background image

12

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

LENNOX HEARTH PRODUCTS  •  MERIT PLUS

®

 B-VENT GAS FIREPLACES (MPB33/35/40/45)  •  INSTALLATION INSTRUCTIONS

Turn on gas supply and test for gas leaks, using 

a gas leak test solution (also referred to as 

bubble leak solution). 

NOTE: 

Using a soapy water solution is 

an effective leak test solution but it is not 

recommended, because the soap residue 

that is left on the pipes/fittings can result in 

corrosion over time. 

A.

 Light the appliance (refer to the lighting 

instructions label in the control compartment 

or in the Care and Operation Instructions 

manual).

B. Brush all joints and connections with the gas 

leak test solution to check for leaks. If bubbles 

are formed, or gas odor is detected, turn the 

gas control knob (off/pilot/on) to the “OFF” 

position (millivolt units), or turn the receiver, 

remote control or control switch to the “OFF” 

position (electronic units). Either tighten or 

refasten the leaking connection, then retest as 

described above.

C. 

When the gas lines are tested and leak free, 

be sure to rinse off the leak testing solution.

6.

 If wall-mounted ON/OFF control is to be 

used, mount it in a convenient location on 

a wall near the fireplace.

7

.  If an optional control is to be used, wire it in 

the low voltage circuit as shown in 

Figure 

18

.

NOTE: 

The supplied 15 feet of 2 conductor wire 

has one end of each conductor connected to 

the gas valve circuit and the other end of each 

conductor placed loose inside the bottom 

compartment.

8

. After the wiring is complete, replace the 

cover plate.

BLOWER CONTROL CIRCUIT WIRING

120V, 60HZ, 1PH  

Factory Wired

Ground

Field Wired

Junction Box 

Tab Intact

Tab 

Broken

Plug blower

into this 

receptacle

ne

er

G - 

dn

uor

G

* Wall-mounted

ON/ OFF Blower 

Switch or Variable 

Speed Control Switch. 

Blower

eti

h

W - 

lar

tu

eN 120 VAC - Blac

k

Green

Ground

Screw

Whit

e

Gree

n

Neutral 

Side of

Receptacle

Hot

Side of

Receptacle

Red

Black

Figure 19 - Junction Box Wiring

       WARNING 

Electronic models of these appli-

ances are equipped with a three-

prong (grounding) plug utilized 

in connecting the electronic 

components to the junction box 

in the lower compartment. This 

grounding plug provides protec-

tion against shock hazard and 

should be plugged directly into 

the properly grounded three-

prong receptacle. DO NOT cut 

or remove the grounding prong 

from the plug.

STEP 6. CONNECTING GAS LINE 

Make gas line connections. All codes require a 

shut-off valve mounted in the supply line. The 

orientation of the shut-off valve should face the 

front (see 

Figure 22

).  

Figure 21

 illustrates two 

methods for connecting the gas supply. The flex-

line method is acceptable in the U.S.; however, 

Canadian requirements vary depending on 

locality. Installation must be in compliance 

with local codes. 

A sediment trap is recommended in the gas 

piping within the home to prevent moisture 

and debris in the line from damaging the valve.

These appliances are equipped with a gas flex 

line for use (where permitted) in connecting the 

unit to the gas line.  A gas flex line is provided 

to aid in attaching the direct vent appliance to 

the gas supply.  The gas flex line can only be 

used where local codes permit. Refer to 

Figure 

21

 for flex line description. The flex line is rated 

for both natural and propane gas. A manual 

shut off valve is also provided with the flex line.

The gas control valve is located in the lower 

control compartment. 

STEP 5. WIRING OPTIONAL FORCED 
AIR BLOWER KIT 

FBK-100, FBK-200, and FBK-250 Kits 

(see Figure 18)

An electrical outlet box is provided for the 

installation of the FBK-100, FBK-200 and FBK-

250 forced air blower kits. Electrical power 

must be provided to this box to operate these 

blowers. Install the blower kits according to the 

installation instructions provided with the kits.

NOTE: 

The tab connecting the two receptacles 

of the outlet box must be broken in the  

FBK-100 and FBK-200 blower kit applications 

(see 

Figure 19

).

To access the valve, open the control 

compartment access panel.  Actuate the spring 

loaded magnetic catches securing the panel. 

First, gently depress the upper right top corner 

of the panel until the magnet catch "pops" the 

door free. Then, gently pulling the panel forward, 

disengage the left magnet catch and allow the 

panel to swing down to open.

The control valves have a 3/8" (10 mm) NPT 

thread inlet and outlet side of the valve (refer to 

Figure 1 [Millivolt] and Figure 2 [Electronic] 

on Page 4)

.

Secure all joints tightly using appropriate 

tools and sealing compounds (ensure propane 

resistant compounds are used in propane 

applications). Optional: Seal around the gas 

line to prevent cold air leakage. Gas line holes 

and other openings can be caulked or stuffed 

with unfaced fiberglass insulation.

TEST ALL CONNECTIONS FOR GAS LEAKS 

(FACTORY AND FIELD)

     

WARNING

Never use an open flame to 

check for leaks.

Содержание MPB33CNE

Страница 1: ... SURFACE VITRÉE CHAUDE PEUT CAUSER DES BRÛLURES LAISSER REFROIDIR LA SURFACE VITRÉE AVANT D Y TOUCHER NE PERMETTEZ JAMAIS À UN ENFANT DE TOUCHER LA SURFACE VITRÉE EL VIDRIO CALIENTE CAUSARÁ QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NIÑOS DEBEN NUNCA TOCAR EL VIDRIO Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT ...

Страница 2: ...on 5 Vent Termination Clearances 5 Appliance and Vent Clearances 6 Pre Installation Steps 7 Typical Installation Sequence 7 Detailed Installation Steps 7 Step 1 Framing 7 Framing Specifications 8 Fireplace Specifications 9 Step 2 Routing Gas Line 9 Step 3 Installing Vent System 10 Step 4 Field Wiring 11 Step 5 Wiring Optional Forced Air Blower Kit 12 Step 6 Connecting Gas Line 12 Step 7 Installing...

Страница 3: ...nal Safety Standards and are tested and listed by OMNI Test Laboratories Inc Report No 116 F 36d 5 toANSIZ21 50b 2009 inCanada CSA 2 22b 2009 and CAN CGA 2 17 M91 R2009 in both USA and Canada as vented gas fireplaces Bothmillivoltandelectronicversionsofthese appliances may be used in bedrooms only when the room is an unconfined space as defined by the National Fuel Gas Code Use in bedrooms may not...

Страница 4: ...onin the US state of Massachusetts if the following additional requirements are met Install this appliance in accordance with Massachusetts Rules and Regulations 248 C M R Installation and repair must be done by a plumber or gas fitter licensed in the Com monwealth of Massachusetts The flexible gas line connector used shall not exceed 36 inches 92 centimeters in length The individual manual shut o...

Страница 5: ...d out of traffic and away from furniture and draperies Figure 3 En raison des températures élevées l appareil devrait être installé dans un endroit où il y a peu de circulation et loin du mobilier et des tentures Figure 3 The location should also be free of electrical plumbing or other heating air conditioning ducting Be aware that this is a heat producing ap pliance Objects placed above the unit ...

Страница 6: ... side of the fireplace may abutt a perpendicular wall For this type of installation the other side of the fireplace must be a flat wall to allow for proper air flow and burner operation Combustiblematerialsmayprojectbeyondone or both sides of the fireplace opening when these materials are kept within the Safe Zone illustrated in Figure 6 3 1 2 in 89mm Top View of Fireplace Combustiblematerials may...

Страница 7: ...abs one on each side located at the base of the fireplace and secure to the floor by nailing with 8d nails or equivalent see Figure 10 Anchor Tab Step 10 REMOVING AND Installing THE Glass Door Page 19 Step 11 Burner Adjustments Page 19 Adjust burner primary air shutter to achieve proper flame appearance Step 12 TESTING VENT OPERATION Page 21 Vent operation test and safety limit switch operation St...

Страница 8: ... Enclosure Including Finishing Materials if any Rough Framing Face Unfinished Shown o N l e d o M A t i n U e z i S A g n i m a r F e z i S B C D E F G H J K n i 5 3 8 1 5 3 4 1 5 3 4 1 9 1 8 5 9 1 7 5 2 1 4 3 8 2 6 1 4 6 1 9 6 8 5 0 4 m m 2 9 8 5 9 8 5 9 8 3 8 4 8 9 4 0 6 4 1 0 3 7 6 0 4 2 0 1 7 6 1 2 3 0 1 n i 8 1 0 4 4 1 0 4 4 1 0 4 4 2 8 5 4 2 6 1 3 1 1 6 6 1 1 0 3 6 1 4 6 1 9 6 2 3 1 1 3 4 m ...

Страница 9: ...lynoone unfamiliarandunqualifiedshouldattemptsizing or installing gas piping NOTES All appliances are factory equipped with a flexible gas line connector and 1 2 shutoff valve see Figure 21 on Page 13 Step 2 ROUTING Gas Line Routea1 2 13mm gaslineasshowninFigure 13 Gas lines must be routed constructed and made of materials that are in strict accordance withlocalcodesandregulations Theappliance as ...

Страница 10: ...rtical is used or 15 4 6 m when an offset is greater than 45 degrees and up to 60 degrees see Figure 17 The offset may start at the fireplace flue collar The maximum overall height of the vent system and appliance should not exceed 40 feet Install the B vent system in accordance with the vent manufacturer s instructions Required Pipe Diameter MPB33 series Requires 4 102 mm MPB35 series Requires 5 ...

Страница 11: ...TIONAL GROUND BATTERY HOLDER DFC WIRE HARNESS SPARK WIRE CABLE PILOT GROUND WIRE PILOT SENSOR CABLE HOOD IGNITER ROD FLAME SENSOR PILOT TUBE CPI SWITCH OFF O INTERMITTENT PILOT MODE ON STANDING PILOT MODE PROFLAME DFC BOARD PROFLAME VALVE ELECTRONIC PILOT ASSEMBLY B BLACK BR BROWN GY GRAY PU PURPLE R RED BL BLUE G GREEN O ORANGE W WHITE Y YELLOW WIRING COLOR CODE B B B R R W W B B B B BL BL G G O ...

Страница 12: ... the grounding prong from the plug Step 6 Connecting Gas Line Make gas line connections All codes require a shut off valve mounted in the supply line The orientation of the shut off valve should face the front see Figure 22 Figure 21 illustrates two methodsforconnectingthegassupply Theflex line method is acceptable in the U S however Canadian requirements vary depending on locality Installation mu...

Страница 13: ... DONOTterminatetheductcloserthan3 below the chimney top Outside supplemental combustion air ducting may be run upwards or vertically through framing and ceiling joists with the hood installed through an outside wall and 3 1 m belowthetermination Ductingmayalsoberun downward through floor joists and under the hometoaventilatedcrawlspacenotconsidered part of the living area of the home Outside Air C...

Страница 14: ... for MPB35 Series appliances and Figure 30 for MPB40 and MPB45 Series appliances NOTE Turn off all electricity to the appliance before you install volcanic stone embers and logs The flame should project 1 25 mm beyond the hood at all three ports see Figure 24 Replace logs if removed for pilot inspection To light the burner turn ON the remote wall switch and rotate the gas valve control knob counte...

Страница 15: ...nt door see Removing the Glass Enclosure Panel on Page 19 Step 2 Install decorative volcanic stone Sprinkle the decorative volcanic stone in a pleasing pattern The volcanic stone should be placed directly on top of the firebox bottom along the front and to the back at the right and left sides of the burner Position any optional ceramic fiber liners before placing the stone Logs should be positione...

Страница 16: ...upper end Place the left log and then the smaller left and right top logs All logs that have notches to fit over the grate tines should be positioned with these notches directly against the grate All top logs that rest on lower logs do so over flattened mounting faces in the bottom logs Properlogandtwigplacementiscriticaltoencourageoutstanding flame appearance and prevent sooting 3 2 4 5 6 1 2 3 4...

Страница 17: ... placed in the order shown Position the rear log on the brackets at the rear of the firebox with the log s notches directly over the brackets Position the right log log no 3 by inserting the pin from the rear log into the hole on its upper end Place the left log and then the smaller left and right top logs All logs that have notches to fit over the grate tines should be positioned with these notch...

Страница 18: ...ion the individual logs as shown below Logs should be placed in the order shown Position the center log on the burner first then place the glowing embers as shown in Figure 27 Place the rear log both the right and left and then the smaller left and right top logs All logs that have notches to fit over the grate tines should be positioned with these notches directly against the grate All top logs t...

Страница 19: ...t appear sooty NOTE Thefollowingchartisprovidedtoaidyou in achieving the correct air shutter adjustment for your installation Removing the Glass Enclosure Panel see Figure 31 Removethetoplouverassembly Openthelower control compartment door see Figure 22 on Page 13 by pressing in simultaneously at the left and right top corners of the door the door is hinged at the bottom Remove the bottom compartm...

Страница 20: ...position 1 Refer to Figures 32 33 and 34 for proper flame appearance To adjust the flame refer to Figure 35 and move the rod up and down the adjustment rod is located in the lower control area Position the air shutter to the factory setting as shown in Table 8 2 Light appliance follow lighting procedure on lighting label in control compartment or in the Care and Operation Instructions 3 Allow the ...

Страница 21: ...ure 37 for its location If during appliance operation the flame goes out independently of the burner on off wall switch it may be due to a blocked vent If this condition occurs the safety limit switch will activate causing the fireplace burner to shut off To reset the safety limit switch perform the following steps NOTE Allow the appliance to cool completely 7 Remove the top louver panel 8 Reset t...

Страница 22: ...de est utilisée pour contrôler le foyer nettoyez la soigneusement pour éliminer la poussière et les traces de graisse ou d huile Collez l étiquette sur le boîtier de la télécommande Figure B Choisissez la langue qui est principale ment parlée dans la résidence du propriétaire En cas de doute collez l étiquette en anglais 3 Si vous ne trouvez pas les étiquettes veuillez appeler Lennox Hearth Produc...

Страница 23: ...sembly C Remove the burner assembly with attached venturi tube Millivolt and Electronic Ignition System Appliances Step 1 SIT Systems Refer to Figure 38 and the instructions provided with the SIT Regu lator Conversion Kit Using a Torx T20 driver to remove and discard the pressure regulator mounting screws two screws for electronic models three screws for millivolt models pressure regulator tower t...

Страница 24: ...y proper burner ignition and operation See Burner Adjustments and Burner Flame Appearance on Pages 19 and 20 Step 12 Inspect the pilot system for proper flame The pilot flame should engulf the flame sensor as shown in Figures 24 and 25 on Page 14 Step 13 Using a manometer test the inlet and manifold gas pressures see Tables 2 and 3 on Page 4 ALWAYS TEST PRESSURES WITH THE VALVE REGULATOR CONTROL A...

Отзывы: