II- PLACEMENT AND INSTALLATION

Make sure unit is installed in accordance with installation 

instructions and applicable codes.

III- START-UP
A- Heating Start-Up

 WARNING

Shock and burn hazard.

ML180UDFE units are equipped with a hot surface 

ignition system. Do not attempt to light manually.

GAS VALVE SHOWN IN ON POSITION

MANIFOLD

PRESSURE

OUTLET

PORT

INLET

PRESSURE

PORT

MANIFOLD

PRESSURE

ADJUSTMENT

SCREW

FIGURE 18 

1 - 

STOP! 

Read the safety information at the beginning 

of this section.

2 -   Set the thermostat to the lowest setting.
3 -   Turn off all electrical power to the unit.
4 -   This  furnace  is  equipped  with  an  ignition  device 

which automatically lights the burners. Do not try to 

light the burners by hand.

5 -   Remove the upper access panel.
6 -   Move  gas  valve  switch  to  OFF  position.  Do  not 

force. See figure 18.

7 -   Wait five minutes to clear out any gas. If you then 

smell gas, STOP! Immediately call your gas supplier 

from a neighbor’s phone. Follow the gas supplier’s 

instructions. If you do not smell gas go to next step.

8 - 

 Move gas valve switch to ON position. Do not force. 

See figure 18.

9 -   Replace the upper access panel.

10 - 

 Turn on all electrical power to to the unit.

11 - 

 Set the thermostat to desired setting.

NOTE - 

When unit is initially started, steps 1 through 

11 may need to be repeated to purge air from gas 

line.

12 -  If  the  appliance  will  not  operate,  follow  the 

instructions “Turning Off Gas to Unit” and call the 

gas supplier.

Turning Off Gas to Unit

1 - 

 Set the thermostat to the lowest setting.

2 -   Turn off all electrical power to the unit if service is to 

be performed.

3 -   Remove the upper access panel.
4 -   Move  gas  valve  switch  to  OFF  position.  Do  not 

force. See figure 18.

5 -   Replace the upper access panel.

B- Safety or Emergency Shutdown

Disconnect main power to unit. Close manual and main 

gas valves.

C- Extended Period Shutdown

Turn off thermostat or set to “UNOCCUPIED” mode. Close 

all gas valves (both internal and external to unit) to guar

-

antee  no  gas  leaks  into  combustion  chamber.  Turn  off 

power  to  unit. All  access  panels  and  covers  must  be  in 

place and secured.

IV-HEATING SYSTEM SERVICE CHECKS

A- C.S.A. Certification

All units are C.S.A. design certified without modifications. 

Refer to the ML180DFE Installation Instruction.

B- Gas Piping

Gas supply piping should not allow more than 0.5”W.C. 

drop in pressure between gas meter and unit. Supply gas 

pipe must not be smaller than unit gas connection. Com

-

pounds used on gas piping threaded joints should be re

-

sistant to action of liquefied petroleum gases.

C- Testing Gas Piping

 CAUTION

If a flexible gas connector is required or allowed by 

the authority that has jurisdiction, black iron pipe 

shall be installed at the gas valve and extend outside 

the furnace cabinet.

 IMPORTANT

In case emergency shutdown is required, turn off the 

main shut-off valve and disconnect the main power 

to unit. These controls should be properly labeled 

by the installer.

 WARNING

Do not exceed 600 in-lbs (50 ft-lbs) torque when 

attaching the gas piping to the gas valve.

When pressure testing gas lines, the gas valve must be 

disconnected and isolated. Gas valves can be damaged if 

subjected to more than 0.5psig (14” W.C.). See figure 19. 

If the pressure is equal to or less than 0.5psig (14”W.C.), 

close the manual shut-off valve before pressure testing to 

isolate furnace from gas supply.

Содержание ML180DF045E36A

Страница 1: ...LP Propane operation ML180DFE model units are equipped with a hot surface ignition system and a constant torque ECM motor The motor is programmed to provide constant torque at each of the five select...

Страница 2: ...Utilization Efficiency based on DOE test procedures and according to FTC labeling regulations Isolated combustion system rating for non weatherized furnaces SPECIFICATIONS Gas Heating Performance Mode...

Страница 3: ...s cfm Watts cfm Watts 0 00 1430 285 1215 180 1035 120 995 110 930 100 0 10 1400 285 1175 185 995 130 885 100 850 90 0 20 1375 300 1145 200 950 140 840 110 725 85 0 30 1335 315 1120 210 915 145 790 115...

Страница 4: ...1195 130 0 10 1725 390 1495 270 1390 220 1320 195 1145 140 0 20 1695 405 1470 285 1340 235 1280 210 1105 145 0 30 1660 415 1425 300 1290 240 1225 215 1040 160 0 40 1615 430 1395 310 1250 255 1185 230...

Страница 5: ...Box includes integrated control interlock switch and transformer Gas Valve Burner Box includes sensor ignitor and rollout switches Combustion Air Inducer Blower Access Panel Heating Compartment Acces...

Страница 6: ...t if repair is attempted The hot surface ignition control system consisting of an integrated control figure 3 with control terminal designa tions in tables 1 2 and 3 sensor and ignitor figure 6 The in...

Страница 7: ...lve Out TABLE 3 1 4 Quick Connect Terminals 120HUM Humidifier 120VAC LINE 120VAC XFMR Transformer 120VAC CIRC Indoor blower 120VAC EAC Indoor air quality accessory 120VAC NEUTRALS Common 120VAC HUM24...

Страница 8: ...Switch Open 9 Pressure Switch failed to close or opened during heat demand 10 Watchguard Pressure Switch opened 5 times during one heat demand 11 Pressure Switch stuck closed prior to activation of c...

Страница 9: ...llout Switch Open 9 Pressure Switch failed to close or opened during heat demand 10 Watchguard Pressure Switch opened 5 times during one heat demand 11 Pressure Switch stuck closed prior to activation...

Страница 10: ...s2 Pressure Switch failed to close or opened during heat demand inducer on 10 Flashes2 Watchguard Pressure switch opened 5 times during a single heating demand 11 Flashes2 Pressure switch stuck closed...

Страница 11: ...zed Longer delay times allow for lower air tempera ture shorter delay times allow for higher air temperature See figure 5 Cooling Fan On Time The fan on time is 2 seconds and is not adjustable Cooling...

Страница 12: ...thin three minutes or SureLight control will go into Watchguard for one hour The switch is factory set and cannot be adjusted The switch may have a different setpoint for each unit model number If lim...

Страница 13: ...ire from Integrated Control and Connect Alligator Clip to Flame Sensor Lead Flame Sensor Terminal Remove Sensor Wire from Integrated Control and Connect Alligator Clip to Terminal on Control DIGITAL M...

Страница 14: ...needed If the reading on the meter is not correct 0 or infinity then a second test is needed Test 2 Check ignitor for correct resistance Seperate the 2 pin jack plug near the manifold and check resist...

Страница 15: ...ducer Pressure Switch S18 Units are equipped with a combustion air pressure switch located on the combustion air inducer orifice bracket The switch is connected to the combustion air inducer housing b...

Страница 16: ...resent in tests 1 and 2 and motor is not operating properly replace motor The motor is not field repairable If replacing the indoor blower motor or blower wheel is necessary placement is critical The...

Страница 17: ...peed tap used for continuous fan 1 2 3 4 or 5 on input plug P49 If 24 volts is not present problem may be up stream of plug P49 Proceed to test 4 Multi Meter set to VAC 12 0 12 0 24 Multi Meter set to...

Страница 18: ...ximately the same resistance within an ohm 3 Check to see if the blower wheel spins freely Motor Test FIGURE 16 TABLE 9 Scale Measurement range in words ohms 2 M two megohm two million ohms 0 2 000 00...

Страница 19: ...to be performed 3 Remove the upper access panel 4 Move gas valve switch to OFF position Do not force See figure 18 5 Replace the upper access panel B Safety or Emergency Shutdown Disconnect main powe...

Страница 20: ...itting Connect to a test gauge to measure supply pressure 2 Start unit and allow 5 minutes for unit to reach steady state 3 After allowing unit to stabilize for 5 minutes record supply pressure and co...

Страница 21: ...opane 10 0 10 0 10 0 11 0 13 0 TABLE 13 Pressure Switch and Gas Conversion Kits at all Altitudes Model Input Size High Altitude Pressure Switch Kit High Altitude Natuarl Gas Orifice Kit LP Propane Ori...

Страница 22: ...132 Vac NOTE Figures 21 and 22 are typical ignition control illustrations CHECK VOLTAGE BETWEEN LINE NEUTRAL AND LOW VOLTAGE C TERMINAL FIGURE 20 TABLE 14 Furnace Status Measurement VAC Expected Maxi...

Страница 23: ...5 W C For cooling speed external static pressure drop must not be more than 0 8 W C 4 Seal the hole when the check is complete EXTERNAL STATIC PRESSURE Supply Duct Static Return Duct Static Total Duct...

Страница 24: ...rovide combustion air 10 Inspect the furnace venting system to make sure it is in place structurally sound and without holes corrosion or blockage Vent system must be free and clear of obstructions an...

Страница 25: ...manifold assembly to the vestibule panel and remove the assembly from the unit 7 Remove screws from both sides top and bottom of vestibule panel 8 Remove heat exchanger It may be necessary to spread c...

Страница 26: ...burner box cover 15 Reconnect all wires 16 Reconnect top cap and vent pipe to combustion air inducer outlet 17 Reconnect gas supply piping 18 Turn on power and gas supply to unit 19 Set thermostat and...

Страница 27: ...e found to be closed Call for heat can continue 5 A92 integrated control energizes B6 combustion air inducer S18 combustion air pressure switch closes Once S18 closes a 15 second pre purge follows 6 A...

Страница 28: ...OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER ON HEATING SPEED LED FLASHES CODE 11 PRESSURE SWITCH CLOSED GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF WITH DELAY Sequence holds until press...

Страница 29: ...NCE FOUR TIMES FLAME SIGNAL 1 5 MICROAMPS OR GREATER YES YES YES ROLLOUT SWITCH CLOSED LED FLASHES CODE 8 ROLLOT SWITCH OPEN GAS VALVE POWER OFF COMBUSTION AIR INDUCER POWER ON INDOOR BLOWER ON SEQUEN...

Страница 30: ...SLOW FLASH RATE REMAINS UNCHANGED THROUGHOUT COOLING CYCLE THERMOSTAT CALLS FOR COOLING COMPRESSOR CONTACTOR AND SYSTEM FAN ENERGIZED WITH 2 SECOND DELAY COOLING SPEED EAC TERM ENERGIZED COMPRESSOR O...

Страница 31: ...D EAC TERM REMAINS ON THERMOSTAT OPENS MANUAL FAN SELECTION MADE AT THERMOSTAT CONTROL G ENERGIZES SYSTEM FAN AT FAN SPEED EAC TERM ENERGIZED NO YES YES NO SYSTEM FAN SWITCHES TO HEAT SPEAD AFTER 30 S...

Отзывы: