B

CANT ON THE OUTSIDE OF

THE FLARE

MALE FLARE

CONNECTION

Figure 16. Making Connections  

(Male to Female Connection)

IMPORTANT

Always use two wrenches when tightening flare nuts to 

avoid twisting refrigerant piping. DO NOT over-tighten 

flare nuts.

TORQUE WRENCH

TO INDOOR

UNIT

TO OUTDOOR UNIT

BACKUP

WRENCH

Figure 17. Tighten Flare Nut

Table 3.   Flare Nut Torque Recommendations

Outside 

Diameter

Recommended 

Torque

No torque wrench available 

Finger tighten and use an 

appropriately sized wrench to 

turn an additional:

Inches

1/4

15 ft.-lb. (20 N)

1/4 turn

3/8

26 ft.-lb. (35 N)

1/2 turn

1/2

41 ft.-lb. (56 N)

7/8 turn

5/8

48 ft.-lb. (65 N)

1 full turn

Indoor Unit Installation

CAUTION

In order to avoid injury, take proper precaution when 

lifting heavy objects.

Please refer to the installation instruction included with the 

indoor unit for setup.

IMPORTANT

Pipe and wire to each zone separately.
Test each indoor unit separately to ensure proper 

operation.

Connecting Multiple Capacity Indoor Units

•  The largest cpacity indoor unit must be connected to 

the lowest refirigerant connection ports on the outdoor 

unit.

• 

The  24,000  Btu  indoor  unit  is  only  allowed  to  be 

connected  to  MPA048S4M,  MPB048S4M  and 

MLA036S4M outdoor units.

NOTE: 

Each indoor unit must be piped AND wired to 

the correct zone piping connections and wiring 

terminals. Make sure that indoor unit A is wired 

to the zone A terminal block and connected to the 

appropriate refrigerant pipe connections.

A B C D

Unit D

Unit D

Unit C

Unit B

Unit A

Unit C

Unit B

Unit A

wire

pipe

outdoor

indoor

L4(ft)

L3(ft)

L2(ft)

L1(ft)

Figure 18. Pipe and Wire Each Zone Separately

A(1/2in)

A(1/4in)

B(3/8in)

B(1/4in)

C(3/8in)

C(1/4in)

Figure 19. Connecting Multiple Capacity Indoor 

Units

Содержание MWMA009S4-*P

Страница 1: ...should be consulted before installation The MWMA MWMB M22A M33A M33B MMDA MCFA and MCFB indoor units are matched with a two to five port multi zone outdoor heat pump unit to create a mini split system...

Страница 2: ...oor Units Indoor Unit Voltage Indoor Unit Voltage MWMA009S4 P 208 230V M33A024S4 P1 208 230V MWMA012S4 P 208 230V MMDA009S4 P 208 230V MWMA018S4 P 208 230V MMDA012S4 P 208 230V MWMA024S4 P1 208 230V M...

Страница 3: ...line shut off valve Port A Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable field provided TAPE Line set wrapped in foam insulatio...

Страница 4: ...M P MPB036S4M P inches 40 3 4 26 1 2 31 7 8 15 1 8 15 7 8 mm 1035 673 810 386 403 MPB048S4M P inches 41 3 4 25 52 1 2 16 3 8 15 7 8 mm 1060 634 1333 415 404 MLA018S4M P MLA030S4M P inches 40 5 8 26 1...

Страница 5: ...very high level of sound trans mission Install unit level Ground Level Building Structure Figure 4 Install Unit Level Choose a place solid enough to bear the weight and vibration of the unit where th...

Страница 6: ...w Figure 8 Avoid Defrost Water Ice Hazard Prevailing Winds Normally wind baffles are not required for a outdoor unit However in order to maximize reliability and performance the following best practic...

Страница 7: ...ed when installed on a concrete pad or the ground to allow drainage to occur If the heat pump unit is installed on wall mounting bracket insert the provided drain connector into one of the 1 inch 25 m...

Страница 8: ...en one of the flare nuts to release the factory nitrogen charge from the indoor units only 4 Remove the flare nuts from the connections on the unit and discard the seal from each of the piping connect...

Страница 9: ...refer to the installation instruction included with the indoor unit for setup IMPORTANT Pipe and wire to each zone separately Test each indoor unit separately to ensure proper operation Connecting Mul...

Страница 10: ...MPB 49 ft 15 m NOTE Minimum Line Set Length 10 ft 3 m per Indoor Unit Outdoor Unit Model No MPA018S4M P MPB018S4M P MLA018S4M P MPA030S4M P MPB030S4M P MLA030S4M P MPA036S4M P MPB036S4M P MLA036S4M P...

Страница 11: ...4 in x 1 2 in 2 018 A 1 1 4 in x 1 2 in 018 B 1 1 4 in x 1 2 in 3 009 A 1 4 in x 3 8 in 009 B 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 3 009 B 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 012 A 1 1 4 in x 1 2...

Страница 12: ...x 3 8 in 009 D 1 4 in x 3 8 in 012 B 1 1 4 in x 1 2 in 018 A 1 4 in x 1 2 in 4 009 D 1 4 in x 3 8 in 012 A 1 4 in x 1 2 in 012 B 1 1 4 in x 1 2 in 012 C 1 1 4 in x 1 2 in Table 4 Match Ups Outdoor Mod...

Страница 13: ...018 B 1 4 in x 1 2 in 018 C 1 1 4 in x 1 2 in 3 018 B 1 4 in x 1 2 in 018 C 1 1 4 in x 1 2 in 024 A 2 3 3 8 in x 5 8 in 4 009 A 1 1 4 in x 3 8 in 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 009 D 1...

Страница 14: ...atch Ups Outdoor Model No of Zones Indoor Unit Capacity Unit No Line Set Required Liquid x Gas MPA048S4M MPB048S4M Indoor Unit A 1 4 liq 1 2 gas Indoor Unit B 1 4 liq 1 2 gas Indoor Unit C 1 4 liq 3 8...

Страница 15: ...8 in 3 009 A 1 1 4 in x 3 8 in 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 3 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 012 A 1 4 in x 1 2 in Table 4 Match Ups Outdoor Model No of Zones Indoor U...

Страница 16: ...the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cylinder to the liquid and gas service ports 2 Open valve on nitrogen cylinder 3 Pressurize the...

Страница 17: ...lies before opening access panel Unit may have multiple power sources CAUTION All terminal connections must be made as illustrated in the following diagrams Improperly connected wiring could damage un...

Страница 18: ...230V Indoor Unit B From Power Supply Outdoor Unit Indoor Unit A Indoor Unit B Figure 21 Connection Diagram Systems 30k and Below To Indoor Unit C L2 1 A 3 A 2 A 208 230V Outdoor Unit Terminal Block Fr...

Страница 19: ...P SENSOR Figure 23 MPA018S4M P Outdoor Unit Wiring Diagram 6 6 6 YELLOW RED L PRO LOW PRESSURE SWITCH H PRO HIGH PRESSURE SWITCH 4 BLACK BLUE BROWN BLACK RED L2 BROWN BROWN BLUE BLUE BLACK BLACK 1 A 3...

Страница 20: ...SWITCH T3 T4 CRANKCASE HEATER DIODE MODULE SV L PFC INDUCTOR T5 MAIN BOARD OUTDOOR DC FAN 2 L 1 L XT1 T2B A B C D E CN13 E D B A INDOOR COIL OUTLET TEMP SENSOR C ELECTRONIC EXPANSION VALVE E CN30 CN2...

Страница 21: ...1 A 3 A L2 2 A L1 BLACK BLUE BROWN BLACK BLUE BROWN BLACK RED 1 B 2 B 3 B COMPRE SSOR DI SCHARG E TEMPER ATURE SENSOR Figure 27 MPB018S4M P Outdoor Unit Wiring Diagram HEAT1 SV HEAT2 WHITE WHITE 6 BLA...

Страница 22: ...EXV EXV HE AT_1 CR ANKCAS E HE ATE R Figure 29 MPB036S4M P Outdoor Unit Wiring Diagram DR IVER B OARD CODE PAR T NAME COMPR E S S OR D HE AT_1 CT1 AC CURRENT DETECTOR 4 WAY VALVE COMP E XV E LE CTR IC...

Страница 23: ...ESSOR DISCHARGE TEMP SENSOR INDUCTOR 2R0509A INDUCTOR 1R25027 Figure 31 MLA018S4M P Outdoor Unit Wiring Diagram HE AT _1 HE AT _2 CRANKCASE HEATER HEAT_1 HEAT_2 COMPRESSOR DISCHARGE TEMP SENSOR OUTDOO...

Страница 24: ...unit terminal strip The voltage must be within the range listed on the unit s nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has...

Отзывы: