MANUAL MAIN

SHUT-OFF VALVE

WILL NOT HOLD

NORMAL TEST

PRESSURE

CAP

ISOLATE

GAS VALVE

FURNACE

1/8 NPT PLUG

FIGURE 19 

When  checking  piping  connections  for  gas  leaks,  use 

preferred means. Kitchen detergents can cause harmful 

corrosion on various metals used in gas piping. Use of a 

specialty Gas Leak Detector is strongly recommended. It 

is available through Lennox under part number 31B2001. 

See Corp. 8411-L10, for further details.
Do not use matches, candles, flame or any other source of 

ignition to check for gas leaks.

D- Gas Pressure Adjustment
Gas Flow (Approximate)

TABLE 10 

GAS METER CLOCKING CHART

Unit

Seconds For One Revolution

Natuarl

LP/Propane

1 cu ft 

Dial

2 cu ft 

Dial

1 cu ft 

Dial

2 cu ft 

Dial

-045

80

160

200

400

-070

55

110

136

272

-090

41

82

102

204

-110

33

66

82

164

-135

27

54

68

136

Natural-1000 btu/cu ft  LP-2500 btu/cu ft

Furnace should operate at least 5 minutes before check

-

ing gas flow. Determine time in seconds for two revolu

-

tions of gas through the meter. (Two revolutions assures a 

more accurate time.) Divide by two and compare to time in 

table 10. If manifold pressure matches table 12 and rate is 

incorrect, check gas orifices for proper size and restriction. 

Remove temporary gas meter if installed.

NOTE - 

To obtain accurate reading, shut off all other gas 

appliances connected to meter.

E- Supply and Manifold Pressure
Supply Pressure Measurement

1 - 

 Remove  the  threaded  plug  from  the  inlet  side  of 

the  gas  valve  and  install  a  field-provided  barbed 

fitting. Connect to a test gauge to measure supply 

pressure.

2 - 

 

Start  unit  and  allow  5  minutes  for  unit  to  reach 

steady state.

3 -   After allowing unit to stabilize for 5 minutes, record 

supply  pressure  and  compare  to  value  given  in 

table 12.

Manifold Pressure Measurement

1 - 

 Remove the threaded plug from the outlet side of 

the  gas  valve  and  install  a  field-provided  barbed 

fitting. Connect to a test gauge to measure manifold 

pressure.

2 -   Start  unit  and  allow  5  minutes  for  unit  to  reach 

steady state.

3 -   While waiting for the unit to stabilize, observe the 

flame.  Flame  should  be  stable  and  should  not  lift 

from burner. Natural gas should burn blue.

4 -   After allowing unit to stabilize for 5 minutes, record 

manifold  pressure  and  compare  to  value  given  in 

table 12.

NOTE - 

Shut  unit  off  and  remove  manometer  as 

soon as an accurate reading has been obtained. 

Take  care  to  remove  barbed  fitting  and  replace 

threaded plug.

F- Proper Combustion

Furnace should operate a minimum 15 minutes with cor

-

rect manifold pressure and gas flow rate before checking 

combustion. Take combustion sample beyond the flue out

-

let and compare to the table below. 

The maximum car-

bon monoxide reading should not exceed 100 ppm.

TABLE 11 

ML180DFE Unit

CO

2

% Nat

CO

2

% LP

-045

6.8 - 7.4

7.5 - 9.0

-070
-090

-110

G- High Altitude

The manifold pressure may require adjustment and com

-

bustion air pressure switch may need replacing to ensure 

proper combustion at higher altitudes. Refer to table 12 

for  manifold  pressure  and  table  13  for  pressure  switch 

change and gas conversion kits.

 IMPORTANT

For safety, shut unit off and remove manometer as 

soon as an accurate reading has been obtained. 

Take care to replace pressure tap plug

.

Содержание ML180DF045E36A

Страница 1: ...LP Propane operation ML180DFE model units are equipped with a hot surface ignition system and a constant torque ECM motor The motor is programmed to provide constant torque at each of the five select...

Страница 2: ...Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations Isolated combustion system rating for non weatherized furnaces SPECIFICATIONS Gas Heating Performance Mode...

Страница 3: ...s cfm Watts cfm Watts 0 00 1430 285 1215 180 1035 120 995 110 930 100 0 10 1400 285 1175 185 995 130 885 100 850 90 0 20 1375 300 1145 200 950 140 840 110 725 85 0 30 1335 315 1120 210 915 145 790 115...

Страница 4: ...1195 130 0 10 1725 390 1495 270 1390 220 1320 195 1145 140 0 20 1695 405 1470 285 1340 235 1280 210 1105 145 0 30 1660 415 1425 300 1290 240 1225 215 1040 160 0 40 1615 430 1395 310 1250 255 1185 230...

Страница 5: ...Box includes integrated control interlock switch and transformer Gas Valve Burner Box includes sensor ignitor and rollout switches Combustion Air Inducer Blower Access Panel Heating Compartment Acces...

Страница 6: ...t if repair is attempted The hot surface ignition control system consisting of an integrated control figure 3 with control terminal designa tions in tables 1 2 and 3 sensor and ignitor figure 6 The in...

Страница 7: ...lve Out TABLE 3 1 4 Quick Connect Terminals 120HUM Humidifier 120VAC LINE 120VAC XFMR Transformer 120VAC CIRC Indoor blower 120VAC EAC Indoor air quality accessory 120VAC NEUTRALS Common 120VAC HUM24...

Страница 8: ...Switch Open 9 Pressure Switch failed to close or opened during heat demand 10 Watchguard Pressure Switch opened 5 times during one heat demand 11 Pressure Switch stuck closed prior to activation of c...

Страница 9: ...llout Switch Open 9 Pressure Switch failed to close or opened during heat demand 10 Watchguard Pressure Switch opened 5 times during one heat demand 11 Pressure Switch stuck closed prior to activation...

Страница 10: ...s2 Pressure Switch failed to close or opened during heat demand inducer on 10 Flashes2 Watchguard Pressure switch opened 5 times during a single heating demand 11 Flashes2 Pressure switch stuck closed...

Страница 11: ...zed Longer delay times allow for lower air tempera ture shorter delay times allow for higher air temperature See figure 5 Cooling Fan On Time The fan on time is 2 seconds and is not adjustable Cooling...

Страница 12: ...thin three minutes or SureLight control will go into Watchguard for one hour The switch is factory set and cannot be adjusted The switch may have a different setpoint for each unit model number If lim...

Страница 13: ...ire from Integrated Control and Connect Alligator Clip to Flame Sensor Lead Flame Sensor Terminal Remove Sensor Wire from Integrated Control and Connect Alligator Clip to Terminal on Control DIGITAL M...

Страница 14: ...needed If the reading on the meter is not correct 0 or infinity then a second test is needed Test 2 Check ignitor for correct resistance Seperate the 2 pin jack plug near the manifold and check resist...

Страница 15: ...ducer Pressure Switch S18 Units are equipped with a combustion air pressure switch located on the combustion air inducer orifice bracket The switch is connected to the combustion air inducer housing b...

Страница 16: ...resent in tests 1 and 2 and motor is not operating properly replace motor The motor is not field repairable If replacing the indoor blower motor or blower wheel is necessary placement is critical The...

Страница 17: ...peed tap used for continuous fan 1 2 3 4 or 5 on input plug P49 If 24 volts is not present problem may be up stream of plug P49 Proceed to test 4 Multi Meter set to VAC 12 0 12 0 24 Multi Meter set to...

Страница 18: ...ximately the same resistance within an ohm 3 Check to see if the blower wheel spins freely Motor Test FIGURE 16 TABLE 9 Scale Measurement range in words ohms 2 M two megohm two million ohms 0 2 000 00...

Страница 19: ...to be performed 3 Remove the upper access panel 4 Move gas valve switch to OFF position Do not force See figure 18 5 Replace the upper access panel B Safety or Emergency Shutdown Disconnect main powe...

Страница 20: ...itting Connect to a test gauge to measure supply pressure 2 Start unit and allow 5 minutes for unit to reach steady state 3 After allowing unit to stabilize for 5 minutes record supply pressure and co...

Страница 21: ...opane 10 0 10 0 10 0 11 0 13 0 TABLE 13 Pressure Switch and Gas Conversion Kits at all Altitudes Model Input Size High Altitude Pressure Switch Kit High Altitude Natuarl Gas Orifice Kit LP Propane Ori...

Страница 22: ...132 Vac NOTE Figures 21 and 22 are typical ignition control illustrations CHECK VOLTAGE BETWEEN LINE NEUTRAL AND LOW VOLTAGE C TERMINAL FIGURE 20 TABLE 14 Furnace Status Measurement VAC Expected Maxi...

Страница 23: ...5 W C For cooling speed external static pressure drop must not be more than 0 8 W C 4 Seal the hole when the check is complete EXTERNAL STATIC PRESSURE Supply Duct Static Return Duct Static Total Duct...

Страница 24: ...rovide combustion air 10 Inspect the furnace venting system to make sure it is in place structurally sound and without holes corrosion or blockage Vent system must be free and clear of obstructions an...

Страница 25: ...manifold assembly to the vestibule panel and remove the assembly from the unit 7 Remove screws from both sides top and bottom of vestibule panel 8 Remove heat exchanger It may be necessary to spread c...

Страница 26: ...burner box cover 15 Reconnect all wires 16 Reconnect top cap and vent pipe to combustion air inducer outlet 17 Reconnect gas supply piping 18 Turn on power and gas supply to unit 19 Set thermostat and...

Страница 27: ...e found to be closed Call for heat can continue 5 A92 integrated control energizes B6 combustion air inducer S18 combustion air pressure switch closes Once S18 closes a 15 second pre purge follows 6 A...

Страница 28: ...OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED FLASHES CODE 11 PRESSURE SWITCH CLOSED GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY Sequence holds until press...

Страница 29: ...NCE FOUR TIMES FLAME SIGNAL 1 5 MICROAMPS OR GREATER YES YES YES ROLLOUT SWITCH CLOSED LED FLASHES CODE 8 ROLLOT SWITCH OPEN GAS VALVE POWER OFF COMBUSTION AIR INDUCER POWER ON INDOOR BLOWER ON SEQUEN...

Страница 30: ...SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZED COMPRESSOR O...

Страница 31: ...D EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G ENERGIZES SYSTEM FAN AT FAN SPEED EAC TERM ENERGIZED NO YES YES NO SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30 S...

Отзывы: