background image

Page 10

CAUTION

DO NOT USE a barometric draft relief in exhaust vent
pipe if outdoor combustion air is connected directly
to the burner. 

Removal of Unit from Common Venting System

In the event that an existing furnace is removed from a
venting system commonly run with separate appliances,
the venting system is likely to be too large to properly vent
the remaining attached appliances. The following test
should be conducted while each appliance is in operation
and the other appliances not in operation remain con-
nected to the common venting system. If venting system
has been installed improperly, the system must be cor-
rected as outlined in the previous section.

 1 − Seal any unused openings in the common venting

system.

 2 − Visually inspect venting system for proper size and

horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion or other deficiencies
which could cause an unsafe condition.

 3 − Insofar as is practical, close all building doors and win-

dows and all doors between the space in which the ap-
pliances remaining connected to the common venting
system are located and other spaces of the building.
Turn on clothes dryers and any appliances not con-
nected to the common venting system. Turn on any
exhaust fans, such as range hoods and bathroom ex-
hausts, so they will operate at maximum speed. Do not
operate a summer exhaust fan. Close fireplace damp-
ers.

 4 − Following the lighting instruction on the unit, place the

appliance being inspected in operation. Adjust ther-
mostat so appliance will operate continuously.

 5 − Test for spillage using a draft gauge.

 6 − After it has been determined that each appliance re-

maining connected to the common venting system
properly vents when tested as outlined above, return
doors, windows, exhaust fans, fireplace dampers and
any other fuel burning appliance to their previous con-
dition of use.

 7 − If improper venting is observed during any of the

above tests, the common venting system must be cor-
rected.

Horizontal Venting

The O23 is approved for horizontal venting with the follow-
ing mechanical vent systems:
Tjernlund (sideshot) #SS1C (Cat. #35E08) or Field Con-
trols #SWG−5 (Cat. #35P08) with the CK−61 (Cat. #18N28)
control kit. Refer to the manufacturers’ installation instruc-
tions for proper installation procedures and service parts
information.

Do not use the same vent with any other appliance
when using a sidewall vent system.

Maximum permissible vent length is 70 equivalent feet.
Minimum length is 15 equivalent feet. Calculate the equiva-
lent vent pipe footage from the furnace to the mechanical
vent system (Tjernlund or Field Controls) by adding the
straight vent pipe length and the equivalent elbow lengths
together.

Locate the barometric draft control within 18 inches of the
furnace flue outlet. See figure 12 for barometric draft con-
trol location.

HORIZONTAL VENTING

barometric

control*

horizontal venting

control

Figure 12

*Barometric control must

be installed in the hori-

zontal venting system and

located within 18" of flue

outlet of furnace.

Flue Connections

IMPORTANT

When flue pipe is installed at less than minimum
clearance listed in table 2, radiation shields must be
installed. See figure 13.

Содержание O23Q2-70

Страница 1: ...t 5 Unit Adjustments 5 Venting 6 Flue Connections 10 Supply Return Air Plenums 11 Oil Supply Line Filter Connections 12 Leak Check 13 Electrical Wiring 13 Unit Start Up Adjustments 16 Service 17 Troub...

Страница 2: ...8 16 mm 495 778 457 498 406 O23Q5 140 154 in 22 1 2 33 1 8 21 22 1 8 18 mm 572 841 533 562 457 O23 Start Up Performance Check List Filter Clean Secure Supply Voltage Electrical Connections Tight Job N...

Страница 3: ...igure 2 FB HEAD HEAD INSULATOR CLIP RETAINING 1 4 HEX HEAD SCREW FB HEADS ASSY FOR AIR TUBE ASSY ELECTRODE HEAD NOZZLE LINE PEDESTAL ADAPTER NOZZLE AIR SCOOP INLET WHEEL BLOWER FLANGE GASKET MOTOR 4X4...

Страница 4: ...nings are required Dimensions of combustion air openings are shown in table 1 One opening shall be below burner level and the other opening shall be no more than 6 152 mm from the room s ceiling IMPOR...

Страница 5: ...lowing D Draft gauge D CO2 or O2 analyzer D Smoke tester D Pressure gauge D High temperature thermometer D Beckett T 500 gauge D Oil vacuum gauge D Knowledge of proper test equipment operation CAUTION...

Страница 6: ...ss steel rather than aluminum Prior to installation of unit make a thorough inspection of the chimney to determine whether repairs are necessary Make sure the chimney is properly constructed and sized...

Страница 7: ...needs to exit from side of cabinet use the pilot hole located on either side of the unit to cut a 6 152 mm round hole Attach finishing plate provided with four sheet metal screws to cover rough edges...

Страница 8: ...talled so that supply ducts carry air circulated by the furnace to areas outside the space con taining the furnace the return air must be handled by ducts which are sealed to the furnace casing and wh...

Страница 9: ...e square inch 6 4 square centimeters per 4 000 Btu 1172 W per hour of the total input rating of all other equipment in the enclosure OIL FURNACE When ducts are used they shall be of the same cross sec...

Страница 10: ...peration Adjust ther mostat so appliance will operate continuously 5 Test for spillage using a draft gauge 6 After it has been determined that each appliance re maining connected to the common venting...

Страница 11: ...draft control at least 12 inches beyond the furnace If there is no space to install the draft control in the flue pipe it may be installed in the vent above the flue pipe Follow the instructions packe...

Страница 12: ...near walls to protect it from damage Avoid running pipes along joists or reverberating surfaces Always use flare fittings All fittings must be accessible Do not use compression fittings IMPORTANT Bot...

Страница 13: ...o mounting bracket 81P89 10 micron filter mounting bracket 53P92 10 micron replacement cartridge for filter 45 gph 53P93 Filter restriction indicator gauge 53P90 Consult burner manufacturer s instruct...

Страница 14: ...Page 14 Figure 17 Typical O23 Wiring Diagram...

Страница 15: ...Page 15 Figure 18 Typical O23 Wiring Diagram...

Страница 16: ...o its highest setting to start unit After plenum thermometers have reached their highest and steadiest readings subtract the readings The difference in tempera tures in the supply and return air plenu...

Страница 17: ...ol 7 Stack Temperature Take a stack temperature reading in the vent pipe Subtract the room air temperature from the stack temperature This will give you the net stack temperature Use the efficiency ch...

Страница 18: ...ergized Circulating fan is energized at the cool speed Cooling compressor turns on immediately Thermostat ends call for cool G and Y terminals are de energized Circulating fan and cooling compressor t...

Страница 19: ...e burner starts fault is in the detector circuit Flame detector leads are shorted Separate leads Flame detector exposed to light Seal off false source of light short circuit in the flame detec tor Rep...

Страница 20: ...plugged orifice or carbon build up around orifice Nozzle orifice plugged Replace nozzle with the same size spray angle and spray type Nozzle strainer plugged Poor or off center spray Ignition Electrod...

Страница 21: ...fter burner fires immedi ately jumper across flame detector termi nals at the pri mary control If burner con tinues to run does not lock out of safety fault may be due to poor fire Inspect fire Unbala...

Страница 22: ...perly rotating wheel Restrictions in return or supply air system Correct cause of restriction Adjustable limit control set too low Reset limit to maximum stop setting Power If voltage fluctuates fault...

Страница 23: ...exchanger Readjust burner Insufficient draft Increase draft Incorrect burner head adjust ment Correct burner setting Too little combustion air Increase combustion air High stack tem perature is more t...

Отзывы: