Lennox MWMA009S4-*P Скачать руководство пользователя страница 5

5

Torque Requirements for Caps and 

Fasteners

When servicing or repairing HVAC components, ensure 

the fasteners are appropriately tightened. “Table 1. Torque 

Requirements” provides torque values for fasteners.

IMPORTANT

Only use Allen wrenches of sufficient hardness (50Rc - 

Rockwell scale minimum). Fully insert the wrench into 

the valve stem recess.
Service valve stems are factory-torqued from 9 ft.-lbs. 

(12 N*m) for small valves, to 25 ft.-lbs. (34 N*m) for large 

valves) to prevent refrigerant loss during shipping and 

handling. Using an Allen wrench rated at less than 50Rc 

risks rounding or breaking off the wrench, or stripping 

the valve stem recess.
See the Lennox Service and Application Notes C-08-1 

for further details and information.

Table 1.  Torque Requirements

Parts

Recommended Torque

U.S.

Newton-Meter- N

Service valve cap

8 ft.-lb.

11

Sheet metal screws

16 in.-lb.

2

Machine screws #10

27 in.-lb.

3

Compressor bolts

7 ft.-lb.

10

Gauge port seal cap

8 ft.-lb.

11

Outdoor Unit Installation

Placement Considerations

CAUTION

In order to avoid injury, take proper precaution when 

lifting heavy objects.

Consider the following when positioning the unit:

•  In coastal areas or other places with salty atmosphere 

of sulfate gas, corrosion may shorten the life of the 

unit. In coastal areas, the coil should be cleaned with 

potable water several times per year to avoid corrosive 

buildup (salt)

•   Some localities are adopting sound ordinances based 

on the unit’s sound level registered from the adjacent 

property, not from the property where the unit is in-

stalled. Install the unit as far as possible from the prop-

erty line

•  When possible, do not install the unit directly outside 

a window. Glass has a very high level of sound trans-

mission

•  Install unit level

Ground

Level

Building Structure

Figure 4.  Install Unit Level

•  Choose a place solid enough to bear the weight and 

vibration of the unit, where the operation noise will not 

be amplified

•  Choose a location where the hot air discharged from 

the unit or the operation noise will not be a nuisance 

to neighbors

•  Avoid installing the outdoor unit near a bedroom or 

other places where noise may cause a problem

• 

There must be sufficient space  to carry the unit into 

and out of the site

• 

There must be unobstructed air flow around the air in

-

let and the air outlet

• 

The unit must not be installed in areas where a flam

-

mable gas leak may occur

• 

Install the outdoor unit a minimum of 3 feet (1m) away 

from any antenna, power cord (line), radio, telephone, 

security  system,  or  intercom.  Electrical  interference 

and radio frequencies from any of these sources may 

affect operation

•  Since water drains from the outdoor unit during vari-

ous stages of operation, do not place anything which 

may be damaged by moisture under the unit

Direct Sunlight, Rain, Snow and Ice Protection

•  If the outdoor unit is subjected to prolonged exposure 

to direct sunlight with temperatures over 100°F (38°C) 

a canopy is recommended as illustrated in “Figure 5. 

Outdoor Unit on Pedestal (Stand) and Protective Can-

opy”  on  page  6  or  “Figure  10.  Dog  House-Style 

Shelter” on page 7

IMPORTANT

The construction of a canopy or shade is necessary 

because of an ambient limit control set to 122°F (50°C)  

to protect the electronics. If the outdoor unit is placed in 

direct sunlight it is possible that the limit may activate 

and shut down the unit. 

•  Place unit away from overhanging roof lines which 

would allow water or ice to drop on, or in front of, coil or 

into unit. Construct a canopy as illustrated in “Figure 5. 

Outdoor Unit on Pedestal (Stand) and Protective Can-

opy” on page 6

Содержание MWMA009S4-*P

Страница 1: ...should be consulted before installation The MWMA MWMB M22A M33A M33B MMDA MCFA and MCFB indoor units are matched with a two to five port multi zone outdoor heat pump unit to create a mini split system...

Страница 2: ...oor Units Indoor Unit Voltage Indoor Unit Voltage MWMA009S4 P 208 230V M33A024S4 P1 208 230V MWMA012S4 P 208 230V MMDA009S4 P 208 230V MWMA018S4 P 208 230V MMDA012S4 P 208 230V MWMA024S4 P1 208 230V M...

Страница 3: ...line shut off valve Port A Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable field provided TAPE Line set wrapped in foam insulatio...

Страница 4: ...M P MPB036S4M P inches 40 3 4 26 1 2 31 7 8 15 1 8 15 7 8 mm 1035 673 810 386 403 MPB048S4M P inches 41 3 4 25 52 1 2 16 3 8 15 7 8 mm 1060 634 1333 415 404 MLA018S4M P MLA030S4M P inches 40 5 8 26 1...

Страница 5: ...very high level of sound trans mission Install unit level Ground Level Building Structure Figure 4 Install Unit Level Choose a place solid enough to bear the weight and vibration of the unit where th...

Страница 6: ...w Figure 8 Avoid Defrost Water Ice Hazard Prevailing Winds Normally wind baffles are not required for a outdoor unit However in order to maximize reliability and performance the following best practic...

Страница 7: ...ed when installed on a concrete pad or the ground to allow drainage to occur If the heat pump unit is installed on wall mounting bracket insert the provided drain connector into one of the 1 inch 25 m...

Страница 8: ...en one of the flare nuts to release the factory nitrogen charge from the indoor units only 4 Remove the flare nuts from the connections on the unit and discard the seal from each of the piping connect...

Страница 9: ...refer to the installation instruction included with the indoor unit for setup IMPORTANT Pipe and wire to each zone separately Test each indoor unit separately to ensure proper operation Connecting Mul...

Страница 10: ...MPB 49 ft 15 m NOTE Minimum Line Set Length 10 ft 3 m per Indoor Unit Outdoor Unit Model No MPA018S4M P MPB018S4M P MLA018S4M P MPA030S4M P MPB030S4M P MLA030S4M P MPA036S4M P MPB036S4M P MLA036S4M P...

Страница 11: ...4 in x 1 2 in 2 018 A 1 1 4 in x 1 2 in 018 B 1 1 4 in x 1 2 in 3 009 A 1 4 in x 3 8 in 009 B 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 3 009 B 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 012 A 1 1 4 in x 1 2...

Страница 12: ...x 3 8 in 009 D 1 4 in x 3 8 in 012 B 1 1 4 in x 1 2 in 018 A 1 4 in x 1 2 in 4 009 D 1 4 in x 3 8 in 012 A 1 4 in x 1 2 in 012 B 1 1 4 in x 1 2 in 012 C 1 1 4 in x 1 2 in Table 4 Match Ups Outdoor Mod...

Страница 13: ...018 B 1 4 in x 1 2 in 018 C 1 1 4 in x 1 2 in 3 018 B 1 4 in x 1 2 in 018 C 1 1 4 in x 1 2 in 024 A 2 3 3 8 in x 5 8 in 4 009 A 1 1 4 in x 3 8 in 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 009 D 1...

Страница 14: ...atch Ups Outdoor Model No of Zones Indoor Unit Capacity Unit No Line Set Required Liquid x Gas MPA048S4M MPB048S4M Indoor Unit A 1 4 liq 1 2 gas Indoor Unit B 1 4 liq 1 2 gas Indoor Unit C 1 4 liq 3 8...

Страница 15: ...8 in 3 009 A 1 1 4 in x 3 8 in 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 3 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 012 A 1 4 in x 1 2 in Table 4 Match Ups Outdoor Model No of Zones Indoor U...

Страница 16: ...the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cylinder to the liquid and gas service ports 2 Open valve on nitrogen cylinder 3 Pressurize the...

Страница 17: ...lies before opening access panel Unit may have multiple power sources CAUTION All terminal connections must be made as illustrated in the following diagrams Improperly connected wiring could damage un...

Страница 18: ...230V Indoor Unit B From Power Supply Outdoor Unit Indoor Unit A Indoor Unit B Figure 21 Connection Diagram Systems 30k and Below To Indoor Unit C L2 1 A 3 A 2 A 208 230V Outdoor Unit Terminal Block Fr...

Страница 19: ...P SENSOR Figure 23 MPA018S4M P Outdoor Unit Wiring Diagram 6 6 6 YELLOW RED L PRO LOW PRESSURE SWITCH H PRO HIGH PRESSURE SWITCH 4 BLACK BLUE BROWN BLACK RED L2 BROWN BROWN BLUE BLUE BLACK BLACK 1 A 3...

Страница 20: ...SWITCH T3 T4 CRANKCASE HEATER DIODE MODULE SV L PFC INDUCTOR T5 MAIN BOARD OUTDOOR DC FAN 2 L 1 L XT1 T2B A B C D E CN13 E D B A INDOOR COIL OUTLET TEMP SENSOR C ELECTRONIC EXPANSION VALVE E CN30 CN2...

Страница 21: ...1 A 3 A L2 2 A L1 BLACK BLUE BROWN BLACK BLUE BROWN BLACK RED 1 B 2 B 3 B COMPRE SSOR DI SCHARG E TEMPER ATURE SENSOR Figure 27 MPB018S4M P Outdoor Unit Wiring Diagram HEAT1 SV HEAT2 WHITE WHITE 6 BLA...

Страница 22: ...EXV EXV HE AT_1 CR ANKCAS E HE ATE R Figure 29 MPB036S4M P Outdoor Unit Wiring Diagram DR IVER B OARD CODE PAR T NAME COMPR E S S OR D HE AT_1 CT1 AC CURRENT DETECTOR 4 WAY VALVE COMP E XV E LE CTR IC...

Страница 23: ...ESSOR DISCHARGE TEMP SENSOR INDUCTOR 2R0509A INDUCTOR 1R25027 Figure 31 MLA018S4M P Outdoor Unit Wiring Diagram HE AT _1 HE AT _2 CRANKCASE HEATER HEAT_1 HEAT_2 COMPRESSOR DISCHARGE TEMP SENSOR OUTDOO...

Страница 24: ...unit terminal strip The voltage must be within the range listed on the unit s nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has...

Отзывы: