background image

24

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Figure 40

Door
Assembly

Gas Line Access Panel

Bottom Panel

Burner
Assembly

Figure 42 -

Figure 41

INSTALLING THE GLASS DOOR

ELECTRONIC

Pilot
Hood

Sensor

Ignitor

MILLIVOLT

Thermocouple

Hood

Ignitor Rod

3/8" Min
(9 mm)

Thermopile

Pilot
Nozzels

Step 6. INSTALLING THE LOGS, GLOW-
ING EMBERS AND VOLCANIC STONES

Step 7. CHECKING APPLIANCE OPERATION

 With gas line installed run initial system check-
out before closing up the front of the unit.
Follow the pilot lighting instructions provided
in the Homeowner's Care and Operation In-
structions. For piezo ignitor location see

 Fig-

ure 39 on page 23 (millivolt appliances only).

Note: Lighting Instructions are also found on
the literature tag tied to the gas piping next to
the gas valve. To access the tag, open the
lower control compartment door (Figure 39 on
page 23 ) 
by pulling the panel forward.

When first lighting the appliance, it will take
a few minutes for the line to purge itself of
air. Once purging is complete, the pilot and
burner will light and operate as indicated in
the instruction manual. Subsequent lighting
of the appliance will not require such purg-
ing. Inspect the pilot flame (remove logs, if
necessary, handling carefully).

Proper log and twig placement is critical to
encourage outstanding flame appearance and
prevent sooting.  These fires are designed to
provide a rich orange/red glow on the logs.
Ensure the bottom of the rear log is fully seated
and pulled as far forward as the pins will al-
low.  Refer to the Log Set Placement
Supplement
 for detailed instructions.

Note: Log setup is by design asymmetric.  The
fire is intentionally positioned off center to
provide a natural fire look.

The logs are packaged in a carton located
within the firebox. One plastic bag of glowing
embers and volcanic stones are located in the
bottom compartment. Refer to the Log Set
Placement Supplement
 for detailed place-
ment instructions for the logs, glowing em-
bers and volcanic stones.

Remove the gas line access plate and gasket
from the provided plastic bag and install them
over the opening, using the provided screws
(4) as shown in 

Figure 39.

Refer to 

Figure 43  and loosen the set screw

for the venturi air shutter.  Manually actuate
the air shutter through several cycles.  Set the
air shutter to 3/32" before placing the logs.

Millivolt Appliance Checkout

The pilot flame should be steady, not lifting or
floating. Flame should be blue in color with
traces of orange at the outer edge.

The top 3/8" (10 mm) at the pilot generator
(thermopile) and the top 1/8" min (tip) of the
quick drop out thermocouple should be en-
gulfed in the pilot flame.

The flame should project 1" (25 mm) beyond
the hood at all three ports 

(Figure 40 ).   Re-

place logs if removed for pilot inspection.

To light the burner; turn “ON” the remote wall
switch and rotate the gas valve control knob
counterclockwise to the “ON” position (“ON”
will be at the bottom side of the valve).

WARNING: HANDLE THIS GLASS WITH
EXTREME CARE! THE GLASS PANEL IS
SUSCEPTIBLE TO DAMAGE — DO NOT
SCRATCH WHILE HANDLING OR WHILE
RE-INSTALLING THE GLASS DOOR
FRAME.

Step 8. INSTALLING THE GLASS DOOR
AND OPTIONAL HOOD

To access the glass door securing latches,
first open the lower control compartment
door (

Figure 42 ) by lifting and pulling the

bottom panel forward.

Retrieve the glass door. Visually inspect the
gasket on the backside of the frame. Gasket
surface must be clean, free of irregularities and
seated firmly.

Position the door in front of the firebox opening
with the bottom of the door held away from the
fireplace 

(Figure 42 ).  Hook the top flange of

the door frame over the top of the firebox frame.
Let the bottom of the door frame swing gently
in towards the fireplace ensuring that the gas-
ket seats evenly as the door frame draws shut.
Fasten the two latches located underneath the
firebox floor to the door's vee-flange. Close
both the latches securely.

If desired, install the optional hood.  Note the
location of the three clips inside the top air
channel above the door.  The clips are equally
spaced on the top surface of the air channel
opening.  Use a screwdriver to open the clips
slightly if needed.  Engage the back edge of the
eyebrow into the clips to secure.

Electronic Appliance Checkout
To light the burner, turn ‘ON’ the unit mounted
On/Off switch or the optional remote wall
switch.  Ensure the ignitor lights the pilot.  The
pilot flame should engulf the flame rod as
shown in 

Figure 41.

Содержание Merit Plus MPLDV-30NE

Страница 1: ...nes se trouvant dans le batiment o vous vous trouvez Evacuez la pi ce le b timent ou la zone Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si v...

Страница 2: ...the bottom compartment 4 One vent restrictor to be used as detailed on page 10 5 One hood and one control compartment cover and one 45 degree starter elbow are strapped to the top of the unit GENERAL...

Страница 3: ...ove 4500 ft For elevations above 4500 feet 1372 meters install the unit according to the regulations of the local authorities having jurisdictionand intheUSA thelatestedition of the National Fuel Gas...

Страница 4: ...m 6 2 6 1 n i 4 6 T N E V m m 4 5 2 n i 1 S E C N A R A E L C E C I V R E S T N O R F s r e t e m 9 0 t e e F 3 Shelf Height see table Do not insulate the space between the appliance and the area abo...

Страница 5: ...nwealth of Massachusetts hori zontal terminations installed less than seven 7 feet above the finished grade must comply with the following additional requirements A hard wired carbon monoxide detector...

Страница 6: ...b Electronic Appliances Connect 120 Vac electrical power to the appliance receptacle Step 5 page 22 Make connection to gas supply Step 6 page 23 Install the logs and glow ing embers Step7 page23 Chec...

Страница 7: ...o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e...

Страница 8: ...1 1 8 0 7 1 7 0 2 1 2 9 4 4 5 8 Note Venting requirements for corner installations the horizontal vent length a to b must not exceed 28 inches 711 mm Inches millimeters These dimensions occur when one...

Страница 9: ...1 3 5 9 4 3 5 3 1 6 8 6 7 2 0 5 1 5 2 2 9 6 5 3 V D L P M n i 2 1 0 4 2 1 7 3 8 5 0 2 8 1 9 2 4 1 5 3 4 3 4 2 8 3 2 1 4 1 7 2 m m 9 2 0 1 3 5 9 4 3 5 0 4 7 5 9 8 9 2 6 4 1 3 2 9 6 0 4 V D L P M n i 2...

Страница 10: ...SYSTEMS ROOF Figures 13 17 and 23 through 25 on pages 12 14 and 15 and their associated Vertical Vent Tables illustrate the various vertical vent ing configurations that are possible for use with the...

Страница 11: ...6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1 1 0 0 6 0 7 5 7 1 2 5 2 1 8 1 0 1 0 6 0...

Страница 12: ...r to Figure 15 Push the vent component against the starter elbow until it fully engages then twist the component clockwise running the dimples down and along the incline channels until they seat at th...

Страница 13: ...5 and SV4 5E90 elbows in the same manner as the straight vent sections The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with...

Страница 14: ...10 15 4 572 3 0 914 20 6 096 4 1 219 V H 40 feet 12 2 m Max H 20 feet 6 096 meters Max meters 40 feet 12 2 meters Maximum Ceiling Firestop Spacer SV4 5VF When using Secure Flex use Firestop Spacer SF4...

Страница 15: ...es covered in this document are fittedwithcollarshavinglockinginclinedchan nels The dimpled end of the vent components fit over the appliance collar to create the posi tive twist lock connection C Pla...

Страница 16: ...ot run ratios that are smallerareacceptableallthewaydowntoator near level Use a carpenter s level to measure fromaconstantsurfaceandadjustthesupport straps as necessary It is important to maintain the...

Страница 17: ...coping vent section elbow as shown in Figure 27 in the same manner as any SV4 5 vent component refer to Step F N Install Firestop Spacer at exterior wall When using the square termination install the...

Страница 18: ...c s e l e T d n a t i K n o i t a n i m r e T n i 2 1 7 o t 2 A L 5 4 V S n o i t c e S 6 L 5 4 V S n o i t c e s t n e v n i 6 2 0 5 o t 9 7 2 4 3 9 1 o t 1 1 Note SV4 5VF Secure Vent SF4 5VF Secure...

Страница 19: ...p Spacer SV4 5HF or SF4 5HF when using Secure Vent or Secure Flex respectively Use Firestop Spacer SV4 5HF5 or SF4 5HF5 when using Secure Vent or Secure Flex on horizontal vent runs for the MPLDV35 40...

Страница 20: ...rapper surface In all cases the firestop spacer provided with the termination may be used with the termination frame to 5 clearance where applicable HORIZONTAL VENT FIGURES TABLES CONTINUED Figure 33...

Страница 21: ...ex Pipe 1 Installthesmall gearclamplooselyaroundthe innerflexibleventpipe pushitbackoutoftheway 2 Apply a bead of Mill Pac Black 700 F high temperature sealant Catalog No 10K81 to the inner adapter co...

Страница 22: ...the appliance junction box 2 Remove the electrical inlet cover plate from the side of the unit by removing the plate s securing screws See Figure 11 on page 9 3 Removethe coverplate sknockoutandthen f...

Страница 23: ...rd pipe and tighten with wrenches from above through the firebox opening If required access the valve by removing the lower control compartment panel see Figure 39 by lifting and pulling the panel for...

Страница 24: ...4 as shown in Figure 39 Refer to Figure 43 and loosen the set screw for the venturi air shutter Manually actuate the air shutter through several cycles Set the air shutter to 3 32 before placing the...

Страница 25: ...R SHUTTER MOVES WHEN THE LEVER ARM IS OPERATED Note When first operating the air shutter adjustment lever arm observe the air shutter If it is not moving open the glass ensure the air shutter screw is...

Страница 26: ...8 203 MANTEL 6 152 MANTEL 4 102 MANTEL 18 457 14 356 12 305 2 51 MANTEL TOP OF APPLIANCE 8 203 10 254 MANTEL CLEARANCES Inches mm 16 406 Figure 45 COLD CLIMATE INSULATION For cold climate installatio...

Страница 27: ...S x e l F f o m m 4 1 9 n i 6 3 x e l F d e s s e r p m o c 8 0 L 4 9 S S 8 4 T I K F S h t i w m r e T e r a u q S l l a m S x e l F f o m m 9 1 2 1 n i 8 4 x e l F d e s s e r p m o c o N t a C o N...

Страница 28: ...ONFORM MENTAUXINSTRUCTIONSDUFABRICANTET TOUTES EXIGENCES ET CODES APPLICABLES DE L AUTORIS SAVOIRLAJURIDICTION SIL INFORMATION DANS CETTE INSTRUCTION N EST PAS SUIVIE EXACTEMENT UN FEU EXPLOSION OU PR...

Страница 29: ...ns do not use pipe joint compounds on flare fittings Step 10 Attach the conversion label provided in the conversion kit to the rating plate on the appliance Step 11 Turn on gas supply and test for gas...

Страница 30: ...30 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE NOTE THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 31: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 31 NOTE THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 32: ...0 043M REV E 06 2008 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products C...

Отзывы: