NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Figure 13

Step 3. INSTALL THE VENT SYSTEM

General Information

These instructions should be used as a guide-
line and do not supersede local codes in any
way. Install vent according to local codes,
these instructions, the current National Fuel
Gas Code (ANSI-Z223.1) in the USA or the
current standards of CAN/CGA-B149.1 and -
B149.2 in Canada.

These fireplaces are designed, tested
and listed for operation and installation
with, and only with, Secure Vent
™   Direct
Vent System Components, Secure Flex

Flexible Vent Components manufactured
by Security Chimneys International and
Z-FLEX
™  Model GA Venting Systems
listed to UL1777 and ULCS635 manufac-
tured by Flexmaster Canada Limited.
These approved vent system components
are labeled for identification. 

 DO NOT

use any other manufacturer's vent com-
ponents with these appliances.

These fireplaces must be vented directly
to the outside.

Determine the venting for the appliance.  If the
vent run will include at least 8 feet of vertical
rise, then install the  second restrictor in the
appliance collar before connecting any vent
(Refer to 

Figure 12 ).  Place the second restric-

tor inside the fixed restrictor.

Note:  The second restrictor is included within
the firebox.

The vent system may not service multiple
appliances, and must never be connected to a
flue serving a solid fuel burning appliance. The
vent pipe is tested to be run inside an enclos-
ing wall (such as a chase). There is no require-
ment for inspection openings in the enclosing
wall at any of the joints in the vent pipe.

Select Venting System - Horizontal or Vertical

With the appliance secured in framing, deter-
mine vent routing and identify the exterior
termination location. The following sections
describe vertical (roof) and horizontal (exterior
wall) vent applications. Refer to the section
relating to your installation. A list of approved
venting components is shown in the tables on
page 26.

VERTICAL TERMINATION SYSTEMS (ROOF)

Figures 13, 17 and 23 through 25 on pages
12, 14 and 15
 and their associated Vertical
Vent Tables illustrate the various vertical vent-
ing configurations that are possible for use
with these appliances.  Secure Vent pipe ap-
plications are shown in these figures; Secure
Flex
 pipe may also be used.

A Vertical Vent Table summarizes each system’s
minimum and maximum vertical and horizontal
length values that can be used to design and
install the vent components in a variety of
applications.

Both these vertical vent systems terminate
through the roof. The minimum vent height
above the roof and/or adjacent walls is speci-
fied in ANSI Z223.1-(latest edition) (In Canada,
the current CAN-1 B149 installation code) by
major building codes. Always consult your
local codes for specific requirements. A gen-
eral guide to follow is the Gas Vent Rule (refer
to 

Figure 4 on page 6 ).

Vertical (Straight) Installation

Determine the number of straight vent sec-
tions required. 4-1/2" (114 mm), 10-1/2" (267
mm), 22-1/2" (572 mm), 34-1/2" (876 mm)
and 461/2" (1181 mm) net section lengths
are available. Plan the vent lengths so that a
joint does not occur at the intersection of
ceiling or roof joists.  Refer to the Vent
Section Length Chart.

Figure 12

Exhaust Vent

Fixed Restrictor

Second Restrictor (For Vertical Vent Only)

SV4.5CGV-1

Termination

SV4.5FA OR
SV4.5FB Flashing
AND SV4.5SC
STORM COLLAR

*SV4.5VF
Firestop/Spacer

SV4.5L6/12/24/36/48
Vent Sections

40' Max.
(12.2 M)

6' Min.

(1.8 M)

1" (25.4 mm)
Minimum
Clearance to
Combustibles

*When using Secure Flex,

use Firestop/Spacer

SF4.5VF

Vertical (Offset) Installation

Analyze the vent routing and determine the
quantities of vent sections and number of
elbows required. Refer to Vertical Vent Fig-
ures and Tables on page 14 and 15
 to select
the type of vertical installation desired. Vent
sections are available in net lengths of 4-1/2"
(114 mm), 10-1/2" (267 mm), 22-1/2" (572
mm), 34-1/2" (876 mm) and 46-1/2" (1181
mm). Refer to the Vent Section Length Chart
on page 11
 for an aid in selecting length
combinations. Elbows are available in 90

°

 and

45

°

 configurations. Refer to 

Figure 18 for the

SV4.5E45 and SV4.5E90 elbow dimensional
specifications.

Содержание Merit Plus MPLDV-30NE

Страница 1: ...nes se trouvant dans le batiment o vous vous trouvez Evacuez la pi ce le b timent ou la zone Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si v...

Страница 2: ...the bottom compartment 4 One vent restrictor to be used as detailed on page 10 5 One hood and one control compartment cover and one 45 degree starter elbow are strapped to the top of the unit GENERAL...

Страница 3: ...ove 4500 ft For elevations above 4500 feet 1372 meters install the unit according to the regulations of the local authorities having jurisdictionand intheUSA thelatestedition of the National Fuel Gas...

Страница 4: ...m 6 2 6 1 n i 4 6 T N E V m m 4 5 2 n i 1 S E C N A R A E L C E C I V R E S T N O R F s r e t e m 9 0 t e e F 3 Shelf Height see table Do not insulate the space between the appliance and the area abo...

Страница 5: ...nwealth of Massachusetts hori zontal terminations installed less than seven 7 feet above the finished grade must comply with the following additional requirements A hard wired carbon monoxide detector...

Страница 6: ...b Electronic Appliances Connect 120 Vac electrical power to the appliance receptacle Step 5 page 22 Make connection to gas supply Step 6 page 23 Install the logs and glow ing embers Step7 page23 Chec...

Страница 7: ...o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e...

Страница 8: ...1 1 8 0 7 1 7 0 2 1 2 9 4 4 5 8 Note Venting requirements for corner installations the horizontal vent length a to b must not exceed 28 inches 711 mm Inches millimeters These dimensions occur when one...

Страница 9: ...1 3 5 9 4 3 5 3 1 6 8 6 7 2 0 5 1 5 2 2 9 6 5 3 V D L P M n i 2 1 0 4 2 1 7 3 8 5 0 2 8 1 9 2 4 1 5 3 4 3 4 2 8 3 2 1 4 1 7 2 m m 9 2 0 1 3 5 9 4 3 5 0 4 7 5 9 8 9 2 6 4 1 3 2 9 6 0 4 V D L P M n i 2...

Страница 10: ...SYSTEMS ROOF Figures 13 17 and 23 through 25 on pages 12 14 and 15 and their associated Vertical Vent Tables illustrate the various vertical vent ing configurations that are possible for use with the...

Страница 11: ...6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1 1 0 0 6 0 7 5 7 1 2 5 2 1 8 1 0 1 0 6 0...

Страница 12: ...r to Figure 15 Push the vent component against the starter elbow until it fully engages then twist the component clockwise running the dimples down and along the incline channels until they seat at th...

Страница 13: ...5 and SV4 5E90 elbows in the same manner as the straight vent sections The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with...

Страница 14: ...10 15 4 572 3 0 914 20 6 096 4 1 219 V H 40 feet 12 2 m Max H 20 feet 6 096 meters Max meters 40 feet 12 2 meters Maximum Ceiling Firestop Spacer SV4 5VF When using Secure Flex use Firestop Spacer SF4...

Страница 15: ...es covered in this document are fittedwithcollarshavinglockinginclinedchan nels The dimpled end of the vent components fit over the appliance collar to create the posi tive twist lock connection C Pla...

Страница 16: ...ot run ratios that are smallerareacceptableallthewaydowntoator near level Use a carpenter s level to measure fromaconstantsurfaceandadjustthesupport straps as necessary It is important to maintain the...

Страница 17: ...coping vent section elbow as shown in Figure 27 in the same manner as any SV4 5 vent component refer to Step F N Install Firestop Spacer at exterior wall When using the square termination install the...

Страница 18: ...c s e l e T d n a t i K n o i t a n i m r e T n i 2 1 7 o t 2 A L 5 4 V S n o i t c e S 6 L 5 4 V S n o i t c e s t n e v n i 6 2 0 5 o t 9 7 2 4 3 9 1 o t 1 1 Note SV4 5VF Secure Vent SF4 5VF Secure...

Страница 19: ...p Spacer SV4 5HF or SF4 5HF when using Secure Vent or Secure Flex respectively Use Firestop Spacer SV4 5HF5 or SF4 5HF5 when using Secure Vent or Secure Flex on horizontal vent runs for the MPLDV35 40...

Страница 20: ...rapper surface In all cases the firestop spacer provided with the termination may be used with the termination frame to 5 clearance where applicable HORIZONTAL VENT FIGURES TABLES CONTINUED Figure 33...

Страница 21: ...ex Pipe 1 Installthesmall gearclamplooselyaroundthe innerflexibleventpipe pushitbackoutoftheway 2 Apply a bead of Mill Pac Black 700 F high temperature sealant Catalog No 10K81 to the inner adapter co...

Страница 22: ...the appliance junction box 2 Remove the electrical inlet cover plate from the side of the unit by removing the plate s securing screws See Figure 11 on page 9 3 Removethe coverplate sknockoutandthen f...

Страница 23: ...rd pipe and tighten with wrenches from above through the firebox opening If required access the valve by removing the lower control compartment panel see Figure 39 by lifting and pulling the panel for...

Страница 24: ...4 as shown in Figure 39 Refer to Figure 43 and loosen the set screw for the venturi air shutter Manually actuate the air shutter through several cycles Set the air shutter to 3 32 before placing the...

Страница 25: ...R SHUTTER MOVES WHEN THE LEVER ARM IS OPERATED Note When first operating the air shutter adjustment lever arm observe the air shutter If it is not moving open the glass ensure the air shutter screw is...

Страница 26: ...8 203 MANTEL 6 152 MANTEL 4 102 MANTEL 18 457 14 356 12 305 2 51 MANTEL TOP OF APPLIANCE 8 203 10 254 MANTEL CLEARANCES Inches mm 16 406 Figure 45 COLD CLIMATE INSULATION For cold climate installatio...

Страница 27: ...S x e l F f o m m 4 1 9 n i 6 3 x e l F d e s s e r p m o c 8 0 L 4 9 S S 8 4 T I K F S h t i w m r e T e r a u q S l l a m S x e l F f o m m 9 1 2 1 n i 8 4 x e l F d e s s e r p m o c o N t a C o N...

Страница 28: ...ONFORM MENTAUXINSTRUCTIONSDUFABRICANTET TOUTES EXIGENCES ET CODES APPLICABLES DE L AUTORIS SAVOIRLAJURIDICTION SIL INFORMATION DANS CETTE INSTRUCTION N EST PAS SUIVIE EXACTEMENT UN FEU EXPLOSION OU PR...

Страница 29: ...ns do not use pipe joint compounds on flare fittings Step 10 Attach the conversion label provided in the conversion kit to the rating plate on the appliance Step 11 Turn on gas supply and test for gas...

Страница 30: ...30 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE NOTE THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 31: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 31 NOTE THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 32: ...0 043M REV E 06 2008 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products C...

Отзывы: