NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

8

Figure 16

Air Duct

Air Inlet

Clamps

Note: Air Inlet
Must Be Free Of
Any Obstructions

Install as follows:

Connect the 4" (102 mm) Class 0 air duct 
provided, to the collar on the fi replace with the 
clamps provided in the kit’s hardware package 
(

Figure 16)

.

Route the Class 0 metallic air duct out the back 
wall or side wall, up through the ceiling or fl oor 
joists to an outside wall.  

The air duct’s inlet 

should be located above any anticipated 
snow level.

 Check local building codes for any 

restrictions.  We recommend that the inlet be 
at least 4 feet above grade level. 

Note:

  Air inlet ducts must not terminate in 

attic space.

Figure 17

3 Feet

Duct Hole Framing:

Cut or frame a hole through the outside of the 
enclosure for the installation of the duct inlet 
hood. A 5" (127 mm) diameter hole is required. 
Feed the loose end of the fl exible duct through 
the hole cut for the inlet hood and attach to the 
collar on the inlet hood using two (2) screws. 
Insert the hood into the opening. Secure in 
place with nails driven through the holes in 
hood fl ange. Seal with noncombustible water-
proof silicon type caulking. If additional duct 
is needed, use Class 0 metallic air duct (

refer 

to

 Figure 16

)

.

Outside Air Kit (provided)

Required on all Outdoor installations
Optional on  Indoor installations

Outside Air Kit Installation (provided)

These appliances are equipped with a com-
bustion air inlet collar so that it is possible to 
duct combustion air from the outdoors to the 
fi rebox. To accomplish an outside air hook-
up, use only the 

Outside Air Kit

 provided with 

these appliances.  These kits come complete 
with all components necessary in completing 
a combustion air vent system.

Indoor Installations -

 An Air Gate Kit must be 

installed prior to the installation of the Outside 
Air Kit (purchased separately - see 

Page 23

 for 

ordering information). 

Outdoor Installations -

 Units installed outdoors 

are required to have the Outside Air Kit  (pro-
vided) installed without the Air Gate Kit.  The 
optional Air Gate Kit is not approved on outdoor 
installations.

Note:

 Secure the duct hood to a vertical post 

with the inlet positioned downward. Ensure that 
nothing blocks the hood opening. This duct 
must never terminate higher than 3 feet below 
the fi replace termination (

Figure 17

)

.

Air Inlet

(duct hood)

       CAUTION 

Avoid installing the air inlet 
where the opening could be 
blocked by snow, bushes or 
other obstacles.  The maximum 
height for the outside air is 50 
feet above the hearth, provid-
ing the air inlet is terminated a 
minimum of three (3) feet below 
the chimney cap level.

       ATTENTION 

Évitez d’installer la prise d’air ou 
l’ouverture pourrait etre bloquee 
par la neige, les buissons ou 
d’autres obstacles.  La hauteur 
maximum pour la prise d’air est 
de 50 pi. Au dessus de la base du 
foyer à condition qu’elle se situe 
à au moins 3 pi. En dessous de 
la sortie de la cheminée.

Содержание Merit Plus MP-420D

Страница 1: ...EQUIPPED TO BE READILY IN STALLED OUTDOORS IF INSTALLED INDOORS YOU MUST INSTALL THE COMBUSTION AIR COVER PROVIDED WITH THE INSTALLATION KIT OR PURCHASE THE OPTIONAL OUTSIDE AIR KIT GATE OAKG OD SEE...

Страница 2: ...tate and national codes and regulations 3 ThisfireplacemustbeinstalledwithSecurity Chimneys FTF8 8 203mm inside diam eter Chimney System only This fireplace is intendedforindoororoutdoorinstallations...

Страница 3: ...always maintain minimum clearances to combustible materials and do not violate any specific installation requirements These fireplaces have been tested and listed by OMNI Test Laboratories Inc Report...

Страница 4: ...materials Outdoor installations less than 15 height require chimney clearance of 2 air space to insulation and construction materials In Canada the chimney and fireplace outer wrapper require a minimu...

Страница 5: ...kept within the shaded areas illustrated in Figure 7 CLEARANCES Minimum clearance to combustibles for the appliance is as follows sides and back 1 25 mm floor 0 0mm adjacentwall 12 305 mm ceiling 37 1...

Страница 6: ...t If you plan to raise the fireplace and hearth extension build the platform assembly then position fireplace and hearth extension on top Secure the platform to the floor to prevent possible shifting...

Страница 7: ...the outside air kit is NOT installed you must install the Outside Air Cover provided with the instructions kit b IfanoutsideairkitISinstalled theOutside Air Kit Gate must be installed see Page 23 of o...

Страница 8: ...ons Outside Air Kit Installation provided These appliances are equipped with a com bustion air inlet collar so that it is possible to duct combustion air from the outdoors to the firebox To accomplish...

Страница 9: ...g Materials if any Rough Framing Face Unfinished Shown Combustion Air Kit Optional Framing Dimensions A 46 1 2 1181 mm B1 43 1 2 1105 mm B2 60 1 2 1537 mm C 33 828 mm D 17 1 2 445 mm E 76 1 4 1937 mm...

Страница 10: ...ions must not interfere with circulating grillwork Figure 19 Figure 20 A B Ceiling Framing C D Roof Framing Framing Dimensions for Ceiling Inches millimeters Flue Type A B FTF8 Vertical USA 14 1 2 368...

Страница 11: ...les espaceurs du dessus du foyer voir le sch ma 13 ne peuvent tre retir es ou modifi es vous ne pouvez pas entaillez le colombage pour ajuster autour ou tre install plus bas que les espaceurs Le colom...

Страница 12: ...and outer wrapper require a minimum 2 air space to insulation and construction materials Reference Figures 19 20 and charts Framing DimensionsforCeilingandRoof whichspecify minimum ceiling and roof di...

Страница 13: ...e the building must be con structed with galvalume outer sections only Theappropriatemodeldesignationsarelocated in the back of this manual F8FS30 Firestop Spacer FTF8 S4 Stabilizer 1 Min Air Space 30...

Страница 14: ...as noted in Step 4 Step 6 Select the proper Security Chimneys roof flashing based on pitch of roof Use chart below for selection Figure 37 Note Do not caulk or seal the ventilating open ings or seal t...

Страница 15: ...chimney must be at least 2 above this reference point In all cases thechimneycannotbelessthen3 above the roof at the edge of the chimney The 2 in 10 rule is necessary in the interest of safety but doe...

Страница 16: ...36 48 11 0 11 1 0 0 0 17 1 5 0 1 0 0 21 1 9 2 0 0 0 27 2 3 1 1 0 0 35 2 11 0 0 1 0 47 3 11 0 0 0 1 51 4 3 0 1 1 0 57 4 9 1 0 0 1 63 5 3 0 1 0 1 67 5 7 2 0 0 1 73 6 1 1 1 0 1 81 6 9 0 0 1 1 93 7 9 0 0...

Страница 17: ...the Straight Up In stallation Instructions for cutting and framing ceiling and roof openings Note See Framing and Dimension Chart for the sizes of the ceiling and roof openings The size of the roof op...

Страница 18: ...ilizer Considerthiswhen determining the need for a stabilizer Note Do not apply excessive pressure to any subsequent chimney section following return elbow assembly when installing Ensure that each su...

Страница 19: ...c tions are placed lower than 18 inches from the fireplace opening These fireplaces have been marked with a maximum rating of 26 000 BTU to assure that homeowners do not exceed the allowable limits fo...

Страница 20: ...ux non combustibles il se pourrait qu il n y ait pas suffisament de d gagement pour installer les portes de verre de votre choix Assurez d avoir un d gagmet suf fisant tout moment afin de ne pasinterf...

Страница 21: ...es 416 x 1 Answer TheminimumrequiredthicknessoftheMicore160is 417 there fore round up to nearest standard thickness available which is 1 2 Using the r formula Note To convert inches to millimeters div...

Страница 22: ...ormal wall decor with elaborate mantels to rustic wood paneling or warm brick facings Only noncombustible materials like stone tile brick etc may overlap the black front facing Do not extend these mat...

Страница 23: ...ith fireplace Shownhereforre placement purposes only Locking Band 63L60 FLB Ref Form 750 080M Spark Arrester 63L57 FSA 2 Ref Form 750 198M INSTALLATION COMPONENTS The following items are available for...

Страница 24: ...n For open top shrouds 96L20 FTF8 CTT Ref Form 750 077M Chimney Pack conventional Convenience Pack Residential 63L70 FTF8 CP7 Contains 3 FTF8 36 1 F8FS 1 F8F6 1 FTF8 CTD 7 P C 8 F T F R O I R E P U S...

Отзывы: