

2 (51)

plenum sides

3 (76)

sides*

6 (152)

rear

24 (610)

front

4 (102)

flue pipe measured vertical**

(measured from above)

9 (229)

NOTE−Service access clearance must be maintained.

*Clearance to allow inspection of furnace and flue connector 
shall be provided. 24" (610 mm) at rear and on one side of furnace should
be allowed for cleaning and service of the blower. 
**Minimum clearance shown for flue pipe may be reduced by using special
protection as provided by local building codes and the National Fire
Protection Association Standards and CSA 189.

NOTE − When service clearances are greater than fire
protection clearances, service clearances take prece-
dence.

Unit must be adjusted to obtain a temperature rise within
the range listed in table 3 in the Start-Up section of this
manual.

When installed, furnace must be electrically grounded in
accordance with local codes or, in the absence of local
codes, with the current National Electric Code, ANSI/NFPA
No. 70, or Canadian Electric Code (CEC) if an external
electrical source is utilized.

Field wiring connection with unit must meet or exceed
specifications of type T wire and withstand a 63

_

F (17

_

C)

temperature rise.

Содержание OF23Q3/4-105

Страница 1: ...OF23 Oil AFII Burner Parts Arrangement 4 Requirements 4 Locate Level Unit 4 Unit Adjustments 5 Venting 6 Flue Connect ions 11 Supply Return Air Plenums 11 Oil Supply Lines Sizing 11 Connect Oil Supply...

Страница 2: ...1 2 1334 27 686 18 x 21 457 x 533 18 x 16 457 x 406 OF23Q5 140 154 22 1 2 572 37 940 52 1 2 1334 27 686 21 x 21 533 x 533 21 x 16 533 x 406 OF23Q5 140 154R 22 1 2 572 37 940 52 1 2 1334 27 686 21 x 2...

Страница 3: ...EAD HEAD INSULATOR CLIP RETAINING 1 4 HEX HEAD SCREW FB HEADS ASSY FOR AIR TUBE ASSY ELECTRODE HEAD NOZZLE LINE PEDESTAL ADAPTER NOZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET MOTOR 4X4 BOX IGNITOR...

Страница 4: ...re inch per 1 000 Btu per hour input This combustion air should be brought into the area containing the furnace below the level of the furnace burner IMPORTANT An opening to the outside for combustion...

Страница 5: ...ct adjustment procedures Nozzle Adjustment Proper adjustment of the nozzle assembly is critical because alignment may have changed during shipping Before the fur nace and oil lines are installed the n...

Страница 6: ...ed accord ing to the requirements of the National Fire Protection Asso ciation The smallest dimensions of the chimney should be at least equal to the diameter of the furnace vent connector Make sure t...

Страница 7: ...pipe shall not be connected to a chimney vent serving a solid fuel appliance or any mechanical draft system 14 All unused chimney openings should be closed 15 All vent pipe run through unconditioned...

Страница 8: ...Space An unconfined space is an area such as a basement or large equipment room with a volume greater than 50 cubic feet 1 4 cubic meters per 1 000 Btu 293 W per hour of the combined input rating of...

Страница 9: ...Vent Figure 11 NOTE Each air duct opening shall have a free area of at least one square inch 6 4 square centimeters per 2 000 Btu 586 W per hour of the total input rating of all equipment in the enclo...

Страница 10: ...common venting system Turn on any exhaust fans such as range hoods and bathroom ex hausts so they will operate at maximum speed Do not operate a summer exhaust fan Close fireplace damp ers 4 Followin...

Страница 11: ...pace to install the draft control in the flue pipe it may be installed in the vent above the flue pipe Follow the instructions packed with the draft control Alternate Side Flue Connections The vent pi...

Страница 12: ...or near walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings All fittings must be accessible Do not use compression fittings IMPORTANT...

Страница 13: ...asy maintenance Table 4 lists the filters for the OF23 furnace Consult the burner manufacturer s instructions that are in cluded with the unit for further details concerning oil supply pipe connection...

Страница 14: ...Page 14 Figure 16 Fan Control Board thermostat terminal strip Figure 17 Typical OF23 Wiring Diagram...

Страница 15: ...Page 15 Figure 18 Typical OF23 Wiring Diagram...

Страница 16: ...eat exchanger to prevent it from picking up radiant heat Set thermostat to its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the re...

Страница 17: ...should still be 0 02 less than the draft pres sure reading taken at the breach You may need to increase the stack draft by adjusting the barometric draft control 7 Stack Temperature Take a stack tempe...

Страница 18: ...ergized Circulating fan is energized at the cool speed Cooling compressor turns on immediately Thermostat ends call for cool G and Y terminals are de energized Circulating fan and cooling compressor t...

Страница 19: ...y control If the burner starts fault is in the Flame detector exposed to light Seal off false source of light the burner starts fault is in the detector circuit short circuit in the flame detec tor Re...

Страница 20: ...le for plugged Nozzle strainer plugged Replace nozzle with the same size spray angle and spray type spect t e o e o p ugged orifice or carbon build up around orifice Poor or off center spray type Foul...

Страница 21: ...inues to run d t l k Too much air lean short fire Reduce combustion air check combustion Poor Fire does not lock out of safety fault may be Too little air long dirty fire Increase combustion air check...

Страница 22: ...operly rotating wheel Restrictions in return or supply air system Correct cause of restriction Adjustable limit control set too low Reset limit to maximum stop setting Power If voltage fluctuates faul...

Страница 23: ...ack tem reading more than a trace Incorrect burner head adjust ment Correct burner setting CO2 stack tem perature and smoke Too little combustion air Increase combustion air smoke Too little blower ai...

Отзывы: