NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

13

Maintain a minimum 1" (25 mm) clearance
to combustible materials for all vertical
vent elements.

Clearances for horizontal vent elements are
1" (25 mm) at the sides and 1" (25 mm) on
the bottom.  Clearances above horizontal
vent elements are 3" (76 mm) for all models
and all applications.  

Exception:  Clearance

is 5" (127 mm) for MPLDV35, MPLDV40 &
MPLDV45, when the center line of the hori-
zontal run is less than 48" (1219 mm) above
the fireplace top wrapper surface.

Framing Dimensions for Roof

Pitch

C

D

0/12

10-1/2 in.

10-1/2 in.

(267 mm)

(267 mm)

6/12

10-1/2 in.

12 in.

(267 mm)

(305 mm)

12/12

10-1/2 in.

17-3/4 in.

(267 mm)

(451 mm)

Figure 19

Figure 20

Figure 22

Figure 21

If the vent system extends more than 5' (1.5
m) above the roof flashing, stabilizers may be
necessary. Additional screws may be used at
section joints for added stability. Guide wires
may be attached to the joint for additional
support on multiple joint configurations.

I. Continue installation of horizontal/inclined
sections -
 Continue with the installation of the
straight vent sections in horizontal/inclined
run as described in Step E. Install support
straps every 5' (1.52 m) along horizontal/
inclined vent runs using conventional plumber’s
tape. It is very important that the horizontal/
inclined run be maintained in a straight (no
dips) and slightly elevated plane in a direc-
tion away from the fireplace 
1/4" per foot (20
mm per meter) which is ideal, though rise per
foot run ratios that are smaller are acceptable
all the way down to at or near level.

It is important to maintain the required clear-
ances to combustibles at the top and bottom
for all horizontal/inclined runs.

Loop the tape around the vent, securing the
ends of the tape to the framing. If desired,
sheet metal screws #6 x 1/2" length may be
used to secure the support straps to the vent
pipe.  Refer to 

Figure 17.

H. Change vent direction to horizontal/in-
clined run -
 At transition from or to a horizon-
tal/inclined run, install the SV4.5E45 and
SV4.5E90 elbows in the same manner as the
straight vent sections.  The elbows feature a
twist section to allow them to be routed about
the center axis of their initial collar section to
align with the required direction of the next
vent run element. Twist elbow sections in a
clockwise direction only so as to avoid the
possiblity of unlocking any of the previously
connected vent sections.
 See 

Figure 18.

Figure 18

SV4.5E90

(90

°

 Elbow)

8-1/8"

(206 mm)

Swivel Joint

(360

°

 swivel)

4-13/16"

(122 mm)

SV4.5E45

(45

°

 Elbow)

Swivel Joint

(360

°

 swivel)

C

D

Storm

Collar

H. Frame roof opening - Identify location for
vent at the roof. Cut and/or frame opening per
Roof Framing Chart and 

Figure 19.

L. Install the vertical termination - The final step
involves installation of the SV4.5CGV-1 Vertical
Termination.  Extend the vent sections to the
height as shown in the "Vertical vent termination
section" on page 6.  The SV4.5CGV-1 Vertical
Termination (

Figure 22 ) installs in the exact

same fashion as any other Secure Vent section.
Align the termination over the end of the previ-
ously installed section, adjusting the radial align-
ment until the four locking dimples of the termi-
nation are aligned with the inlets of the four
incline channels of the last vent section.  Push the
termination down until it fully engages, then twist
the termination clockwise running the dimples
down and along the incline channels until they
seat at the end of the channels.

J. Install the roof flashing - Extend the vent
sections through the roof structure. Install the
roof flashing over the vent section and posi-
tion such that the vent column rises vertically
(use carpenters level) (

Figure 20 ). Nail along

perimeter to secure flashing or adjust roofing
to overlap the flashing edges at top and sides
only and trim where necessary. Seal the top
and both sides of the flashing with waterproof
caulking.

K. Install the storm collar - Install the storm
collar, supplied with the flashing, over the
vent/flashing joint.  See 

Figure 21.  Loosen

the storm collar screw. Slide collar down until
it meets the top of the flashing. Tighten the
adjusting screw. Apply non-combustible caulk-
ing or mastic around the circumference of the
joint to provide a water tight seal.

Содержание Merit Plus MPLDV-30NE

Страница 1: ...nes se trouvant dans le batiment o vous vous trouvez Evacuez la pi ce le b timent ou la zone Appelez imm diatement votre fournisseur de gaz depuis un voisin Suivez les instructions du fournisseur Si v...

Страница 2: ...the bottom compartment 4 One vent restrictor to be used as detailed on page 10 5 One hood and one control compartment cover and one 45 degree starter elbow are strapped to the top of the unit GENERAL...

Страница 3: ...ove 4500 ft For elevations above 4500 feet 1372 meters install the unit according to the regulations of the local authorities having jurisdictionand intheUSA thelatestedition of the National Fuel Gas...

Страница 4: ...m 6 2 6 1 n i 4 6 T N E V m m 4 5 2 n i 1 S E C N A R A E L C E C I V R E S T N O R F s r e t e m 9 0 t e e F 3 Shelf Height see table Do not insulate the space between the appliance and the area abo...

Страница 5: ...nwealth of Massachusetts hori zontal terminations installed less than seven 7 feet above the finished grade must comply with the following additional requirements A hard wired carbon monoxide detector...

Страница 6: ...b Electronic Appliances Connect 120 Vac electrical power to the appliance receptacle Step 5 page 22 Make connection to gas supply Step 6 page 23 Install the logs and glow ing embers Step7 page23 Chec...

Страница 7: ...o t a l u g e r r e t e m t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e e f 3 y l b m e s s a r o t a l u g e r r e t e m e h t e v o b a t e e f 5 1 f o t h g i e h a n i h t i w m c 1 9 t e...

Страница 8: ...1 1 8 0 7 1 7 0 2 1 2 9 4 4 5 8 Note Venting requirements for corner installations the horizontal vent length a to b must not exceed 28 inches 711 mm Inches millimeters These dimensions occur when one...

Страница 9: ...1 3 5 9 4 3 5 3 1 6 8 6 7 2 0 5 1 5 2 2 9 6 5 3 V D L P M n i 2 1 0 4 2 1 7 3 8 5 0 2 8 1 9 2 4 1 5 3 4 3 4 2 8 3 2 1 4 1 7 2 m m 9 2 0 1 3 5 9 4 3 5 0 4 7 5 9 8 9 2 6 4 1 3 2 9 6 0 4 V D L P M n i 2...

Страница 10: ...SYSTEMS ROOF Figures 13 17 and 23 through 25 on pages 12 14 and 15 and their associated Vertical Vent Tables illustrate the various vertical vent ing configurations that are possible for use with the...

Страница 11: ...6 6 8 1 5 5 1 0 0 0 0 4 4 5 0 9 1 5 7 8 5 1 1 0 0 0 4 5 5 6 9 1 5 7 3 6 1 0 1 0 0 4 5 5 5 0 2 5 2 1 7 1 0 1 1 5 0 7 7 0 2 5 2 7 1 0 0 0 6 0 6 5 1 1 2 5 2 6 7 1 1 0 0 6 0 7 5 7 1 2 5 2 1 8 1 0 1 0 6 0...

Страница 12: ...r to Figure 15 Push the vent component against the starter elbow until it fully engages then twist the component clockwise running the dimples down and along the incline channels until they seat at th...

Страница 13: ...5 and SV4 5E90 elbows in the same manner as the straight vent sections The elbows feature a twist section to allow them to be routed about the center axis of their initial collar section to align with...

Страница 14: ...10 15 4 572 3 0 914 20 6 096 4 1 219 V H 40 feet 12 2 m Max H 20 feet 6 096 meters Max meters 40 feet 12 2 meters Maximum Ceiling Firestop Spacer SV4 5VF When using Secure Flex use Firestop Spacer SF4...

Страница 15: ...es covered in this document are fittedwithcollarshavinglockinginclinedchan nels The dimpled end of the vent components fit over the appliance collar to create the posi tive twist lock connection C Pla...

Страница 16: ...ot run ratios that are smallerareacceptableallthewaydowntoator near level Use a carpenter s level to measure fromaconstantsurfaceandadjustthesupport straps as necessary It is important to maintain the...

Страница 17: ...coping vent section elbow as shown in Figure 27 in the same manner as any SV4 5 vent component refer to Step F N Install Firestop Spacer at exterior wall When using the square termination install the...

Страница 18: ...c s e l e T d n a t i K n o i t a n i m r e T n i 2 1 7 o t 2 A L 5 4 V S n o i t c e S 6 L 5 4 V S n o i t c e s t n e v n i 6 2 0 5 o t 9 7 2 4 3 9 1 o t 1 1 Note SV4 5VF Secure Vent SF4 5VF Secure...

Страница 19: ...p Spacer SV4 5HF or SF4 5HF when using Secure Vent or Secure Flex respectively Use Firestop Spacer SV4 5HF5 or SF4 5HF5 when using Secure Vent or Secure Flex on horizontal vent runs for the MPLDV35 40...

Страница 20: ...rapper surface In all cases the firestop spacer provided with the termination may be used with the termination frame to 5 clearance where applicable HORIZONTAL VENT FIGURES TABLES CONTINUED Figure 33...

Страница 21: ...ex Pipe 1 Installthesmall gearclamplooselyaroundthe innerflexibleventpipe pushitbackoutoftheway 2 Apply a bead of Mill Pac Black 700 F high temperature sealant Catalog No 10K81 to the inner adapter co...

Страница 22: ...the appliance junction box 2 Remove the electrical inlet cover plate from the side of the unit by removing the plate s securing screws See Figure 11 on page 9 3 Removethe coverplate sknockoutandthen f...

Страница 23: ...rd pipe and tighten with wrenches from above through the firebox opening If required access the valve by removing the lower control compartment panel see Figure 39 by lifting and pulling the panel for...

Страница 24: ...4 as shown in Figure 39 Refer to Figure 43 and loosen the set screw for the venturi air shutter Manually actuate the air shutter through several cycles Set the air shutter to 3 32 before placing the...

Страница 25: ...R SHUTTER MOVES WHEN THE LEVER ARM IS OPERATED Note When first operating the air shutter adjustment lever arm observe the air shutter If it is not moving open the glass ensure the air shutter screw is...

Страница 26: ...8 203 MANTEL 6 152 MANTEL 4 102 MANTEL 18 457 14 356 12 305 2 51 MANTEL TOP OF APPLIANCE 8 203 10 254 MANTEL CLEARANCES Inches mm 16 406 Figure 45 COLD CLIMATE INSULATION For cold climate installatio...

Страница 27: ...S x e l F f o m m 4 1 9 n i 6 3 x e l F d e s s e r p m o c 8 0 L 4 9 S S 8 4 T I K F S h t i w m r e T e r a u q S l l a m S x e l F f o m m 9 1 2 1 n i 8 4 x e l F d e s s e r p m o c o N t a C o N...

Страница 28: ...ONFORM MENTAUXINSTRUCTIONSDUFABRICANTET TOUTES EXIGENCES ET CODES APPLICABLES DE L AUTORIS SAVOIRLAJURIDICTION SIL INFORMATION DANS CETTE INSTRUCTION N EST PAS SUIVIE EXACTEMENT UN FEU EXPLOSION OU PR...

Страница 29: ...ns do not use pipe joint compounds on flare fittings Step 10 Attach the conversion label provided in the conversion kit to the rating plate on the appliance Step 11 Turn on gas supply and test for gas...

Страница 30: ...30 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE NOTE THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 31: ...NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE 31 NOTE THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 32: ...0 043M REV E 06 2008 Lennox Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products C...

Отзывы: