8

Securing Outdoor Unit to Slab,  Frame, or Rails

If the outdoor unit is installed on a field-provided slab or 

frame, use lag bolts or equivalent to secure the outdoor 

unit to the slab or frame.

Four Field-provided Anchor Bolts

Figure 13. Securing Outdoor Unit to Slab

Four Field-Provided 

Anchor Bolts

Figure 14. Securing Outdoor Unit to Rails

Securing Outdoor Unit To Hanging Brackets

If  the  outdoor  unit  is  installed  on  field-provided  wall 

mounting brackets, use lag bolts or equivalent to secure 

the outdoor unit to the bracket. Minimum rear clearance 

can be reduced to 6 inches (152 mm) when mounted 

on brackets and with no obstructions on the other three 

sides. Allow for condensate disposal when placing units 

above one another.

Air Outlet

Air Inlet

6 in

152 mm

Figure 15. Securing Outdoor Unit to Brackets

Refrigerant Piping Connections

Field piping consists of two copper lines connecting 

the outdoor unit to the indoor unit. “Table 1. Torque 

Requirements” lists the connection sizes. The connections 

are made using the provided brass flare nuts at the end of 

the refrigerant piping connections. 

Both lines must be individually insulated.

1.  The seal on the unit refrigerant piping connections 

should remain in place until the last possible moment. 

This will prevent dust or water from getting into the 

refrigerant piping before it is connected.

2. 

CAREFULLY adjust refrigerant piping connections to 

suit the application.

3.  Slowly  loosen  one  of  the  flare  nuts  to  release  the 

factory nitrogen charge from the indoor units only.

4. 

Remove  the  flare  nuts  from  the  connections  on  the 

unit and discard the seal from each of the piping 

connections.

5. 

Slide the flare nuts onto the ends of the field-provided 

refrigerant piping before using a suitable flaring tool to 

flare the end of the copper pipe.

6.  Apply recommended HFC-410A refrigerant lubricant 

to the outside of the flared refrigerant lines. 

IMPORTANT

The  compressor  in  this  unit  contains  PVE 

oil  (Polyvinylether).  PVE  oil  is  formulated  for 

 

hydrofluorocarbon  (HFC)  refrigerants,  such  as  HFC-

410A, which this system contains. While it may have 

some miscibility properties with mineral-based oil and 

POE oil (Polyolester), it is not recommended to mix PVE 

oil with any other type of refrigerant oil.

7.  Align the threaded connections with the 

flared  refrigerant  lines.  Tighten  the  flare  nuts 

lightly  at  first  to  obtain  a  smooth  match  as 

illustrated in “Figure 16. Making Connections 

 

(Male to Female Connection)” on page 9.

8.  Once snug, continue another half-turn on each nut 

which should create a leak-free joint. A torque wrench 

may  be  used  to  tighten  flare  nuts  using  “Table  3.   

Flare  Nut  Torque  Recommendations”  on  page  9 

recommendations. 

Do not over-tighten a flared joint. 

Flared connections should always be accessible 

and must be insulated to prevent condensation.

9.  After refrigerant piping has been installed and checked 

for leaks, apply insulation over all flared connections.

Table 2.  Refrigerant Piping and Indoor Unit 

Connection Sizes

Size 

(Btuh)

Liquid Line 

in.

Gas Line 

in.

9000

1/4

3/8

12000

1/4

1/2

18000

1/4

1/2

24000

3/8

5/8

Содержание MWMA009S4-*P

Страница 1: ...should be consulted before installation The MWMA MWMB M22A M33A M33B MMDA MCFA and MCFB indoor units are matched with a two to five port multi zone outdoor heat pump unit to create a mini split system...

Страница 2: ...oor Units Indoor Unit Voltage Indoor Unit Voltage MWMA009S4 P 208 230V M33A024S4 P1 208 230V MWMA012S4 P 208 230V MMDA009S4 P 208 230V MWMA018S4 P 208 230V MMDA012S4 P 208 230V MWMA024S4 P1 208 230V M...

Страница 3: ...line shut off valve Port A Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable field provided TAPE Line set wrapped in foam insulatio...

Страница 4: ...M P MPB036S4M P inches 40 3 4 26 1 2 31 7 8 15 1 8 15 7 8 mm 1035 673 810 386 403 MPB048S4M P inches 41 3 4 25 52 1 2 16 3 8 15 7 8 mm 1060 634 1333 415 404 MLA018S4M P MLA030S4M P inches 40 5 8 26 1...

Страница 5: ...very high level of sound trans mission Install unit level Ground Level Building Structure Figure 4 Install Unit Level Choose a place solid enough to bear the weight and vibration of the unit where th...

Страница 6: ...w Figure 8 Avoid Defrost Water Ice Hazard Prevailing Winds Normally wind baffles are not required for a outdoor unit However in order to maximize reliability and performance the following best practic...

Страница 7: ...ed when installed on a concrete pad or the ground to allow drainage to occur If the heat pump unit is installed on wall mounting bracket insert the provided drain connector into one of the 1 inch 25 m...

Страница 8: ...en one of the flare nuts to release the factory nitrogen charge from the indoor units only 4 Remove the flare nuts from the connections on the unit and discard the seal from each of the piping connect...

Страница 9: ...refer to the installation instruction included with the indoor unit for setup IMPORTANT Pipe and wire to each zone separately Test each indoor unit separately to ensure proper operation Connecting Mul...

Страница 10: ...MPB 49 ft 15 m NOTE Minimum Line Set Length 10 ft 3 m per Indoor Unit Outdoor Unit Model No MPA018S4M P MPB018S4M P MLA018S4M P MPA030S4M P MPB030S4M P MLA030S4M P MPA036S4M P MPB036S4M P MLA036S4M P...

Страница 11: ...4 in x 1 2 in 2 018 A 1 1 4 in x 1 2 in 018 B 1 1 4 in x 1 2 in 3 009 A 1 4 in x 3 8 in 009 B 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 3 009 B 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 012 A 1 1 4 in x 1 2...

Страница 12: ...x 3 8 in 009 D 1 4 in x 3 8 in 012 B 1 1 4 in x 1 2 in 018 A 1 4 in x 1 2 in 4 009 D 1 4 in x 3 8 in 012 A 1 4 in x 1 2 in 012 B 1 1 4 in x 1 2 in 012 C 1 1 4 in x 1 2 in Table 4 Match Ups Outdoor Mod...

Страница 13: ...018 B 1 4 in x 1 2 in 018 C 1 1 4 in x 1 2 in 3 018 B 1 4 in x 1 2 in 018 C 1 1 4 in x 1 2 in 024 A 2 3 3 8 in x 5 8 in 4 009 A 1 1 4 in x 3 8 in 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 009 D 1...

Страница 14: ...atch Ups Outdoor Model No of Zones Indoor Unit Capacity Unit No Line Set Required Liquid x Gas MPA048S4M MPB048S4M Indoor Unit A 1 4 liq 1 2 gas Indoor Unit B 1 4 liq 1 2 gas Indoor Unit C 1 4 liq 3 8...

Страница 15: ...8 in 3 009 A 1 1 4 in x 3 8 in 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 3 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 012 A 1 4 in x 1 2 in Table 4 Match Ups Outdoor Model No of Zones Indoor U...

Страница 16: ...the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cylinder to the liquid and gas service ports 2 Open valve on nitrogen cylinder 3 Pressurize the...

Страница 17: ...lies before opening access panel Unit may have multiple power sources CAUTION All terminal connections must be made as illustrated in the following diagrams Improperly connected wiring could damage un...

Страница 18: ...230V Indoor Unit B From Power Supply Outdoor Unit Indoor Unit A Indoor Unit B Figure 21 Connection Diagram Systems 30k and Below To Indoor Unit C L2 1 A 3 A 2 A 208 230V Outdoor Unit Terminal Block Fr...

Страница 19: ...P SENSOR Figure 23 MPA018S4M P Outdoor Unit Wiring Diagram 6 6 6 YELLOW RED L PRO LOW PRESSURE SWITCH H PRO HIGH PRESSURE SWITCH 4 BLACK BLUE BROWN BLACK RED L2 BROWN BROWN BLUE BLUE BLACK BLACK 1 A 3...

Страница 20: ...SWITCH T3 T4 CRANKCASE HEATER DIODE MODULE SV L PFC INDUCTOR T5 MAIN BOARD OUTDOOR DC FAN 2 L 1 L XT1 T2B A B C D E CN13 E D B A INDOOR COIL OUTLET TEMP SENSOR C ELECTRONIC EXPANSION VALVE E CN30 CN2...

Страница 21: ...1 A 3 A L2 2 A L1 BLACK BLUE BROWN BLACK BLUE BROWN BLACK RED 1 B 2 B 3 B COMPRE SSOR DI SCHARG E TEMPER ATURE SENSOR Figure 27 MPB018S4M P Outdoor Unit Wiring Diagram HEAT1 SV HEAT2 WHITE WHITE 6 BLA...

Страница 22: ...EXV EXV HE AT_1 CR ANKCAS E HE ATE R Figure 29 MPB036S4M P Outdoor Unit Wiring Diagram DR IVER B OARD CODE PAR T NAME COMPR E S S OR D HE AT_1 CT1 AC CURRENT DETECTOR 4 WAY VALVE COMP E XV E LE CTR IC...

Страница 23: ...ESSOR DISCHARGE TEMP SENSOR INDUCTOR 2R0509A INDUCTOR 1R25027 Figure 31 MLA018S4M P Outdoor Unit Wiring Diagram HE AT _1 HE AT _2 CRANKCASE HEATER HEAT_1 HEAT_2 COMPRESSOR DISCHARGE TEMP SENSOR OUTDOO...

Страница 24: ...unit terminal strip The voltage must be within the range listed on the unit s nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has...

Отзывы: