Troubleshooting:  Burner starts and fires, but short cycles (too little heat)

Source

Procedure

Causes

Correction

Thermostat

Check thermostat.

Heat anticipator set too low

Correct heat anticipator setting.

Vibration at thermostat

Correct source of vibration.

Thermostat in the path of a
warm air draft

Shield thermostat from draft or
relocate.

Limit Control

Connect voltmeter between line
voltage connections to primary
control (black & white leads). If
burner cycles due to power inter-
ruption, it is cycling on limit.

Dirty furnace air filters

Clean or replace filter.

Burner running too slow

Increase blower speed to main-
tain proper temp. rise.

Blower motor seized or burned
out

Replace motor.

Blower bearings seized

Replace bearings and shaft.

Blower wheel dirty

Clean blower wheel.

Blower wheel in backward

Reverse blower wheel.

Wrong motor rotation

Replace with properly rotating
wheel.

Restrictions in return or supply
air system

Correct cause of restriction.

Adjustable limit control set too
low

Reset limit to maximum stop
setting.

Power

If voltage fluctuates, fault is in the
power source. Recheck voltage
at the power source.

Loose wiring connection

Locate and secure connection.

Low or fluctuating line voltage

Call power company.

Troubleshooting:  Burner runs continuously (too much heat).

Source

Procedure

Causes

Correction

Thermostat

Disconnect
thermostat
wires at the pri-
mary control.

If burner turns
off, fault is in
the thermostat
circuit.

Shorted or welded thermostat
contacts

Repair or replace the thermo-
stat.

Stuck thermostat bimetal

Clear obstruction or replace
thermostat.

Thermostat not level

Level thermostat.

Shorted thermostat wires

Repair short or replace wires.

Thermostat out of calibration

Replace thermostat.

Thermostat in cold draft

Correct draft or relocate the
thermostat.

Primary control

If burner does
not turn off,
fault is in the
primary control.

Defective primary control

Replace the defective primary
control.

Содержание O23Q2-70

Страница 1: ...t 5 Unit Adjustments 5 Venting 6 Flue Connections 10 Supply Return Air Plenums 11 Oil Supply Line Filter Connections 12 Leak Check 13 Electrical Wiring 13 Unit Start Up Adjustments 16 Service 17 Troub...

Страница 2: ...8 16 mm 495 778 457 498 406 O23Q5 140 154 in 22 1 2 33 1 8 21 22 1 8 18 mm 572 841 533 562 457 O23 Start Up Performance Check List Filter Clean Secure Supply Voltage Electrical Connections Tight Job N...

Страница 3: ...igure 2 FB HEAD HEAD INSULATOR CLIP RETAINING 1 4 HEX HEAD SCREW FB HEADS ASSY FOR AIR TUBE ASSY ELECTRODE HEAD NOZZLE LINE PEDESTAL ADAPTER NOZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET MOTOR 4X4...

Страница 4: ...nings are required Dimensions of combustion air openings are shown in table 1 One opening shall be below burner level and the other opening shall be no more than 6 152 mm from the room s ceiling IMPOR...

Страница 5: ...lowing D Draft gauge D CO2 or O2 analyzer D Smoke tester D Pressure gauge D High temperature thermometer D Beckett T 500 gauge D Oil vacuum gauge D Knowledge of proper test equipment operation CAUTION...

Страница 6: ...ss steel rather than aluminum Prior to installation of unit make a thorough inspection of the chimney to determine whether repairs are necessary Make sure the chimney is properly constructed and sized...

Страница 7: ...needs to exit from side of cabinet use the pilot hole located on either side of the unit to cut a 6 152 mm round hole Attach finishing plate provided with four sheet metal screws to cover rough edges...

Страница 8: ...talled so that supply ducts carry air circulated by the furnace to areas outside the space con taining the furnace the return air must be handled by ducts which are sealed to the furnace casing and wh...

Страница 9: ...e square inch 6 4 square centimeters per 4 000 Btu 1172 W per hour of the total input rating of all other equipment in the enclosure OIL FURNACE When ducts are used they shall be of the same cross sec...

Страница 10: ...peration Adjust ther mostat so appliance will operate continuously 5 Test for spillage using a draft gauge 6 After it has been determined that each appliance re maining connected to the common venting...

Страница 11: ...draft control at least 12 inches beyond the furnace If there is no space to install the draft control in the flue pipe it may be installed in the vent above the flue pipe Follow the instructions packe...

Страница 12: ...near walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings All fittings must be accessible Do not use compression fittings IMPORTANT Bot...

Страница 13: ...o mounting bracket 81P89 10 micron filter mounting bracket 53P92 10 micron replacement cartridge for filter 45 gph 53P93 Filter restriction indicator gauge 53P90 Consult burner manufacturer s instruct...

Страница 14: ...Page 14 Figure 17 Typical O23 Wiring Diagram...

Страница 15: ...Page 15 Figure 18 Typical O23 Wiring Diagram...

Страница 16: ...o its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the readings The difference in tempera tures in the supply and return air plenu...

Страница 17: ...ol 7 Stack Temperature Take a stack temperature reading in the vent pipe Subtract the room air temperature from the stack temperature This will give you the net stack temperature Use the efficiency ch...

Страница 18: ...ergized Circulating fan is energized at the cool speed Cooling compressor turns on immediately Thermostat ends call for cool G and Y terminals are de energized Circulating fan and cooling compressor t...

Страница 19: ...e burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off false source of light short circuit in the flame detec tor Rep...

Страница 20: ...plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray type Nozzle strainer plugged Poor or off center spray Ignition Electrod...

Страница 21: ...fter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbala...

Страница 22: ...perly rotating wheel Restrictions in return or supply air system Correct cause of restriction Adjustable limit control set too low Reset limit to maximum stop setting Power If voltage fluctuates fault...

Страница 23: ...exchanger Readjust burner Insufficient draft Increase draft Incorrect burner head adjust ment Correct burner setting Too little combustion air Increase combustion air High stack tem perature is more t...

Отзывы: