Unit Start-Up

IMPORTANT

Units should  be energized 24 hours before unit 

start-up to prevent compressor damage as a result 

of slugging.

1. 

Inspect  all  factory-installed  and  field-installed  wiring 

for loose connections.

2.  Verify that the manifold gauge set is connected.

3. 

Add additional refrigerant charge if required before 

opening valves and while system is still under a 

vacuum.

4.  Open the liquid and gas line master valves and each 

individual port’s service valve to release the refrigerant 

charge contained in outdoor unit into the system.

5.  Replace the stem caps and tighten to the value listed 

in “Table 1. Torque Requirements” on page 5.

6.  Check voltage supply at the outdoor unit terminal strip. 

The voltage must be within the range listed on the 

unit’s  nameplate.  If  not,  do  not  start  the  equipment 

until you have consulted with the power company and 

the voltage condition has been corrected.

7.  Refer to the included user guide to operate the system 

using the provided remote control.

8.  Visually check for binding of both indoor and outdoor 

fans.

Refrigerant Charge

The outdoor unit is factory-charged with refrigerant. 

Calculate the additional refrigerant required according to 

the length of the liquid pipe (one way) between the outdoor 

unit and indoor unit connections.

Be sure to add the proper amount of additional refrigerant. 

Failure to do so may result in reduced performance.

Table 6.  Refrigerant Charge

System

Pre-charge  

Pipe Length

Amount of Refrigerant to add

Two-port

50 ft. (15 m)

0.16 oz ((L1 ft + L2 ft) - 50 ft)
0.005 kg ((L1 m + L2 m) - 15 m)

Three-

port

75 ft. (23 m)

0.16 oz ((L1 ft + L2 ft + L3 ft) - 75 ft)
0.005 kg ((L1 m + L2 m + L3 m) - 23 

m)

Four-port

100 ft. (30 m)

0.16 oz ((L1 ft + L2 ft + L3 ft + L4 ft) 

- 100 ft)

0.005 kg ((L1 m + L2 m + L3 m + L4 

m) - 30 m)

Five-port

125 ft. (38 m)

0.16 oz ((L1 ft + L2 ft + L3 ft + L4 ft + 

L5 ft) - 125 ft)

0.005 kg ((L1 m + L2 m + L3 m + L4 

m + L5 m) - 38 m)

Содержание MWMA009S4-*P

Страница 1: ...should be consulted before installation The MWMA MWMB M22A M33A M33B MMDA MCFA and MCFB indoor units are matched with a two to five port multi zone outdoor heat pump unit to create a mini split system...

Страница 2: ...oor Units Indoor Unit Voltage Indoor Unit Voltage MWMA009S4 P 208 230V M33A024S4 P1 208 230V MWMA012S4 P 208 230V MMDA009S4 P 208 230V MWMA018S4 P 208 230V MMDA012S4 P 208 230V MWMA024S4 P1 208 230V M...

Страница 3: ...line shut off valve Port A Wiring Condensate drain line wrapped in foam insulation Refrigerant Line Set Condensate Line And Indoor Outdoor Cable field provided TAPE Line set wrapped in foam insulatio...

Страница 4: ...M P MPB036S4M P inches 40 3 4 26 1 2 31 7 8 15 1 8 15 7 8 mm 1035 673 810 386 403 MPB048S4M P inches 41 3 4 25 52 1 2 16 3 8 15 7 8 mm 1060 634 1333 415 404 MLA018S4M P MLA030S4M P inches 40 5 8 26 1...

Страница 5: ...very high level of sound trans mission Install unit level Ground Level Building Structure Figure 4 Install Unit Level Choose a place solid enough to bear the weight and vibration of the unit where th...

Страница 6: ...w Figure 8 Avoid Defrost Water Ice Hazard Prevailing Winds Normally wind baffles are not required for a outdoor unit However in order to maximize reliability and performance the following best practic...

Страница 7: ...ed when installed on a concrete pad or the ground to allow drainage to occur If the heat pump unit is installed on wall mounting bracket insert the provided drain connector into one of the 1 inch 25 m...

Страница 8: ...en one of the flare nuts to release the factory nitrogen charge from the indoor units only 4 Remove the flare nuts from the connections on the unit and discard the seal from each of the piping connect...

Страница 9: ...refer to the installation instruction included with the indoor unit for setup IMPORTANT Pipe and wire to each zone separately Test each indoor unit separately to ensure proper operation Connecting Mul...

Страница 10: ...MPB 49 ft 15 m NOTE Minimum Line Set Length 10 ft 3 m per Indoor Unit Outdoor Unit Model No MPA018S4M P MPB018S4M P MLA018S4M P MPA030S4M P MPB030S4M P MLA030S4M P MPA036S4M P MPB036S4M P MLA036S4M P...

Страница 11: ...4 in x 1 2 in 2 018 A 1 1 4 in x 1 2 in 018 B 1 1 4 in x 1 2 in 3 009 A 1 4 in x 3 8 in 009 B 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 3 009 B 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 012 A 1 1 4 in x 1 2...

Страница 12: ...x 3 8 in 009 D 1 4 in x 3 8 in 012 B 1 1 4 in x 1 2 in 018 A 1 4 in x 1 2 in 4 009 D 1 4 in x 3 8 in 012 A 1 4 in x 1 2 in 012 B 1 1 4 in x 1 2 in 012 C 1 1 4 in x 1 2 in Table 4 Match Ups Outdoor Mod...

Страница 13: ...018 B 1 4 in x 1 2 in 018 C 1 1 4 in x 1 2 in 3 018 B 1 4 in x 1 2 in 018 C 1 1 4 in x 1 2 in 024 A 2 3 3 8 in x 5 8 in 4 009 A 1 1 4 in x 3 8 in 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 009 D 1...

Страница 14: ...atch Ups Outdoor Model No of Zones Indoor Unit Capacity Unit No Line Set Required Liquid x Gas MPA048S4M MPB048S4M Indoor Unit A 1 4 liq 1 2 gas Indoor Unit B 1 4 liq 1 2 gas Indoor Unit C 1 4 liq 3 8...

Страница 15: ...8 in 3 009 A 1 1 4 in x 3 8 in 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 3 009 B 1 1 4 in x 3 8 in 009 C 1 4 in x 3 8 in 012 A 1 4 in x 1 2 in Table 4 Match Ups Outdoor Model No of Zones Indoor U...

Страница 16: ...the following procedure to test for system leaks 1 Connect the manifold gauge set and dry nitrogen gas cylinder to the liquid and gas service ports 2 Open valve on nitrogen cylinder 3 Pressurize the...

Страница 17: ...lies before opening access panel Unit may have multiple power sources CAUTION All terminal connections must be made as illustrated in the following diagrams Improperly connected wiring could damage un...

Страница 18: ...230V Indoor Unit B From Power Supply Outdoor Unit Indoor Unit A Indoor Unit B Figure 21 Connection Diagram Systems 30k and Below To Indoor Unit C L2 1 A 3 A 2 A 208 230V Outdoor Unit Terminal Block Fr...

Страница 19: ...P SENSOR Figure 23 MPA018S4M P Outdoor Unit Wiring Diagram 6 6 6 YELLOW RED L PRO LOW PRESSURE SWITCH H PRO HIGH PRESSURE SWITCH 4 BLACK BLUE BROWN BLACK RED L2 BROWN BROWN BLUE BLUE BLACK BLACK 1 A 3...

Страница 20: ...SWITCH T3 T4 CRANKCASE HEATER DIODE MODULE SV L PFC INDUCTOR T5 MAIN BOARD OUTDOOR DC FAN 2 L 1 L XT1 T2B A B C D E CN13 E D B A INDOOR COIL OUTLET TEMP SENSOR C ELECTRONIC EXPANSION VALVE E CN30 CN2...

Страница 21: ...1 A 3 A L2 2 A L1 BLACK BLUE BROWN BLACK BLUE BROWN BLACK RED 1 B 2 B 3 B COMPRE SSOR DI SCHARG E TEMPER ATURE SENSOR Figure 27 MPB018S4M P Outdoor Unit Wiring Diagram HEAT1 SV HEAT2 WHITE WHITE 6 BLA...

Страница 22: ...EXV EXV HE AT_1 CR ANKCAS E HE ATE R Figure 29 MPB036S4M P Outdoor Unit Wiring Diagram DR IVER B OARD CODE PAR T NAME COMPR E S S OR D HE AT_1 CT1 AC CURRENT DETECTOR 4 WAY VALVE COMP E XV E LE CTR IC...

Страница 23: ...ESSOR DISCHARGE TEMP SENSOR INDUCTOR 2R0509A INDUCTOR 1R25027 Figure 31 MLA018S4M P Outdoor Unit Wiring Diagram HE AT _1 HE AT _2 CRANKCASE HEATER HEAT_1 HEAT_2 COMPRESSOR DISCHARGE TEMP SENSOR OUTDOO...

Страница 24: ...unit terminal strip The voltage must be within the range listed on the unit s nameplate If not do not start the equipment until you have consulted with the power company and the voltage condition has...

Отзывы: